Viking Sprinkler 11a - Manual

Viking Sprinkler 11a

Viking Sprinkler 11a – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – TECHNICAL DATA; Ordering Information:; Viking price list; Available Finishes And Temperature Ratings:; Standard Sprinkler Wrench 10896W/B
  • Page 3 – TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES; Wrench 12144W/B for Coated and/or Recessed Pendent Sprinklers
  • Page 4 – Approval Chart 1; Micromatic; Standard Orifice
  • Page 5 – Approval Chart 2; Installed with the Viking Micromatic
  • Page 6 – Approval Chart 3; MicromaticHP; Footnotes
  • Page 7 – DESIGN CRITERIA; Wrench 13577W/B for Wax Coated Sprinklers
Loading the manual

MICROMATIC

®

AND

MicromaticHP

®

STANDARD

RESPONSE PENDENT

SPRINKLERS

TECHNICAL DATA

March 7, 2008

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]

1. DESCRIPTION

Viking Micromatic

®

and MicromaticHP

®

Standard Response Pendent Sprinklers are

small, thermosensitive, glass-bulb spray sprinklers available in several different fin-
ishes, temperature ratings, and K-Factors to meet design requirements. The special
Polyester and Teflon

®

coatings can be used in decorative applications where colors are

desired. In addition, these coatings have been investigated for installation in corrosive
atmospheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflon

®

and Polyester coat-

ings as corrosion resistant.)
Viking standard response sprinklers may be ordered and/or used as open sprinklers
(glass bulb and pip cap assembly removed) on deluge systems. Refer to

Ordering

Instructions

on page 11b.

2. LISTINGS AND APPROVALS

cULus Listed:

Category VNIV

FM Approved:

Classes 2001, 2002, 2006, 2015, and 2017

NYC Approved:

MEA 89-92-E, Volume 12

ABS Certified:

Certificate 04-HS407984A-PDA

VdS Approved:

Certificate G4040096, G4040098, G4060058, G4060059, G4980001, G4980002, G4980005, and G4980007

LPC Approved:

Ref. No. 096e/06 and 167a/04

CE Certified:

Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40141, 0786-CPD-40181, 0832-CPD-2001, and

0832-CPD-2003

MED Certified:

Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008, and RINA Certificate

No. MED497705C5

NOTE:

Other International approval certificates are available upon request.

Refer to the Approval Charts on pages 11d-f and Design Criteria on page 11f for cULus and FM approval requirements that must
be followed.

3. TECHNICAL DATA

Speci

fi

cations:

Available since 1997.
Minimum Operating Pressure: Refer to the Approval Chart

Maximum Working Pressure: Sprinklers VK023 and VK122 are rated for

use with water working pressures ranging from the minimum 7 psi
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-
sure (HP) sprinklers can be identified by locating “250” stamped on
the deflector. All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar) wwp.

Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: Refer to the Approval Charts
Nominal K-Factor: Refer to the Approval Charts

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: Refer to the Approval Charts

Material Standards:

Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 10139, 10142, 10170, 10173, 10223, and

12105. Brass UNS-C26000 for all other Sprinklers.

Bushing (for Sprinklers 09994, 10189, 10221, and 10222): Brass UNS-C36000
Bulb: Glass, nominal 5 mm diameter

Form No. F_100397

Replaces page 11a-h, dated October 12, 2007.
(Added Dry System note in approval chart for Small Orifice)

Viking Technical Data may be found on

The Viking Corporation’s Web site at

http://www.vikinggroupinc.com.

The Web site may include a more recent

edition of this Technical Data Page.

Sprinkler 11a

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - TECHNICAL DATA; Ordering Information:; Viking price list; Available Finishes And Temperature Ratings:; Standard Sprinkler Wrench 10896W/B

TECHNICAL DATA March 7, 2008 The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected] MICROMATIC ® AND MicromaticHP ® STANDARD RESPONSE PENDENT SPRINKLERS Belleville Spring Sealing A...

Page 3 - TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES; Wrench 12144W/B for Coated and/or Recessed Pendent Sprinklers

MICROMATIC ® AND MicromaticHP ® STANDARD RESPONSE PENDENT SPRINKLERS TECHNICAL DATA March 7, 2008 The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected] TABLE 1: AVAILABLE SPRINKLE...

Page 4 - Approval Chart 1; Micromatic; Standard Orifice

TECHNICAL DATA March 7, 2008 The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected] MICROMATIC ® AND MicromaticHP ® STANDARD RESPONSE PENDENT SPRINKLERS Approval Chart 1 Micromatic...

Other Viking Models