Page 3 - Table 1 — Physical Data — 50PCH,PCV Units; CAUTION
3 or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof mate- rial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper star...
Page 4 - UNIT HANGER DETAIL; Fig. 1 — 50PCH Unit Dimensions
4 F RIGHT RETURN S TRAIGHT DI S CHARGE FRONT L N O M RIGHT RETURN FRONT LEFT/ S TRAIGHT DI S CHARGE C S P BACK DI S CHARGE CONDEN S ATE 3 / 4" FPT 3 . 3 " [ 83 . 8 MM] 0.7" [17. 8 MM] FRONT-VIEW E D K J 2 1 1.1 [27.9 MM] A CAP B S P RIGHT RETURN RIGHT VIEW - AIR COIL OPENING AIR COIL C T...
Page 5 - Fig. 2 — Typical Installation — 50PCH Units; UNIT HANGER ISOLATION DETAIL
5 AccessoryElectric Heat(if applicable) Filter Access Return Loop Supply Loop Water OutWater In Integral hanger support-pre-attached in factory Field-supplied transition tominimize pressure loss 3/8" threaded rods (by others) Return Air(Ductworknot shown) Thermostat Wiring Power Wiring Balancing...
Page 6 - Fig. 3 — 50PCV Unit Dimensions
6 ACCE SS PANEL S TOP VIEW-LEFT RETURN U R S I S OMETRIC VIEW LEFT RETURN LEFT VIEW - AIR COIL OPENING T C POWER S UPPLY 3 /4" [19.1 MM] HV KNOCKOUT LOW VOLTAGE 1/2" [12.7 MM] LV KNOCKOUT LOW VOLTAGE 1/2" [12.7 MM] LV KNOCKOUT CONDEN S ATE 3 /4" FPT FRONT-VIEW K 1.00 [25.4 MM] F J H ...
Page 7 - Step 3 — Locate Unit —; Fig. 4 — Typical Vertical Installation of 50PCV Unit; Side Discharge to Back Discharge
7 Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for a WSHP:• Units are for indoor use only.• Locate in areas where ambient temperatures are between 40 F and 100 F and relative humidity is no greater than 75%. • Provide sufficient space for water, elect...
Page 8 - Fig. 7 — Horizontal Hanger Bracket; COMPRE; Fig. 8 — 50PCV Unit Mounted with
8 Side to Back Discharge Conversion 1. Remove screws to free the top and discharge panels. See Fig. 5. 2. Remove the access panel and set aside.3. Lift the discharge panel from side of unit and rotate it to back using care not to damage blower wiring. 4. Check blower wire routing and connections for...
Page 9 - Step 7 — Pipe Connections —; Table 2 — Metal Hose Minimum Bend Radii; NOTE: Unit does not need to be sloped toward drain.; Fig. 11 — Vertical Condensate Connection
9 Each unit must be installed with its own individual vent and means to flush or blow out the condensate drain line. Do not in- stall units with a common trap or vent.VENTING — Install a vent in the condensate line of any application that may allow dirt or air to collect in the line. Con- sider the ...
Page 15 - with Deluxe
15 D elux e D NO TES : 1. Compressor a nd b lo w er moto r ther mally prote c ted inter nally . 2 . A ll wir ing t o th e u n it m u st co mply wit h NEC and local code s . 3 . T ra n sf or me r is wired t o 4 60-v BLK /RED lead f o r 4 60-3 -60 unit s . T rans- fo rm er is e nerg y limit ing or ma ...
Page 16 - WH
16 WH S P-OPEN F S D Fig. 1 8 — Unit s wi th Comple te C a n d WS HP Ope n Mul tiple Protoc ol C o nt rols A50-8697 LEGEND BM — Blo w e r Motor BR — Bl o w e r Rela y CO — Cond ensate Ov erflo w FSD — F ir e S m ok e D e te ct o r LW T — Lea ving W a ter T e mper ature N.C . — Nor m ally Closed OA D...
Page 18 - — WSHP Op
18 01220 7- 1 B T 4 8 5BT LED 1 DB In s t a ll B T 4 8 5 where de vi ce i s loc a ted a t the en d o f n e twork s eg me nt o n ly . + 24 v a c (If n o t in s t a lled , it m us t b e con nect ed to DO-5) DE HUMIDIFY OUTP U T CO NTA C T (D O-6) (F A C TORY O P TION ) FA N S PE ED (DO -7 ) (M ED OR L...
Page 19 - Table 3 — 50PCH,PCV Unit Electrical Data; Fig. 21 — Typical Single-Phase Line Voltage Power Connection
19 Table 3 — 50PCH,PCV Unit Electrical Data LEGEND *Units using 460-v and ECM (electronically commutated motor), modulatingHWR (hot water reheat), and/or internal secondary pump will require a neutralwire from the supply side in order to feed accessory with 265-v.NOTES: 1. HACR circuit breaker in U....
Page 20 - Step 9 — Wire Field Controls; only; NOTE: Low voltage connector may be removed for easy installation.; TERMINAL STRIP P2
20 Step 9 — Wire Field Controls THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the Aquazone™ control board. See Fig. 13-20, and 22. WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory set...
