INSPECT EQUIPMENT File claim with shipping company prior to installation if shipmentis damaged or incomplete. Locate unit rating plate on unit servicepanel. It contains information needed to properly install unit.Check rating plate to be sure unit matches job specifications. Step 2—Install on a Soli...
4. Position sensing bulb on horizontal portion of suction tube adapter. Secure using supplied hardware. 5. Insulate bulb after installation. (See Fig. 5.) 6. Leak check all connections. FAN COILS If indoor unit (fan coil) comes factory equipped with a bi-flowhard shutoff TXV, no TXV change is requir...
SWEAT CONNECTION To avoid valve damage while brazing, service valves must bewrapped in a heat-sinking material such as a wet cloth. 1. Remove plastic retainer holding outdoor piston in liquid service valve. 2. Locate adapter tube shipped with unit. 3. Install strainer in adapter tube and connect tub...
Manual Carrier 38BYC
Summary
INSTALLATION Step 1—Check Equipment and Job Site UNPACK UNIT Move to final location. Remove carton, taking care not to damageunit. INSPECT EQUIPMENT File claim with shipping company prior to installation if shipmentis damaged or incomplete. Locate unit rating plate on unit servicepanel. It contains ...
If TXV installation is required, remove existing AccuRater® fromindoor coil. Refer to Figs. 4 and 5 and install TXV kit as follows: 1. Install suction tube adapter. 2. Install liquid flare-to-sweat adapter. 3. Connect external equalizer tube to fitting on suction tube adapter. 4. Position sensing bu...
OUTDOOR UNIT CONNECTED TO FACTORY APPROVEDINDOOR UNIT Outdoor unit contains correct system refrigerant charge for opera-tion with indoor unit of same size when connected by 15 ft offield-supplied or factory accessory tubing. Check refrigerantcharge for maximum efficiency. REFRIGERANT TUBING Connect ...