3M 5797A-MT - Manual

3M 5797A-MT

3M 5797A-MT – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
Page: / 12

Table of Contents:

  • Page 2 – Contents
  • Page 3 – Cable X; from; Cable Y; for use later in these instructions.
  • Page 4 – *Note: This assumes that the installer has determined; Aluminum; Copper connectors do not require a length
  • Page 5 – Place Components on Cable
  • Page 9 – Install Splice Jacket; to install jacket tubes.
  • Page 10 – Bind the final wrap in place with vinyl tape.; Wrap. The resin contains a; Armorcast
Loading the manual

Cold Shrink QS-III

Three-Conductor Splice Kit for use on
Armor and Non-Armor Cables

Instructions

IEEE Std. 404

35 kV Class
250 kV BIL

* Splices (including size transitions) can be made to smaller or larger conductors, provided

both cables are within the Insulation O.D. Range and the connector meets the dimensional
requirements shown below.

Connector Dimensional Requirements

Minimum

Maximum

inches (mm)

inches (mm)

Outside Diameter

0.51" (13,0 mm)

1.70" (43,2 mm)

Length

Aluminum (Al/Cu)

------

6.00" (152 mm)

Length

Copper (Cu)

------

6.50" (165 mm)

Cable Range Requirements

Kit Number

Cable Insulation

Conductor

O.D. Range

Size Range

5797A-MT

1.07" to 1.70"

1/0 AWG - 350 kcmil*

(27,2 mm to 43,2 mm)

(60 - 185 mm

2

)

3M

Cold Shrink

QS-III Splicing Kit

5797A-MT

78-8126-0432-6-A

CAUTION

Working around energized high-voltage systems may cause serious
injury or death. Installation should be performed by personnel familiar
with good safety practice in handling high-voltage electrical equipment.
De-energize and ground all electrical systems before installing product.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Contents

2 78-8126-0432-6-A Contents 1.0 Kit Contents ............................................................................................................................................3 2.0 Prepare Cable ..................................................................................................

Page 3 - Cable X; from; Cable Y; for use later in these instructions.

3 78-8126-0432-6-A 1.0 Kit Contents: 1.1 Kit Contents are as follows: 3 ..............Cold Shrink 5467A QS-III Silicone Splice Bodies6 ..............Tubes, P55/R Red Compound3 ..............Metallic Shield Sleeves6 ..............Constant Force Spring Shield Connectors (1.31" I.D.)2 ................

Page 4 - *Note: This assumes that the installer has determined; Aluminum; Copper connectors do not require a length

4 78-8126-0432-6-A 2.3 Cut the phase cores to the appropriate length. Cores of Cable X should be 33" (838 mm) when measured from the cable jacket end or 31 1/2"(800 mm) when measured from end of the armor. Cores of Cable Y should be 25" (635 mm) when measured from the cable jacket end or...

Other 3M Models