Page 21 - view; WARNING; OUTER JACKET
21 WSHP OPEN WIRING — The WSHP Open controller will be factory wired to the Complete C or Deluxe D control board, however, the system wiring will need to be completed utilizing WSHP Open controller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation includes harness, LW...
Page 22 - System Checkout —; Table 8 — 50PCV Blower Performance with; COIL FACE VELOCITY; CONNECT THE BLUE WIRE TO:; Fig. 28 — Blower Speed Selection
22 Wiring a Supply Air Temperature (SAT) Sensor — The SAT sensor is required for reheat applications. If the cable used to wire the SAT sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shiel...
Page 25 - Operating Limits; When the disconnect switch is closed, high voltage is
25 Table 11 — DIP Switch Block S2 — Accessory 1 Relay Options LEGEND NOTE: All other DIP switch combinations are invalid. Table 12 — DIP Switch Block S2 — Accessory 2 Relay Options LEGEND NOTE: All other switch combinations are invalid. Auto Dehumidification Mode or High Fan Mode — Switch 7 provides...
Page 26 - Table 13 — Operating Limits — 50PCH,PCV Units; Scroll Compressor Rotation —; Table 14 — Water Temperature Change; Dry Bulb
26 Table 13 — Operating Limits — 50PCH,PCV Units LEGEND Scroll Compressor Rotation — It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the prop- er direction: 1. Connect service gages to suction and discharge pressure ...
Page 31 - Display Interface
31 To start-up a unit with WSHP Open controls: 1. To plug in the BAC view 6 handheld display into a SPT sensor, point the two ears on the connector up and tilt the bottom of the plug toward you. Insert the plug up into the SPT sensor while pushing the bottom of the plug away from you. 2. BAC view 6 ...
Page 32 - Table 26 — Coaxial Water Pressure Drop; Antifreeze —
32 Flow Regulation — Flow regulation can be accom- plished by two methods. Most water control valves have a flow adjustment built into the valve. By measuring the pressure drop through the unit heat exchanger, the flow rate can be deter- mined. See Table 26. Adjust the water control valve until the ...
Page 33 - Table 28 — Antifreeze Percentages by Volume; OPERATION
33 the water loop. If an open type cooling tower is used continu- ously, chemical treatment and filtering will be necessary. Table 27 — Approximate Fluid Volume (gal.) per 100 Ft of Pipe LEGEND NOTE: Volume of heat exchanger is approximately 1.0 gallon. Table 28 — Antifreeze Percentages by Volume OP...
Page 36 - COMPLETE C AND DELUXE D BOARD
36 • The IAQ sensor reading is greater than the DCV start control set point.The control has four user adjustable set points: DCV start control set point, DCV maximum control set point, minimum damper position, and DCV maximum damper position.Two-Position OA Damper — The control can be configured to ...
Page 37 - Retry Mode —; Table 29 — Complete C Control Current LED
37 stage 2 followed by heating stage 2 then reduces capacity to heating stage 1. Operates for 1 minute per step.DEHUMIDIFICATION TEST — Tests dehumidification mode. Operates for 2 minutes.AUXILIARY HEATING TEST — Tests auxiliary heat. Sequences fan on and enables heating coil for 1 minute.H 2 O ECON...
Page 40 - Fig. 32 — Thermistor Nominal Resistance; Fig. 33 — FP1 and FP2 Thermistor Location; COAX —
40 Air Coil Fan Motor Removal Disconnect motor power wires from motor terminals before motor is removed from unit. 1. Shut off unit main power supply.2. Loosen bolts on mounting bracket so that fan belt can be removed. 3. Loosen and remove the 2 motor mounting bracket bolts on left side of bracket. ...
Page 41 - Table 32 — Troubleshooting
41 Table 32 — Troubleshooting LEGEND RV — Reversing Valve FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION Main Power Problems X X Green Status LED Off Check line voltage circuit breaker and disconnect. Check for line voltage between L1 and L2 on the contactor. Check for 24 vac between R and C on contr...
Page 43 - APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
43 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION LEGEND SCREEN NAME POINT NAME PASSWORD LEVEL EDITABLE RANGE DEFAULT NOTES Equipment Status Operating Mode No Password Required Off, Fan Only, Economize, Cooling, Heating, Cont Fan, Test, Start Delay, Dehumidify Displays unit operating mode SPT F Display...
Page 44 - APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
44 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PASSWORD LEVEL EDITABLE RANGE DEFAULT NOTES Unit Maintenance Operating Mode No Password required Off, Fan Only,Economize, Cooling, Heating, Cont Fan, Test, Start Delay, Dehumidify Displays unit operating mode Fan Ope...
Page 46 - APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
46 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PASSWORD LEVEL EDITABLE RANGE DEFAULT NOTES Configuration Unit Configuration Fan Mode Admin Password level access only X Auto/Continuous/ Always On Continuous Auto= Intermittant operation during both occupied and uno...
Page 52 - HEATING CYCLE ANALYSIS; = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE; SUBCOOLING; = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500094-01 Printed in U.S.A. Form 50PC-3SI CL-2 5-11A 3-11 Replaces: 50PC-2SI Copyright 2011 Carrier Corporation - - - - - - - - - - - - ...