Page 2 - SAFETY CONSIDERATIONS; WARNING; INSTALLATION GUIDELINE
2 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for inf...
Page 3 - CAUTION
3 Same tube sizes are capable of handling higher flowrates (expressed as tons of cooling capacity) with Puron refrigerant compared to R--22 at constant pressure drops. For example, a 1 / 2 --inch OD liquid line is rated at 33% higher tons with Puron R than with R--22 (at 5 _ F pressure drop). A 1 1 ...
Page 10 - A U Z
10 Model Type 38AU= Carrier Condensing Unit Puron ® R --- 410A Refrigerant Type of Coil D = Dual Circuit, A/C Scroll Compressor Z = Single Circuit, A/C Scroll Compressor Refrigerant Options A = None B = Low Ambient Nominal Tonnage 16 = 15 Tons 25 = 20 Tons Not Used A = Not Used Not Used 0 = Not Used...
Page 11 - Matching 38AU Model To Evaporator Coil; Table 3 – Evaporator Coil Connections; INSTALLATION; Jobsite Survey; Step 1 — Plan for Unit Location; NOTE; Step 2 — Complete Pre-Installation Checks; Check Unit Electrical Characteristics:
11 Matching 38AU Model To Evaporator Coil The Model 38AUZ is a single-circuit unit design, requiring one set of refrigeration piping. This model can be connected to an evaporator coil with one circuit or with two circuits (by manifolding the evaporator connections into a single piping system). The M...
Page 12 - Step 5 — Complete Refrigerant Piping
12 Step 3 — Prepare Unit Mounting Support Slab Mount — Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow. Step 4 — Rig and Mount the Unit UNIT D...
Page 13 - Liquid Lift —
13 Enter the appropriate table to select the recommended line sizes. Model: Line Sizes Table Quantity of Line Sets 38AUZ 5 1 38AUD 6 2 Liquid Lift — A liquid lift condition exists when the outdoor unit is located below the indoor (evaporator) unit and liquid flows vertically up in a portion of the l...
Page 14 - Table 7 –; 8AU Maximum Suction Pipe Size; Vertical Separation (outdoor unit above indoor unit) –
14 Table 6 – 38AUD 16-25 Piping Recommendations (Two-Circuit Unit) NOTE : 38AUD requires TWO sets of refrigeration piping R-410A Equivalent LengthFt 0-38 38-75 75-113 113-150 150-188 m 0-12 12-23 23-34 34-46 46-57 Model Linear LengthFt 0-25 25-50 50-75 75-100 100-125 m 0-8 8-15 15-23 23-30 30-38 38A...
Page 15 - Table 9 – Refrigerant Specialties Part Numbers.
15 Circuit 1 Connections Circuit 2 Connections CKT 1 CKT 1 CKT 2 CKT 2 C10355 Fig. 6 -- 38AUD Service Valve Locations Plan the Circuit 1 and Circuit 2 tubing segments carefully, mark each segment and check constantly as piping systems are assembled to avoid piping errors. 38AUD unit cannot be field-...
Page 16 - drop
16 INDOOR COIL CKT 2 AIRFLOW INDOOR COIL CKT 1 AIRFLOW 15 DIAMS MIN 10 DIAMS 8 DIAMS MIN TXV SENSING BULB EQUALIZER LINE SIGHT GLASS A LOCATION SIGHT GLASSES B LOCATION TXV CKT 2 FILTER DRIER A LOCATION FILTER DRIERS B LOCATION FLOW TXV SENSING BULB TXV CKT 1 8 DIAMS MIN 15 DIAMS MIN 10 DIAMS Single...
Page 17 - Preliminary Charge —; Step 6 — Install Accessories
17 The stub tube connections include 1 / 4 -in SAE service fittings with Schrader valve cores (see Fig. 10). Before making any brazed connections to the unit service valves, remove both Schrader valve caps and cores and save for re-installation. Connect a source for nitrogen to one of these service ...
Page 18 - Step 7 — Complete Electrical Connections; to be connected to a 208-v power supply, the control
18 Step 7 — Complete Electrical Connections ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injur...
Page 19 - Convenience Outlets —
19 11 13 L1 L2 L3 C TB1 208/230-3-60 460-3-60575-3-60 Units Without Disconnect Option Units With Disconnect Option 2 4 6 1 3 5 L1 L2 L3 Optional Disconnect Switch Disconnect factory test leads; discard. Factory Wiring Disconnect per NEC C10204 Fig. 12 -- Power Wiring Connections Affix the crankcase ...
Page 20 - Convenience Outlet Utilization; NOTICE; ELECTRICAL OPERATION HAZARD; Installing Weatherproof Cover
20 B 50HJ542739 Maximum Continuous use : 8 Amps 24/7 Convenience Outlet Utilization NOTICE C10207 Fig. 15 -- Convenience Outlet Utilization Notice Label Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wire...
Page 22 - Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data; Legend and Notes for Table 10
22 Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data UNIT SIZE 38AU NOMINAL POWER SUPPLY VOLTAGE RANGE COMPRESSOR NO C.O. or UNPWRD C.O. No. 1 No. 2 OFM POWER SUPPLY DISCONNECT SIZE V --- Ph --- Hz Min Max RLA LRA RLA LRA Qty FLA (ea) MCA FUSE or HACR BRKR FLA LRA D*16 Z*16 208/230 ---3 ---60 18...
