VINO2500SSD, 4500SSD
VINO6500SSD, 8500SSD
Installer’s Instruction
Federal law requires that WINE-MATE split cooling systems be
installed by an EPA certified refrigeration technician.
WINE-MATE split system is shipped as components and is ready for use only
after a certified refrigeration technician has properly installed, chatged and tested
the system. Proper installation is critical. Vinotemp can only warrant the quality of
the components. The installation and proper operation of the system must be
warranted by the installer. Installation of the system must be done in accordance
with all state and local building codes.
The condensing unit and evaporator unit are connected by a liquid line and an
insulated suction line that are supplied by the installer. These lines must be
properly sized for the distance between the two units. After the units and the lines
are installed, the system must be pressure tested. If no leaks are found,
evacuate and charge system with R134A. Refrigerant amount will vary
depending on the length of line set.
1. Condensing Unit
•
Place the condensing units WM250-850SCU in a properly ventilated
location. If it is not, heat exhausted by the condensing unit will build up
and the cooling system will not operate properly.
•
Leave minimum 5 feet clearance for the exhaust side and leave minimum
1 foot clearance for the fresh air intake side.
•
Condensing unit shall be elevated to avoid possible flooding and shaded
from direct sun. It shall not be exposed to temperatures higher than 110
°
F or lower than 45
°
F (optional low ambient kit for 20
°
F).
2. Evaporator Unit
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
- 1 - • The WM25-85SFCD evaporator units shall be installed for ceiling mount with air supply on both sides and air return on the bottom. • Supply and return air flow from the evaporator unit shall be unobstructed for at least 1 foot. • There is a gravity drain line so that it can not be installed a...
- 2 - 5. Pressure, Superheat and Subcooling Readings NOTES: THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY. Complaint Possible Causes a. High suction pressure and low head pressure b. High suction pressure and low head pressure Low superheat and low subcooling c. High suction pressure a...
- 3 - Back Position : Process and manometer port closed for normal operation Front Position : Main connection to liquid or suction line closed Middle Position : All ports open for vacuum, charge and measurement 7. Electrical Wiring Fig. 2.2 VINO2500 & 4500SSD Electrical Wiring Diagram (VTSTAT) F...