Page 2 - Warnings, Cautions and Notices; Note that warnings, cautions and notices appear at; Important; WARNING; Overview of Manual; result in death or serious injury.
© 2008 Trane All rights reserved SS-SVX09A-EN Warnings, Cautions and Notices Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in...
Page 3 - Table of Contents; General Information
Table of Contents SS-SVX09A-EN 3 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation . . . . . . . . . . . . . ....
Page 5 - Model Number Description; Unit Nameplate
SS-SVX09A-EN 5 General Information Model Number Description All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided below. Its use will enable the owner/operator, in...
Page 6 - Nitrogen
6 SS-SVX09A-EN General Information Evaporator Nameplate (EVP Chiller Applications Only) The nameplate is located on the same side of the refrigerant connections near the top. To view the nameplate, remove the tape over the area and spread the insulation. Retape the insulation after viewing. Unit Des...
Page 7 - Installation; Unit Inspection; As soon as the unit arrives at the job site; file a claim with the; Figure 2; EVP Chiller Considerations; The EVP chiller must be installed indoors unless:
SS-SVX09A-EN 7 Installation Unit Inspection As soon as the unit arrives at the job site [ ] Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data). [ ] Verify that the power supply complies with the unit nameplate specifications. [ ] Visuall...
Page 8 - Unit Dimensions & Weight Information
8 SS-SVX09A-EN Installation NOTICE To prevent internal chiller damage due to freezing, do not install the BPHE chiller outdoors without adequate freeze protection. Allow adequate clearance for water and refrigerant piping connections, space to perform service procedures, i.e. read gauges, thermomete...
Page 10 - RAUC-C20 Unit Dimensional Data & Recommended Clearances
10 SS-SVX09A-EN Installation Figure 3. RAUC-C20 Unit Dimensional Data & Recommended Clearances
Page 11 - RAUC-C25 Unit Dimensional Data & Recommended Clearances
SS-SVX09A-EN 11 Installation Figure 4. RAUC-C25 Unit Dimensional Data & Recommended Clearances
Page 12 - RAUC-C30 Unit Dimensional Data & Recommended Clearances
12 SS-SVX09A-EN Installation Figure 5. RAUC-C30 Unit Dimensional Data & Recommended Clearances
Page 13 - RAUC-C40 Unit Dimensional Data & Recommended Clearances
SS-SVX09A-EN 13 Installation Figure 6. RAUC-C40 Unit Dimensional Data & Recommended Clearances
Page 14 - RAUC-C50 Unit Dimensional Data & Recommended Clearances
14 SS-SVX09A-EN Installation Figure 7. RAUC-C50 Unit Dimensional Data & Recommended Clearances
Page 15 - RAUC-C60 Unit Dimensional Data & Recommended Clearances
SS-SVX09A-EN 15 Installation Figure 8. RAUC-C60 Unit Dimensional Data & Recommended Clearances
Page 16 - All water connections are Victaulic.; BPHE 20 Evaporator Chiller Dimensions
16 SS-SVX09A-EN Installation Note: All water connections are Victaulic. Figure 9. BPHE 20 Evaporator Chiller Dimensions Evaporator mounting brakets and insulation are provided with ChillerBPHE Accessory for field installation - Field provided vinyl tape is required to seal insulation edges after ins...
Page 17 - Figure 10. BPHE 25 Evaporator Chiller Dimensions
SS-SVX09A-EN 17 Installation Note: All water connections are Victaulic. Figure 10. BPHE 25 Evaporator Chiller Dimensions 7.994 8.084 17.670 6.440 3.331 2.431 23.432 1.130 ID 2.431 2.261 17.720 2.261 3.451 SUCTION LIQUID ENTERING WA T E R LEA V ING WA T E R 2X Ø2.00 2.138 Ø ID SW AGELOK B-4-P 1/4"...
Page 18 - Figure 11. BPHE 30 Evaporator Chiller Dimensions
18 SS-SVX09A-EN Installation Note: All water connections are Victaulic. Figure 11. BPHE 30 Evaporator Chiller Dimensions 17.670 2.431 3.331 23.432 10.004 6.440 2.431 2.261 10.604 1.130 ID 2.138 ID 2.261 2.261 17.720 3.451 SUCTION LIQUID SW AGELOK B-4-P 1/4" NPT MALE PIPE PLUG OR EQUIV A LENT FIE...
Page 19 - Figure 12. BPHE 40 Evaporator Chiller Dimensions
SS-SVX09A-EN 19 Installation Note: All water connections are Victaulic. Figure 12. BPHE 40 Evaporator Chiller Dimensions 3.960 23.780 2.551 30.292 13.533 2.517 2.517 8.500 6.767 6.767 13.533 30.292 2.826 4.235 23.230 1.380 ID X 2 7.720 9.096 SUCTION CIR #1 LIQUID CIR #1 SUCTION CIR #2 LIQUID CIR #2 ...
Page 20 - Figure 13. BPHE 50 Evaporator Chiller Dimensions
20 SS-SVX09A-EN Installation Note: All water connections are Victaulic. Figure 13. BPHE 50 Evaporator Chiller Dimensions 3.960 23.780 2.551 30.292 13.533 2.517 2.517 8.500 6.766 6.767 13.533 30.292 2.827 4.235 23.230 1.380 ID X 2 8.872 9.096 SUCTION CIR #1 LIQUID CIR #1 SUCTION CIR #2 LIQUID CIR #2 ...
