Page 2 - Introduction; It’s Hard To Stop A Trane.
RT-PRC002-EN © 2004 American Standard Inc. All rights reserved Introduction Packaged RooftopAir Conditioners Through the years, Trane has designedand developed the most complete line ofPackaged Rooftop products available inthe market today. Trane was the first tointroduce the Micro—microelectronic u...
Page 3 - Contents; Model Number Description
3 RT-PRC002-EN Contents Introduction Features and Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Cooling PerformanceFan PerformanceHeat Performance Controls Electric Power Dimension and Weights Mechanical Specifications 2 4 9 10 12 13 1...
Page 5 - Quality and Reliability; —prevents the unit from short cycling,; ReliaTel Makes Testing Easy; ReliaTelTM
5 RT-PRC002-EN Features andBenefits Easy to Install, Service andMaintain Because today’s owners are very cost-conscious when it comes to service andmaintenance, the Trane Voyager wasdesigned with direct input from servicecontractors. This valuable informationhelped to design a product that would get...
Page 7 - Rigorous Testing; VariTracTM
7 RT-PRC002-EN Features andBenefits Reference or Comparative Enthalpy Measures and communicates humiditywhile maximizing comfort control. Sloped Drain Pans Standard on every unit. Standardized Components Components are placed in the samelocation on all Voyager units. Familiarizeyourself with one Voy...
Page 11 - SA; Dehumidification Selection; Plot on psychrometric chart.; supply airflow; and leaving; evaporator coil
11 RT-PRC002-EN SelectionProcedure MA' MA' SA' SA' RA' RA' OA OA OA OA RA' 68°F DB,67°F WB 75°F DB,52% RH MA' 72.2°F DB65°F WB SA' 47°F DB SA SA REHEAT SA 73°F DB Dehumidification Selection Determine normal unit cooling andheating capacities as previouslydescribed in the selection procedures onprior...
Page 13 - Standard Efficiency; Table GD - 1— General Data
13 RT-PRC002-EN (12½ , 15 Ton) Standard Efficiency GeneralData 12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units TC*150D3, D4, DW, DK TC*180B3, B4, BW, BK Cooling Performance 1 Gross Cooling Capacity 150,000 182,000 EER 2 9.8 9.9 Nominal CFM / ARI Rated CFM 5,000/4,400 6,000...
Page 14 - Table GD - 2 — General Data
14 RT-PRC002-EN (17½, 20, 25 Ton) Standard Efficiency GeneralData Table GD - 2 — General Data 17½ Ton 20 Ton 25 Ton Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units TC*210C3, C4, CW, CK TC*240B3, B4, BW, BK TC*300B3, B4, BW, BK Cooling Performance 1 Gross Coo...
Page 15 - High Efficiency; Table GD - 3 — General Data
15 RT-PRC002-EN (12½, 15 Ton) High Efficiency GeneralData 12½ Ton 15 Ton Downflow and Horizontal Downflow and Horizontal TC*151C3,C4,CW TC*181C3,C4, CW Cooling Performance 1 Gross Cooling Capacity 154,000 189,000 EER 2 11.3 11.5 8 Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300 ARI Net Cooling C...
Page 16 - Table GD - 4 — General Data
16 RT-PRC002-EN GeneralData (17½ , 20, 25 Ton) High Efficiency *Indicates both downflow and horizontal units. Table GD - 4 — General Data 17½ Ton 20 Ton 25 Ton Downflow and Horizontal Downflow and Horizontal Downflow and Horizontal TC*211C3,C4,CW TC*241C3,C4,CW TC*301C3,C4,CW Cooling Performance 1 G...
Page 29 - Table PD-15 — Gross Cooling Capacities (MBH)25 Ton Three Phase TC
29 RT-PRC002-EN PerformanceData (25 Ton)High Efficiency Table PD-15 — Gross Cooling Capacities (MBH)25 Ton Three Phase TC * 301C3, C4, CW - Standard Refrigeration System Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH...
Page 30 - Table PD-16 — Gross Cooling Capacities (MBH)25 Ton Three PhaseTC
30 RT-PRC002-EN PerformanceData (25 Ton)High Efficiency Table PD-16 — Gross Cooling Capacities (MBH)25 Ton Three PhaseTC * 301C3, C4, CW— TXV Option Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC ...
Page 31 - Table PD-17 — Evaporator Fan Performance — 121⁄2 Ton — TC*150D — Continued; Table PD-17 — Evaporator Fan Performance — 121⁄2Ton — TC*150D
31 RT-PRC002-EN Table PD-17 — Evaporator Fan Performance — 12½ Ton — TC*150D — Continued External Static Pressure (Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor & Sheaves ...
Page 32 - Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B
32 RT-PRC002-EN For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.Fan motor heat (MBH) = 3.15 x Fan BHPData includes pressure drop ...