Page 23 - System Check; Turn on the crankcase heater for 24 hours before starting; Preliminary Checks
23 PRE-START-UP IMPORTANT : Before beginning Pre-Start-Up or Start-Up, review Start-Up Checklist at the back of thisbook. The Checklist assures proper start-up of a unitand provides a record of unit condition, applicationrequirements, system information, and operation atinitial start-up. UNIT DAMAGE...
Page 24 - Start Unit
24 Compressor Overload — This overload interrupts power to the compressor when either the current or internal motor winding temperature becomes excessive, and automatically resets when the internal temperature drops to a safe level. This overload may require up to 60 minutes (or longer) to reset. If...
Page 32 - OPERATING SEQUENCE; Base Unit Controls; Cooling, Unit Without Economizer —
32 OPERATING SEQUENCE Base Unit Controls Indoor (Supply) Fan — The indoor fan contactor (IFC) is remotely located at the fan coil or fan section. If the thermostat fan operation is selected as Continuous, the IFC is energized and the indoor (supply) fan motor runs continuously. If the thermostat fan...
Page 33 - Refrigeration System
33 ROUTINE SYSTEM MAINTENANCE These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation: Quarterly Inspection (and 30 days after initial start) — Indoor section S Condenser coil cleanlines...
Page 34 - SEAT
34 Liquid Line Filter Drier — The factory-provided filter drier is specifically designed to operate with Puron ® . Replace the filter drier with factory-authorized components only with a filter drier with desiccant made from 100% molecular sieve grade XH-11. Filter drier must be replaced whenever th...
Page 35 - Comfort Alert Diagnostic Module
35 Comfort Alert Diagnostic Module The Comfort Alert Diagnostic Module (CADM) monitors and analyzes data from the Copeland Scroll ® three-phase compressor and the thermostat demand. The CADM also provides a 3-minute anti-recycle time delay to compressor cycling. Each compressor has a separate CADM m...
Page 36 - Table 11 – LED Status Codes
36 Table 11 – LED Status Codes Status LED Status LED Description Status LED Troubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” LED On Solid Thermostat demand signal Y is present, but the com- pressor is not running. 1. Compressor prote...
Page 37 - Compressor Protection
37 Table 12 – CADM Troubleshooting Miswired Module Indication Recommended Troubleshooting Action Green LED is not on, module does not power up Determine if both R and C module terminals are connected. Verify voltage in present at module’s R and C terminals. NOTE: The CADM requires a constant nominal...
Page 38 - Condenser Fans/Motors
38 Condenser Fans/Motors ServiceValves Access Panel -Control Box &Compressors C10087 Fig. 34 -- 38AUD Size 16 Cabinet C10095 Fig. 35 -- 38AUD*16 Piping 38A U
Page 42 - Coil Type Identification
42 Coil Type Identification 38AU units are available with different coil types. Cleaning methods differ for each type so identifying the coil type is important. Unit model number and appearance can identify the coil type. NOVATION t Type — The new NOVATION Heat Exchanger Technology is an all--alumin...
Page 44 - FASTENER TORQUE VALUES; Table 13 – Torque Values; TROUBLESHOOTING
44 7. Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize po- tential for fin damage. 8. Ensure cleaner thoroughly penetrates deep into finned areas. 9. Interior and exterior finned areas must be tho...
Page 46 - APPENDIX A; Air Conditioner & Heat Pump with PURON; warnings; APPENDIX B; Wiring Diagram List; Unit
46 APPENDIX A Air Conditioner & Heat Pump with PURON ® — Quick Reference Guide S Puron ® (R-410A) refrigerant operates at 50 percent to 70 percent higher pressures than R-22. Be sure thatservicing equipment and replacement components aredesigned to operate with Puron ® . S Puron ® refrigerant cy...
Page 47 - APPENDIX C; Low Ambient Option — Factory Installed; Speed Control Sensor Resistance —
47 APPENDIX C Low Ambient Option — Factory Installed Units with the factory installed low ambient option are equipped with a Motormaster R solid--state head pressure control which regulates fan speed. A temperature sensor, mounted on circuit 1 of the outdoor coil (see Figs. 44 and 45) controls the s...
Page 49 - Table 14 – Wind Baffle Dimension
49 Table 14 – Wind Baffle Dimension DIMENSIONS --- INCHES UNIT BAFFLE A B C D E F G H J 38AUZ*16 38AUD*16 (MCHX) LEFT SIDE 19 3 / 4 20 1 / 2 21 1 / 4 43 1 / 8 8 3 / 8 18 27 1 / 4 40 --- BACK 80 1 / 4 81 81 3 / 4 43 1 / 8 8 3 / 8 18 27 1 / 4 40 --- RIGHT SIDE 38 3 / 4 39 1 / 2 40 1 / 4 43 1 / 8 8 3 /...
Page 52 - BOTT
52 RIGHT BACK LEFT FRONT BOTT OM BRACKET T O P BRACKETS C 10367 Fig. 48 -- W ind Baf fl e Inst allat ion — 15 Ton Unit s 38A U
Page 56 - CHECK VOLTAGE IMBALANCE
56 CHECK VOLTAGE IMBALANCE LINE-TO-LINE VOLTS: AB V AC V BC V (AB + AC + BC)/3 = AVERAGE VOLTAGE = V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM! CALL LOCAL POWER COMPANY FOR ASS...