Page 2 - About this manual; Foreword; General information
Reception When the unit arrives on site, checkit has not been damaged in any wayduring transport. If damage isobserved, or even merely suspected,notify the carrier within 24 hours byregistered letter. Notify the localTrane Sales office at the same time.The unit should be totally inspectedwithin 3 da...
Page 3 - Contents
CG-SVU01B-E4 3 Contents Foreword 2 Warranty 2 Reception 2 General information 2 TRACER CH532 Presentation 4 Hardware architecture 5 Starting/stopping the unit 9 Menus 10 Display menu: “Data display” 11 Customer settings menu: “Settings” 12 Clock Setting menu: “Clock” 15 Unit configuration menu: “Con...
Page 4 - TRACER CH532 Presentation; Downward and Upward; Validation button
4 CG-SVU01B-E4 TRACER CH532 Presentation Important note: This document describes all the functions availableon TRACER CH532 with softwareversion 2.0 and explains how toprogram it.Certain parameters must only bemodified by qualified personnel.Before changing any parameter,always check that the change...
Page 5 - Hardware architecture
CG-SVU01B-E4 5 Hardware architecture Figure 2 - TRACER CH532 inputs andoutputs Prg Esc 9 9 10 11
Page 8 - Note: External water setpoint
8 CG-SVU01B-E4 TRACER CH532 offers customer the possibility to use inputs or outputsin order to:- use an external water setpoint reset using an analog input (refer to figure 3) - use an auxiliary setpoint- connect a remote on/off of the unit or a circuit - reset faults- connect a remote Cooling/Heat...
Page 9 - Starting/stopping the unit
CG-SVU01B-E4 9 Starting/stopping the unit Once the unit is powered on (maindisconnect switch closed) TRACER CH532 returns to the following display: Line 2 gives current date and timeLine 3 gives current leaving watertemperatureLine 4 gives the unit status: OFF BY KEYB = Local stop UNIT ON = Unit run...
Page 10 - Menus; Data display
10 CG-SVU01B-E4 Menus TRACER CH532 allows the user to access 4 menus to display or adjustoperation parameters: • “ Data display ” menu - This menu allows the user to visualize alloperation parameters: - Water and air temperatures- Refrigerant pressures- Saturated refrigerant temperatures - Compresso...
Page 11 - Display menu: “Data display”
CG-SVU01B-E4 11 Display menu: “Data display” From the menu screen, select “ Data Display ” then press Pressing or will allow navigation from screen 1 to 8 asshown hereafter: The menu is looped making itpossible to scroll from the first itemin the menu to the last item. 1. Water and air temperaturesL...
Page 15 - Clock Setting menu: “Clock”
CG-SV01B-E4 15 Clock Setting menu: “Clock” From the menu screen, select “ Clock ” then press . Following screen will appear: Enter default password:”0000”(factory set) Press and cursor will move to first field of password. Pressing or will increment the value from 0 to 9999. Keeping pressure on or w...
Page 22 - Alarms; Alarms display and Resetting
Alarms 1. Alarms display and Resetting A fault on a unit will be shownthrough the user interface orthrough 2 digital outputs, one foreach refrigerant circuit. The alarms are divided into 3categories:- Warning. Shows that something is wrong on the unit but unit can bekept in operation. A message isdi...
Page 25 - Description; Figure 9; A B
LonTalk ® option Description The Lon interface uses an EchelonFTT-10 transceiver, which isapproved to be used on the TP/FT-10channel.This channel is characterized by thefollowing main features:• It consists of up to 60 nodes on a single network segment • Data rate : 78 125 kbps• Maximum distance : 1...
Page 26 - Object details; LED meaning and function
LonTalk ® option Chiller Controller 8040 Mandatory network variables Optional network variables nv1 nviChillerEnablesnvt_switch nv2 nv7 nv8 nv3 nv4 nv11 nv12 nv13 nv15 nv16 nviCoolSetptsnvt_temp_p nviModeSnvt_hvac_mode nviHeatSetptsnvt_temp_p nvoOnOffsnvt_switch nvoActiveSetptsnvt_temp_p nvoLvgCHWTT...
Page 28 - Cable characteristics
28 CG-SV01B-E4 LonTalk ® option Cable characteristics Level 4 cable may be used with TP/FT-10 channels. The level 4 cable specification used by Echelon and as originallydefined by the National Electrical Manufacturers Association (NEMA) differs from the Category 4 specificationproposed by the Electr...
Page 29 - Notes
Page 32 - Safety recommendations; Maintenance contract
The manufacturer has a policy of continuousproduct improvement, and reserves the rightto alter any details of the products at any timewithout notice. This publication is a general guide to install,use and properly maintain our products. Theinformation given may be different from thespecification for...