Page 33 - Table PD-19 — Evaporator Fan Performance — 171⁄2 Ton — TC*210C — Continued; Table PD-19 — Evaporator Fan Performance — 171⁄2 Ton — TC*210C
33 RT-PRC002-EN PerformanceData (17½Ton) Standard Efficiency *Indicates both downflow and horizontal units . For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.For Standard Motor & Low Static Drive Accessory Fan Speed (R...
Page 34 - Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B — Continued; Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B
34 RT-PRC002-EN *Indicates both downflow and horizontal units . PerformanceData (20 Ton) Standard Efficiency For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.For Oversized Evaporator Fan Speed (...
Page 35 - Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B; Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B — Continued
35 RT-PRC002-EN PerformanceData (25 Ton) Standard Efficiency *Indicates both downflow and horizontal units . Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM...
Page 36 - Table PD-22 — Evaporator Fan Performance — 121⁄2 Ton — TCD151C — Continued
36 RT-PRC002-EN (12½ Ton) High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. *Unit applications bel...
Page 37 - Table PD-23 — Evaporator Fan Performance — 121⁄2 Ton — T*D151C — Continued
37 RT-PRC002-EN (12½ Ton) High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.Table includes Dehumidi...
Page 38 - Table PD-24 — Evaporator Fan Performance — 121⁄2 Ton — TCH151C — Continued
38 RT-PRC002-EN (12½ Ton) High Efficiency PerformanceData Table PD-24 — Evaporator Fan Performance — 12½Ton — TCH151C — Standard Refrigeration System External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BH...
Page 39 - Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Continued
39 RT-PRC002-EN PerformanceData (15 Ton) High Efficiency *Indicates both downflow and horizontal units . Factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested tooperate reliably and continuously at all cataloged conditions.Using the full horse...
Page 40 - Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Continued
40 RT-PRC002-EN PerformanceData (15 Ton) High Efficiency Factory supplied motors, in commercial equipment, aredefinite purpose motors, specifically designed and tested tooperate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shownin our tab...
Page 41 - Table PD-27— Evaporator Fan Performance — 171⁄2 Ton — TC*211C — Continued
41 RT-PRC002-EN PerformanceData (17½ Ton) High Efficiency *Indicates both downflow and horizontal units . Table PD-27 — Evaporator Fan Performance — 17½ Ton — TC*211C — Standard or TXV Refrigeration System External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BH...
Page 42 - Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Continued
42 RT-PRC002-EN PerformanceData (20 Ton) High Efficiency For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.For Oversized Evaporator Fan Speed (RPM), reference Table PD-33. *Unit applications belo...
Page 43 - Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Continued
43 RT-PRC002-EN PerformanceData (20 Ton) High Efficiency For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.Table includes Dehumidif...
Page 44 - Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Continued
44 RT-PRC002-EN PerformanceData (25 Ton) High Efficiency *Indicates both downflow and horizontal units . For Standard Evaporator Fan Speed (RPM), reference Table PD-31.For Standard Motor & High Static Drive Accessory Fan Speed (RPM),reference Table PD-32.For Standard Motor & Low Static Drive...
Page 45 - Table PD-34 — Standard Motor & Low Static Fan Drive
45 RT-PRC002-EN (12½-25 Ton) PerformanceData *Indicates both downflow and horizontal units. Table PD-31— Standard Motor & Drive/Fan Speed (Rpm) Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Tons Model No. Open Open Open Open Open Open Closed TC*150D3,4,W, TC*151C3,4,W 640 680 720 760 800 8...
Page 47 - Table PD-36 — Auxiliary Electric Heat Capacity; Table PD-38 — Air Temperature Rise Across Electric Heaters (Degree F)
47 RT-PRC002-EN Table PD-36 — Auxiliary Electric Heat Capacity Total2 Stage1 Stage 2 Unit KW MBH No. of KW MBH KW MBH Tons Model No. Input 1 Output 1 Stages Input 1 Output 1 Input 1 Output 1 18.00 61.47 1 18.00 61.47 — — TC*150D3,D4,DW,DK 27.00 4 92.15 2 9.00 30.72 18.00 61.43 12½-15 TC*180B3,B4,BW,...
Page 48 - Table PD-39— Hot Gas Reheat Temperature Rise
48 RT-PRC002-EN Table PD-39— Hot Gas Reheat Temperature Rise 1,2,3 Leaving Evaporator Dry Bulb [F] 1 Tons SCFM 35 40 45 50 55 60 65 2500 23.4 23.8 25.0 26.9 29.5 32.9 37.0 3000 21.4 21.6 22.5 24.0 26.0 28.7 31.9 3500 19.5 19.7 20.4 21.5 23.1 25.2 27.7 12½ 4000 17.8 18.1 18.6 19.6 20.9 22.5 24.5 4500...
Page 49 - Controls; Field Installed Control Options
49 RT-PRC002-EN Controls Programmable Night Setback Auto or manual changeover with seven-day programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. Allprogrammable sensors have System On,Heat, Cool, Service LED/indicators asstandard. Night Setback Sensors haveone (1) Occupied, one (1) Un-o...
