Page 2 - Introduction
©American Standard Inc. 2000 TWA-PRC001-EN Introduction Split System Heat Pumps…Designed With Your Needs In Mind. The Trane reputation for quality andreliability is reflected in the Odyssey™Commercial Split System Heat Pumps.Trane’s focused attention on the splitsystem marketplace results in anoutst...
Page 3 - Contents; Model Number Description
Contents TWA-PRC001-EN Introduction Features and Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Cool and Heat PerformanceFan Performance Electric Power Connection and Wiring Dimension and Weights Mechanical Specifications 2 4 6 7 8 9 12...
Page 5 - Odyssey
5 TWA-PRC001-EN Features andBenefits Heat Pump OptionsThe Odyssey ™ split system product line includes heat pumps in both single anddual compressor options.TWA075A and TWA100A singlecompressor models feature singlerefrigeration circuitry lowering jobinstallation costs by requiring only oneset of ref...
Page 7 - Standard Filter
7 TWA-PRC001-EN SelectionProcedure Cooling CapacityStep 1 — Calculate the building’s totaland sensible cooling loads at designconditions. Use the Trane calculationform or any other standard acceptedmethod. Step 2 — Size the equipment using TablePD-1. Match the cooling loads at designconditions. Exam...
Page 8 - TWE = Cooling Convertible
TWA-PRC001-EN 8 ModelNumberDescription Digit 8 - Electrical Characteristics D = 380-415/3/50 Digit 9, 10 - Factory - Installed Options 00 = Packed Stock0S = Black Epoxy Coated Coil Digit 11- Minor Design Sequence D = Fourth Digit 12- Service Digit A = First Split System Heat Pump Model Nomenclature ...
Page 9 - Table GD-1 — General Data — Heat Pumps
9 TWA-PRC001-EN GeneralData (Heat Pumps) Table GD-1 — General Data — Heat Pumps TWA075A TWA100A Cooling Performance 1 Gross Cooling Capacity, BTUH (KW) Matched Air Handler, BTUH (KW) 82,000 (23.97) 109,000 (31.97) Heat Pump Only 2 , BTUH (KW) 82,000 (23.97) 105,000 (30.75) ARI Net Cooling Capacity 3...
Page 10 - General Data — Heat Pumps
TWA-PRC001-EN 10 GeneralData (Heat Pumps) Table GD-2 General Data — Heat Pumps TWA155B TWA200B Cooling Performance 1 Gross Cooling Capacity, BTUH (KW) Matched Air Handler, BTUH (KW) 166,000 (48.57) 216,000 (63.24) Condensing Unit Only 2 , BTUH (KW) 161,000 (47.04) 209,000 (61.18) ARI Net Cooling Cap...
Page 24 - Table PD-13— Evaporator Fan Performance — TWE050A
TWA-PRC001-EN 24 PerformanceData (Air Handler) Table PD-14 — Blower Speeds Motor DriveTurns Open Drive 6 5 4 3 2 1 0 Standard N/A 590 639 688 737 786 835 High Static N/A 713 772 832 891 951 1009 Table PD-13 — Evaporator Fan Performance — TWE050A External Static Pressure (Inches of Water Gauge) .10...
Page 27 - Table PD-19 — Evaporator Fan Performance TWE155B
27 TWA-PRC001-EN PerformanceData (Air Handler) Table PD-20— Blower Speeds Motor Sheave Turns Open Drive 6 5 4 3 2 1 0 Standard 619 648 677 705 734 763 N/A High Static 777 806 835 863 892 921 950 Table PD-19 — Evaporator Fan Performance — TWE155B External Static Pressure (Inches of Water Column) .10&...
Page 29 - PD-24 — Static Pressure Drop Through Accessories — Air Handler
29 TWA-PRC001-EN PerformanceData Table PD-23— Discharge Plenum And Grille Assembly Throw Distance — Air Handler Unit Louver Angle Deflection Position Model No. CFM L/S Straight 20, Ft. (m) 40, Ft. (m) 55, Ft. (m) 1400 661 38 (11.6) 24 (7.3) 22 (6.7) 18 (5.5) 1600 755 42 (12.8) 31 (9.4) 26 (7.9) 20 (...
Page 30 - Table PD-25 — Auxiliary Electric Heat Capacity — Air Handler
TWA-PRC001-EN 30 PerformanceData Table PD-25 — Auxiliary Electric Heat Capacity — Air Handler No. Stage 1 Stage 2 Total Unit Total of KW Btuh KW KW Btuh KW Btuh KW Model No. KW Stages Input Output Output Input Output Output Output Output TWE050, 075,100 3.47 1 3.47 11,851 3.47 — — — 11,851 3.47 6.92...
Page 34 - Heat Pump — Single Compressor
TWA-PRC001-EN 34 TypicalWiring (Heat Pump) Heat Pump — Single Compressor Typical unit wiring diagram. For specificwiring, see individual Service Facts.
Page 36 - Heat Pump — Dual Compressors
TWA-PRC001-EN 36 Heat Pump — Dual Compressors Typical unit wiring diagram. For specificwiring, see individual Service Facts. (Heat Pump) TypicalWiring
Page 38 - Air Handler
TWA-PRC001-EN 38 TypicalWiring (Air Handler) Air Handler Typical unit wiring diagram. For specificwiring, see individual Service Facts.
Page 39 - Figure DD-1 — TWA075 Heat Pump; All dimensions are in inches and millimeters.
