Page 3 - Fig. 2 — Mounting Applications; 9BY IN REMOTE APPLICATION WITH DUCTWORK
LEGEND Refrigerant Connection Field-Supplied Refrigerant Piping *Field-Supplied Floor Stand (Height to Match Wall Opening). Fig. 2 — Mounting Applications 09BY DISCHARGEDUCT INLETDUCT TO OUTSIDE INSULATE IF THROUGHCONDITIONED SPACE HANGERRODS TO RAIN DRAIN(REQUIRED IF RAIN WILL ENTER UNIT) TO REFRIG...
Page 4 - Fig. 3 — Base Unit Dimensions; DIMENSION
09BY DIMENSIONS (English) DIMENSION 006 (Ft-in.) 008 (Ft-in.) 012 (Ft-in.) 014 (Ft-in.) 016,024 (Ft-in.) A 2-11 1 ⁄ 2 3- 6 13 ⁄ 16 3- 6 13 ⁄ 16 3- 6 13 ⁄ 16 5- 0 B 1- 7 11 ⁄ 16 1-11 5 ⁄ 8 1-11 5 ⁄ 8 1-11 5 ⁄ 8 2- 9 7 ⁄ 16 C 4- 0 7 ⁄ 16 4- 8 5- 3 1 ⁄ 2 5-11 7- 6 9 ⁄ 16 D 1-11 1 ⁄ 4 2- 3 9 ⁄ 16 2- 3 9...
Page 6 - Table 1 — Condenser Unit Application; Table 2 — Physical Data
Table 1 — Condenser Unit Application UNIT 50BZ 09BY 006 008 012 014 016 024 006 S 008 S 012 O S 014 O S 016 O S 024 O S LEGEND S — StandardO — OptionalNOTE: Contact your local representative for use with reciprocating air-cooled chillers and other compressor-bearing unit combinations. Table 2 — Phys...
Page 7 - Step 2 — Rig and Place Unit; Fig. 4 — Unit Rigging
Step 2 — Rig and Place Unit RIGGING — The 09BY units are mounted on skids. Leavethe unit on the skid until it is in the final position. While onthe skid, the unit can be rolled, dragged or forklifted; do notapply force to the unit. Use a minimum of 3 rollers whenrolling, and raise from above to remo...
Page 8 - Step 5 — Complete Refrigerant Piping
Step 3 — Install Accessory Low-Ambient Kit orInlet Filter Kit (If Required) — If the unit will be op- erated with inlet air to the condenser below 50 F, a low-ambient damper may be required. The low-ambient kit con-trols head pressure by discharge dampers on the condenserfan. The dampers are actuate...
Page 9 - Table 3 — Minimum Refrigerant Line Size Data; Fig. 8 — Typical 2-Circuit Condenser Manifolded
LIQUID LIFT — Amount of liquid lift available before re-frigerant flashing occurs depends on amount of liquid sub-cooling in the system. All 09BY condensers have positive subcooling when ap- plied with optimum charge. With subcooling, it is possibleto overcome an appreciable pressure drop and/or sta...
Page 10 - Step 6 — Ductwork —; The 09BY unit is designed for; UNIT; Fig. 9 — Condenser Ductwork Details
CHECK VALVE — When the 09BY condenser is installedwith the condenser located above the compressor evapora-tor, it is recommended that a field-supplied check valve beinstalled on the hot gas discharge line. This prevents refrig-erant which condenses in the discharge line during the offcycle from drai...
Page 11 - Step 7 — Insulate the Unit —; The 09BY units are; Step 8 — Complete Electrical Connections; To rewire the unit, disconnect and reconnect the wires at; Table 4 — Electrical Data; Fig. 10 — Placement of Duct Flanges on Units
3. A high-density fiberglass (2 lb minimum density) or semi- rigid foamed insulation such as Styrofoam™ will be re-quired inside the ducts to prevent air erosion. The insu-lation must be firmly secured in the discharge duct nearthe blower discharge to withstand the high air velocity. Step 7 — Insula...
Page 12 - Condenser operation on improper line voltage or exces-; — Fan Motor Contactor; Fig. 11 — Combination Field Wiring
Determine maximum deviation from average voltage:(AB) 243 – 239 = 4 v(BC) 239 – 236 = 3 v(AC) 239 – 238 = 1 vMaximum deviation is then 4 v. To determine the percentageof voltage imbalance: 4 % Voltage Imbalance = 100 x 239 = 1.7% This amount of phase imbalance is satisfactory since it is below the a...
Page 13 - Fig. 12 — Condenser Fan Pulley Adjustment
START-UP To prevent personal injury, be sure wire fan guards aresecured in place over each fan discharge (or that fansare ducted) before starting the unit. Complete Unit Start-Up Checklist on page CL-1 prior to start-up of this system. System Evacuation and Dehydration — Refer to GTAC II, Module 4, ...
Page 14 - Table 5 — Condenser Fan Performance
Table 5 — Condenser Fan Performance UNIT 09BY AIRFLOW (Cfm) EXTERNAL STATIC PRESSURE (in. wg) 0.0 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 006 2000 676 0.26 905 0.51 1085 0.80 1230 1.08 1348 1.34 1449 1.60 2500 845 0.51 1039 0.82 1197 1.14 1339 1.51 1466 1.88 1570 2.21 300...
Page 16 - TROUBLESHOOTING; See Table 6 for problems and possible solutions.; Table 6 — Troubleshooting; PROBLEM
TROUBLESHOOTING See Table 6 for problems and possible solutions. Table 6 — Troubleshooting PROBLEM POTENTIAL CAUSE SOLUTION Unit is tripping onhigh-pressure switchor high dischargepressure is noted. 1. Fan belts are slipping or broken.2. Fan is not delivering adequate air for condenser.3. Low-ambien...
Page 19 - A. Preliminary Information; COMPRESSOR BEARING UNIT:
START-UP CHECKLIST A. Preliminary Information COMPRESSOR BEARING UNIT: MODEL NO. SERIAL NO. 09BY UNIT: MODEL NO. SERIAL NO. FIELD-INSTALLED ACCESSORIES B. Pre-Start-Up CONDENSING UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) CHECK POWER SUPPLY. ...
Page 20 - CHECK VOLTAGE IMBALANCE
CHECK VOLTAGE IMBALANCE IS CONDENSER MOTOR WIRED FOR CORRECT VOLTAGE? (Y/N) LINE-TO-LINE VOLTS: AB V AC V BC V (AB + AC + BC)/3 = AVERAGE VOLTAGE = V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = % IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMP...