Surge Suppression
for Zone 0 Locations

Synopsis

This note discusses the surge
protection requirements of
intrinsically safe circuits entering a
Zone 0 hazardous area. It
analyses the potential gradients
generated by lightning strikes and
their possible routes of invasion.
The alleviation of the problem at
the zone 0 interface transfers the
problem elsewhere and an
adequately safe pragmatic
solution is proposed.

991.115

03/99

Application Note
TAN 1005

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Application Notes from Telematic

CONTENTS PAGE 1 INTRODUCTION ........................................................................................................................... 1 2 INTRINSIC SAFETY REQUIREMENTS FOR EARTHING AND BONDING ............................................... 2 3 CERTIFICATION OF SURGE SUPPRESSORS ....

Page 3 - INTRODUCTION

SURGE SUPPRESSION FORZONE 0 LOCATIONS tal requirement of all the methods of protection used for power equip-ment. It is not usual for lightning induced current to directly cause enoughheating to create a hazard by temperature ignition, since the currentpulses are too short to create a sustained high...

Page 4 - CERTIFICATION OF SURGE SUPPRESSORS

tion from this possibility or sited with care in the shelter of some otherprotrusion. The diagram shows a two wire 4 to 20 milliamp transmitterwith internal isolation fed from a galvanic isolator. To establish theorder of the problem some assumptions are made which cannot befully justified but are b...