Page 2 - Check Equipment and Job Site; Unpack Unit; Install on a Solid, Level Mounting Pad; NOTE; Clearance Requirements

2 INSTALLATION RECOMMENDATIONS NOTE : In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment. 1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer. 2. Ensure that vapor and liquid tube diameter...

Page 3 - CAUTION; Make Piping Connections; WARNING; Outdoor Unit Connected to Factory--Approved Indoor

3 Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 _ F (12.78 _ C) without low ambient cooling enabled, and the maximum outdoor operating ambient in cooling mode is 125 _ F (51.67 _ C). At line voltage of 208v (or below) and an outdoor ambient of 120 _ F (48.9 _ C) (and ...

Page 4 - Table 2 – Accessory Usage; Yes

4 Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (in.) UNIT SIZE LIQUID RATED VAPOR* Connection Diameter Tube Diameter Connection Diameter Tube Diameter 25HPA624 3/8 3/8 3/4 3/4 25HPA636 3/8 3/8 7/8 7/8 25HPA648 3/8 3/8 7/8 1 --- 1/8 25HPA660 3/8 3/8 7/8 1 --- 1/8 ...