Page 2 - LEGEND
2 Recognize safety information. This is the safety alert symbol ( ). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. GENERAL The Aquazone™ 50PSW water source heat pump (WSHP) is a single-package vertically mounted unit with electron...
Page 3 - cm
3 B C A M L K 2.5 cm 1 2 3 4 5 6 J H G F E D Req u ired S ervice Acce ss Option a l S ervice Acce ss 2.5 cm 4.6 cm 1 2 3 4 5 6 Req u ired S ervice Acce ss Option a l S ervice Acce ss B C A 3 . 3 cm 6.9 cm 1 8 .5 cm 4. 3 cm Fig. 1 — 50PSW036-120 Unit SIZES 036,060 LEGEND NOTES: 1. Dimensions shown in...
Page 4 - FPT —; Female Pipe Thread; CAUTION
4 PROTECTION — Once the units are properly positioned on the jobsite, they must be covered with either a shipping carton, vinyl film, or an equivalent protective covering. Open ends of pipes stored on the jobsite must be capped. This precaution is especially important in areas where painting, plaste...
Page 5 - not; Fig. 3 — Typical Water Loop System —
5 8. Remove any access panel screws that may be difficult to remove once unit is installed. Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for the WSHP:• Units are for indoor use only.• Provide sufficient space for water and electrical connections. • Lo...
Page 6 - Table 2 — Water Quality Guidelines
6 Table 2 — Water Quality Guidelines LEGEND *Heat exchanger materials considered are copper, cupronickel, 304 SS (stainless steel), 316 SS, titanium. †Closed recirculating system is identified by a closed pressurized piping system. **Recirculating open wells should observe the open recirculating des...
Page 7 - Step 6 — Wire Electrical Connections; Table 3 — 50PSW Electrical Data; WARNING
7 Step 6 — Wire Electrical Connections All field-installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC. Operatin...
Page 12 - Step 7 — Wire Low Voltage Connections; only; System Checkout —; Fig. 8 — Typical Field Wiring; Typical; Fig. 10 — Typical Aquazone Accessory Wiring
12 EXTERNAL LOOP POWER CONNECTION — If the unit is to be connected to an external loop pump or flow controller, connect the pump to the loop pump terminal block PB1. The maximum power handling is 4 amps at 240-v. The pumps will automatically cycle as required by the unit.220-V OPERATION — All 220/24...
Page 13 - Table 4 — DIP Switch Block S2 —
13 FIELD SELECTABLE INPUTS Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field. Complete C Control Jumper Settings (SeeFig. 4-6) WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low T...
Page 14 - Scroll Compressor Rotation —
14 Table 5 — DIP Switch Block S2 — Accessory 2 Relay Options LEGEND NOTE: All other DIP switch combinations are invalid. START-UP Use the procedure outlined below to initiate proper unit start-up.NOTE: This equipment is designed for indoor installation only. Operating Limits (See Table 6) ENVIRONMEN...
Page 15 - Table 7 — Heat Exchanger Pressure Drop; NOTE: Bold values indicate use of antifreeze is re; Cleaning and Flushing —; UNIT SIZE
15 Table 7 — Heat Exchanger Pressure Drop UNIT SIZES 036-120 UNIT SIZES 180,360 NOTE: Bold values indicate use of antifreeze is re q uired. Cleaning and Flushing — Cleaning and flushing of the piping system is the single most important step to ensure proper start-up and continued efficient operation...
Page 16 - per 30 M of Pipe; Table 9 — Antifreeze Percentages by Volume; Internal Pipe Size; CC; Fig. 11 — Test Mode Pins Location
16 Table 8 — Approximate Fluid Volume (L) per 30 M of Pipe LEGEND NOTE: Volume of heat exchanger is approximately 1.0 gallon(3.78 liters). Table 9 — Antifreeze Percentages by Volume Cooling Tower/Boiler Systems — These systems typically use a common loop maintained at 15.6 to 32.2 C. The use of a cl...
Page 17 - Retry Mode —; Table 10 — Complete C Control Current LED
17 Upon entering Test mode, the status LED (light-emitting di- ode) will flash a code representing the last fault. For diagnostic ease at the thermostat, the alarm will also cycle during Test mode. The alarm relay will cycle on and off similar to the sta- tus LED to indicate a code representing the ...
Page 19 - Fig. 14 — Thermistor Nominal Resistance
19 but take care to prevent liquid from being carried over by the gases. Warm solution acts faster, but cold solution is just as effec- tive if applied for a longer period.GRAVITY FLOW METHOD — Do not add solution faster than vent can exhaust the generated gases. When condenser is full, allow soluti...
Page 20 - Fig. 15 — FP1 and FP2 Thermistor Location; COAX —; uid Line Flow
20 S UCTIO N COMPRE SS OR DI S CHARGE COAX EXP AN S ION VA LV E FP 2 FP 1 LIQUI D LIN E WA TER IN WA TER OUT CONDEN S A TE OVERFLO W (CO) AIR COI L FREEZ E PROTECTIO N WA TE R COI L PROTECTIO N THERMI S T OR ( ° C) ( ° C) AI R COI L AIRFLOW AIRFLO W a50-8163 LEGEND Fig. 15 — FP1 and FP2 Thermistor L...
Page 21 - Table 13 — Troubleshooting
21 Table 13 — Troubleshooting LEGEND FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION Main Power Problems X X Green Status LED Off Check line voltage circuit breaker and disconnect. Check for line voltage between L1 and L2 on the contactor. Check for 24-vac between R and C on controller. Check primary/...
Page 24 - HEATING AND COOLING CYCLE ANALYSIS; = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE; SUBCOOLING; = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE; DESCRIPTION; REVERSING; COAX; Source
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500073-01 Printed in U.S.A. Form 50PSW-C1SI Pg CL-2 10-10 Replaces: New Copyright 2010 Carrier Corporation - - - - - - - - - - - - - - -...