39 TWA-PRC001-EN (Heat Pump) DimensionalData Figure DD-1 — TWA075 Heat Pump All dimensions are in inches and millimeters. Note 1 MINIMUM CLEARANCE FOR PROPEROPERATION IS 36 INCHES (914 MM)FROM WALLS, SHRUBBERY, PRIVACYFENCES, ETC. MINIMUM CLEARANCEBETWEEN ADJACENT UNITS IS 72INCHES (1828 MM)
Page 41 - Figure DD-3 — TWA155B Heat Pump
41 TWA-PRC001-EN DimensionalData (Heat Pump) Figure DD-3 — TWA155B Heat Pump All dimensions are in inches and millimeters. Note 1 MINIMUM CLEARANCE FOR PROPEROPERATION IS 36 INCHES (914 MM)FROM WALLS, SHRUBBERY, PRIVACYFENCES, ETC. MINIMUM CLEARANCEBETWEEN ADJACENT UNITS IS 72INCHES (1828 MM)
Page 42 - Figure DD-4 — TWA200B Heat Pump
TWA-PRC001-EN 42 (Heat Pump) DimensionalData Figure DD-4 — TWA200B Heat Pump All dimensions are in inches and millimeters. Note 1 MINIMUM CLEARANCE FOR PROPEROPERATION IS 36 INCHES (914 MM)FROM WALLS, SHRUBBERY, PRIVACYFENCES, ETC. MINIMUM CLEARANCEBETWEEN ADJACENT UNITS IS 72INCHES (1828 MM)
Page 43 - Figure DD-5 — TWE050A Air Handlers
43 TWA-PRC001-EN (Air Handler) DimensionalData Figure DD-5 — TWE050A Air Handlers All dimensions are in inches and millimeters. Notes:1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on eith...
Page 44 - Figure DD-6 — TWE075A Air Handler
TWA-PRC001-EN 44 (Air Handler) DimensionalData Figure DD-6 — TWE075A Air Handler All dimensions are in inches and millimeters. Notes:1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on eithe...
Page 45 - Figure DD-7— TWE100A Air Handler
45 TWA-PRC001-EN Notes:1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontalconfiguration. Plastic drain pan access plate on the end of ...
Page 46 - Figure DD-8— TWE100B Air Handler
TWA-PRC001-EN 46 DimensionalData (Air Handler) Notes:1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontalconfiguration. Plastic drain p...
Page 48 - Figure DD-10— TWE155B Air Handler
TWA-PRC001-EN 48 DimensionalData Figure DD-10— TWE155B Air Handler All dimensions are in inches and millimeters. (Air Handler) Notes:1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on eithe...
Page 49 - Figure DD-11 — TWE200B Air Handler
49 TWA-PRC001-EN DimensionalData (Air Handlers) Figure DD-11 — TWE200B Air Handler All dimensions are in inches and millimeters. Notes:1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on eit...
Page 51 - Figure DD-14 — Electric Heater for TWE155 and 200 Air Handlers
51 TWA-PRC001-EN DimensionalData (Accessories) Figure DD-13— Electric Heater for TWE050, 075, 100 Air Handlers All dimensions are in inches and millimeters. Figure DD-14 — Electric Heater for TWE155 and 200 Air Handlers
Page 52 - Figure DD-16 — Subbase
TWA-PRC001-EN 52 DimensionalData (Accessories) Figure DD-15 — Discharge Plenum and GrilleAll dimensions are in inches and millimeters. Figure DD-16 — Subbase Table DD-5 — Subbase Dimensions — in.(mm) Model Model No. A B TWE050 BAYBASE001 38 22 (965.2) (558.8) TWE075 BAYBASE002 47 1 / 2 25 (1206.5) (...
Page 53 - Weights
53 TWA-PRC001-EN Weights (Heat Pumps) TWA075A, 100A Table W-1 — Unit and Corner Weights — Lbs (Kg) Unit Shipping Net Corner Weights Model No. Maximum — lbs (Kg) Maximum — lbs (Kg) 1 2 3 4 TWA075A 390 343 112 89 63 79 (176.9) (155.6) (50.8) (40.4) (28.6) (35.8) TWA100A 468 414 146 106 68 94 (212.3) (...
Page 54 - Vertical
TWA-PRC001-EN 54 Weights Table W-3 — Air Handlers, Coils, And Corner Weights — Lbs (Kg) 1 Unit Shipping Net Corner Weights — Vertical Corner Weights — Horizontal Model No. Maximum (lbs) Maximum (lbs) #1 #2 #3 #4 A B C D TWE050 298 262 59 59 59 59 54 64 64 54 (135) (118.9) (26.8) (26.8) (26.8) (26.8)...
Page 55 - Heat Pumps; Controls; This
55 TWA-PRC001-EN MechanicalSpecifications Heat Pumps GeneralUnit shall be assembled on heavy gaugesteel mounting/lifting rails and shall beweather proofed. Unit shall include ahermetic scroll or reciprocatingcompressor(s), plate fin condenser coil,fans and motors, controls, and holdingcharge of nitr...
Page 56 - Air Handlers; — The accessory
TWA-PRC001-EN 56 Air Handlers GeneralAir handler units shall be completelyfactory assembled including coil,condensate drain pan, fan motor(s),filters, and controls in an insulatedcasing that can be applied in eithervertical or horizontal configuration. Unitshall be rated and tested in accordancewith...