Page 2 - Up to; Table 1; II. Pressure Switch Installation; CAUTION; Figure 1
2 I. Description HANG07, HALP09, and HAC1PS01-14 conversion kits arerequired when installing the following units above theirmaximum rated altitudes: Amana Air Command 80 SSE Amana Air Command SSE II Amana Air Command SSEIIQ Amana SV furnaces Amana Packaged Gas/Electric Units: PGA/B/D**C Increases in...
Page 3 - Derates
3 Table 2 Pressure Switch Kits (Category I Venting Only) HAC1PS Nat. Gas Derates (See Sec. V) 01 02 03 04 05 06 07 08 09 10 11 12 13 14 GUI(A/B)045(A/B) 7501 - 9500 ft 9501 - 11000 ft 34±4%42±4% XX GUI(A/B)045(CA/CX) 7501 - 9500 ft 9501 - 11000 ft 34±4%42±4% XX GUI(A/B)070(A/B/CA/CX) 7501 - 9500 ft ...
Page 4 - III. Orifice Installation; Remove the gas manifold by removing the burner box
4 HATS01 HATS02 HATS03 HATS04 HATS05 HATS06 HATS07 HATS08 HATS09 GUI(S,V)070 X X GUI(S,V)090 X X GUI(S,V)115 X X GUI(S,V)140 X X GCIS070 X X GCIS090 X X Low Pressure Switch "WC -0.37 -0.37 -0.37 -0.32 -0.27 -0.32 -0.32 -0.27 -0.23 High Pressure Switch "WC -0.66 -0.6 -0.55 -0.55 -0.46 -0.55 -...
Page 5 - Tighten orifices with a box-end wrench. Do not use a; Orifice
5 Furnace Model Kit Number Altitude (Feet) Orifice GUIAGUIBGCIAGCIB HANG07 7501 - 11000 #45 GUICGCICGUID PGA/B/D**C HANG07 6001 - 11000 #45 NOTE: Units Installed in Canada are certified to 4500 feet only,therefore these kits are not applicable in Canada. Table 4 Natural Gas Orifice Kits* * This tabl...
Page 6 - IV. Propane Gas Conversion; WARNING
6 CAUTION T o p r e v e n t u n s a t i s f a c t o r y f u r n a c eoperation, the proper gas conversion kitmust be used for each valve. Use the White-Rodgers spring kit only with the White-Rodgers gas valve, Honeywell spring kitonly with the Honeywell gas valve andRobertshaw spring kit only with t...
Page 7 - OUTLET
7 O FF ON M P C 1 3 2 INLET Pressure Regulator Adjustment (Under Cap Screw) Inlet Pressure Tap (Side of Valve) Outlet (Manifold) Pressure Tap (Side of Valve) Gas Valve On/Off Selector Switch OUTLET Figure 7 White-Rodgers 36E22 Gas Valve Pressure Regulator Adjustment (Under Cap Screw) OUTLET INLET Ga...
Page 8 - Manometer; Single Stage Furnaces
8 V. Operational Check 1. Start the furnace using the procedures in the section, “Operating Your Furnace” in the installation instruc-tions. In addition, perform the following checks andadjustments. 2. The position of the ignitor, relative to the burner, is not affected by this conversion procedure ...
Page 9 - Table 6; Natural Gas Firing Rates; Table 7; a. Turn off gas supply to all other appliances except the
9 Derating Example 1: GUIA115A40 at 8500 ft. Sea level input = 115,000 BTU/Hr. From Table 2: Derate at 8500 ft. = 27±4% Since we are at the mid point of the elevation range, weuse the mid point of the derate; 27%. New Input = 115000 x (1 - .27) = 83950 BTU/hr Derating Example 2: GUIC045DA30 at 7500 ...
Page 10 - For propane gas conversions, attach conversion data; VI. Complete The Installation; Check Burner Flames
10 • The temperature rise for each heating speed mustbe within the range specified on the rating plate orSpecification Sheet. NOTE: Air temperature rise is the temperature differ-ence between supply and return air. With a properly designed system, the proper amount oftemperature rise will normally b...