Page 50 - Table ED-1 — Unit Wiring — Standard Efficiency
50 RT-PRC002-EN *Indicates both downflow and horizontal units. ElectricalData Table ED-1 — Unit Wiring — Standard Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size or Maximum Circuit Size or Maximum Tons Model No...
Page 52 - 80 Volts Three Phase
52 RT-PRC002-EN Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only), continued Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. KW Rating 1 Stages MCA Max Circuit MCA...
Page 60 - 60 Volts Three Phase
60 RT-PRC002-EN Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and 151/181/ 241 Reheat Option(Downflow Only) Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With M...
Page 61 - 75 Volts Three Phase
61 RT-PRC002-EN ElectricalData (High Efficiency) Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and 151/181/ 241 Reheat Option(Downflow Only), continued Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control M...
Page 62 - Refrigeration System
62 RT-PRC002-EN ElectricalData *Indicates both downflow and horizontal units. (High Efficiency) Compressor Motors Condenser Fan Motors Unit Amps 1 Amps 1 Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA TCD151C3 2 208-230 3 5.7/5.7 3450 18.6 156 2 1 .50 3.2 8.8 12½ TCD151C4 2 460...
Page 64 - Table ED-15 — Electrical Characteristics — Power Exhaust Accessory
64 RT-PRC002-EN Table ED-15 — Electrical Characteristics — Power Exhaust Accessory AccessoryOperating \Amps Tons Voltage Phase HP RPM FLA LRA 12½ 1, 2 208-230 1 3/4 1040 6.6 13.5 15, 17½ 460 1 3/4 1040 3.2 8.4 20, 25 575 1 3/4 1040 2.1 5.2 Notes:1. 12½ Ton Standard Unit.2. 12½ Ton High Efficiency Un...
Page 65 - Zone Sensors —Typical Number Of Wires; Programmable Night Setback with
65 RT-PRC002-EN JobsiteConnections For specific wiring information, see the installation instructions.All wiring except power wires is low voltage.All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed...
Page 70 - All dimensions are in inches.
70 RT-PRC002-EN DimensionalData (12½ Ton) High Efficiency (12½, 15, 17½ Ton) Standard Efficiency All dimensions are in inches. Note: Duct flanges mount 7-7/16" downinside the curb on the 1½" curb flanges.See recommended duct dimensions onthe next page.Roofcurb is intended for downflow useonl...
Page 71 - Downflow Duct Connections — Field Fabricated
71 RT-PRC002-EN DimensionalData RETURN SUPPLY 1 1\2"PERIMETERCURB FLANGE 59 7/16" 17 7/8" 26 5/16" 52 1/2" 1" 14 1/16" 7 7/16" 1" All dimensions are in inches. Downflow Duct Connections — Field Fabricated Note:Duct flanges mount 7-7/16" down insidethe curb on ...
Page 72 - Downflow Unit Clearance
72 RT-PRC002-EN DimensionalData (15-25 Ton) High Efficiency (20, 25 Ton) Standard Efficiency All dimensions are in inches. Note:Duct flanges mount 7-7/16" down insidethe curb on the 1½" curb flanges. Seerecommended duct dimensions on thenext page.Roofcurb is intended for downflow useonly. Do...
Page 73 - RETURN
73 RT-PRC002-EN DimensionalData (15-25 Ton) High Efficiency (20, 25 Ton) Standard Efficiency Downflow Duct Connections — Field Fabricated All dimensions are in inches. RETURN SUPPLY 1 1\2"PERIMETERCURB FLANGE 73 7/16" 19 5/16" 26 5/16" 66 1/2" 1" 14 1/16" 7 7/16" 1...
Page 78 - Weights
78 RT-PRC002-EN Weights (12½-25 Ton) Table W-1 — Accessory Net Weights (Lbs) 1, 7 Oversized High 5 Low 5 Economizer Outside Air Damper Power Roof Motor Static Static Model No. Net Manual Motorized Exhaust 4 Curb 4 Adder Drive Drive TCD150D, 180BTCD121,151C, TCD210C 65 32 60 95 205 5 2 2 TCD240BTCD18...
Page 81 - inch high
81 RT-PRC002-EN MechanicalSpecifications General The units shall be dedicated downflow orhorizontal airflow. The operating rangeshall be between 115°F and 0°F in coolingas standard from the factory for all units.Cooling performance shall be rated inaccordance with ARI testing procedures.All units sh...
Page 82 - Factory Installed Options; The disconnect switch will be sized
82 RT-PRC002-EN MechanicalSpecifications Controls Unit shall be completely factory wiredwith necessary controls and contactorpressure lugs or terminal block for powerwiring. Unit shall provide an externallocation for mounting a fused disconnectdevice. ReliaTel controls shall be providedfor all 24 vo...
Page 84 - Field Installed Options
84 RT-PRC002-EN Field Installed Options CO 2 Sensing The CO 2 sensor has the ability to monitor space occupancy levels within thebuilding by measuring the parts permillion of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO 2 space ventil...