APC 5000VA - Manual
APC 5000VA – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – TOWER; CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
- Page 4 – MECHANICAL DESIGN
- Page 5 – INPUT PFC POWER STAGE
- Page 6 – AUTOMATIC BYPASS
- Page 9 – PART 3 - PART 3 – ACCESSORIES
- Page 10 – SOFTWARE AND CONNECTIVITY
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
APC Smart-UPS RT
BID SPECIFICATIONS FOR
3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC
Uninterruptible Power Supply
PART 1 - GENERAL
1.1
SUMMARY
A.
This specification describes the operation and functionality of a continuous duty, single-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as
the UPS.
B.
The UPS utilizes double conversion online topology designed to protect electronic
equipment by supplying reliable, network-grade power featuring extremely tight
voltage and frequency regulation. The UPS also features internal bypass and input
power factor correction.
C.
The primary sections of the UPS are: input disconnect and filter stage, input PFC power
stage, energy storage stage (DC bus capacitor bank), output power stage (inverter),
bypass and a battery charger. The control of power module and fault detection logic is
microcontroller based. Input disconnect and filter stage contains input backfeed relay
(in models with a input wire plug), input filter, transient suppression, battery select
transfer relays. Input PFC power stage contains non-isolated power factor correcting
AC/DC converters. This converter is capable of full power operation in very wide input
voltage range
or from a nominal DC battery voltage. The energy storage stage is a split
DC bus capacitor handling seamless transitions from battery to line and vice versa as
well as the low and high frequency power stages ripple. The inverter stage operates
directly from the DC bus and produces an AC output voltage of
200/208/220/230/240VAC output. The output of UPS is either connected through a
bypass relay to the inverter or to the input filtered line. UPS contains a battery charger,
which operates from the DC bus
.
D.
The UPS batteries are modular, hot-swappable, user-replaceable.
E.
In addition, this specification describes the performance, functionality, and design of
the UPS Service Bypass Panel, hereafter referred to as the SBP, the external Battery
Systems, and connectivity solutions.
F.
The UPS and associated equipment shall operate in conjunction with a primary power
supply and an output distribution system to provide quality uninterrupted power for
mission critical, electronic equipment load.
G.
All programming and miscellaneous components for a fully operational system as
described in this specification shall be available as part of the UPS.
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM H. Configuration Specifics: The UPS is available in one of the following configurations: MODEL SKU # TOWER APC Smart-UPS RT 3000VA RM 230V SURT3000XLI APC Smart-UPS RT 5000VA RM 230V SURT5000XLI APC Smart-UPS RT 6000VA RM 230V SURT6000XLI RACK MOUNT AP...
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 2.1 MECHANICAL DESIGN A. The UPS is contained in a rugged steel cabinet with two plastic front bezels; B. The UPS dimensions are 13 x 43 x 66cm (5.1 x 17 x 26 in.); C. The UPS cabinet is capable of conversion between Tower and Rack-Mount configurations...
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 3. Output frequency: 50/60 +/- 3Hz tracking or 50/60 +/- 0.1Hz tracking (user selectable); 4. AC output voltage distortion: Max. 2% @ 100% linear load; Max. 5% @ 100% non-linear Load; 5. AC output static voltage regulation: +/-1%; 6. AC output dynamic ...