Page 21 - Figure 14. BPHE 60 Evaporator Chiller Dimensions
SS-SVX09A-EN 21 Installation Note: All water connections are Victaulic. Figure 14. BPHE 60 Evaporator Chiller Dimensions 3.960 23.780 2.551 30.292 13.533 2.517 2.517 8.500 6.766 6.767 13.533 30.292 2.826 4.235 23.230 1.380 ID X 2 14.858 SUCTION CIR #1 LIQUID CIR #1 SUCTION CIR #2 LIQUID CIR #2 2.138...
Page 22 - Typical Unit Weights & Point Loading Data
22 SS-SVX09A-EN Installation Table 1. Typical Unit Weights & Point Loading Data Unit Size Operating Weight Unit Weight on Isolator @ Mounting Location Location 1 2 3 4 5 6 AL CU AL CU AL CU AL CU AL CU AL CU AL CU C20 1522 1720 509 559 398 439 345 404 270 317 C25 1640 1842 555 602 421 467 378 43...
Page 23 - Rigging; the typical unit operating weights table before proceeding.
SS-SVX09A-EN 23 Installation Rigging WARNING Heavy Objects! Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. ...
Page 24 - Unit Isolation; “Neoprene isolators” or “Spring isolator” section below.; Neoprene Isolators; Table 3; Typical Neoprene Isolator Selection & Location
24 SS-SVX09A-EN Installation Unit Isolation To minimize unit sound and vibration transmission, one of the following installation methods should be used: 1. Install the unit directly on an isolated (detached) concrete pad or on isolated concrete footings located at each unit load point. 2. Install th...
Page 25 - appropriate isolator. Refer to; Leveling the Unit
SS-SVX09A-EN 25 Installation Spring Isolators Install the spring isolators at each unit mounting (load) point using the following procedure: 1. Elevate the unit (one side at a time) to allow access to the base rail mounting holes. WARNING Heavy Objects! Use solid type blocks, i.e. 4" X 4" wo...
Page 26 - Typical Spring Isolator Selection & Location; Shipping Fasteners; Compressor Shipping Hardware
26 SS-SVX09A-EN Installation Table 4. Typical Spring Isolator Selection & Location Shipping Fasteners Compressor Shipping Hardware Figure 16 illustrates the location of each tiedown bolt and rubber isolator bolt for the compressor assembly in each circuit. Refer to the illustration and the follo...
Page 27 - General Unit Requirements; [ ] Install a properly sized filter drier in each liquid line.
SS-SVX09A-EN 27 Installation General Unit Requirements The checklist listed below is a summary of the steps required to successfully install a commercial air cooled condenser. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does n...
Page 29 - ”No Controls” Units
SS-SVX09A-EN 29 Installation WARNING Ground Wire! All field-installed wiring must be completed by qualified personnel. All field-installed wiring must comply with NEC and applicable local codes. Failure to follow this instruction could result in death or serious injuries. WARNING Grounding Required!...
Page 30 - Figure 17. EVP Chiller Piping
30 SS-SVX09A-EN Installation WARNING Ground Wire! All field-installed wiring must be completed by qualified personnel. All field-installed wiring must comply with NEC and applicable local codes. Failure to follow this instruction could result in death or serious injuries. WARNING Grounding Required!...
Page 31 - EVP Chiller Units; Refrigerant Line Components; control for coil frost protection, and ball shutoff valves.
SS-SVX09A-EN 31 Installation Low Voltage Wiring (AC & DC) WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before se...
Page 32 - Liquid Line Moisture Indicator Sight Glass; Refer to; Liquid Line Solenoid Valves; Refer to; Ball Shutoff Valves; Filter/Filter Drier Recommendations
32 SS-SVX09A-EN Installation Refer to Table 5 for filter/filter drier recommendations. Liquid Line Moisture Indicator Sight Glass To aid in troubleshooting, install a moisture indicator sight glass in the liquid line near the evaporator, down stream of the solenoid valve prior to any branch takeoffs...
Page 33 - Split System Component Number Definitions; Figure 18. Typical Placement of Split System piping Components
SS-SVX09A-EN 33 Installation Split System Component Number Definitions (1)Interconnecting Suction Line Tubing (2)Suction Line Filter (3)Shutoff Valves - Manual ball valves (4)Interconnecting Liquid Line Tubing. If risers exceed 10 feet, Trane must review the application (5)Shutoff valves - Manual ba...
Page 34 - Refrigerant Piping; Use Type “L” refrigerant grade copper tubing only.; Suction Line Piping; Do not use suction line traps.; Suction Line Interconnecting Tubing
34 SS-SVX09A-EN Installation Refrigerant Piping Refrigerant piping must be properly sized and applied. These two factors have a very significant effect on both system performance and reliability. NOTICE Use Type “L” refrigerant grade copper tubing only. Refrigerant Piping should be sized and laid ou...
Page 35 - Liquid Line Piping; Avoid putting liquid lines underground.; Liquid Line Interconnecting Tubing
SS-SVX09A-EN 35 Installation Liquid Line Piping Liquid line sizes are based on their ability to provide a minimum of 5 degrees F (2.7ºC) of sub-cooling at the expansion valve throughout the unit’s operating system. Increasing the liquid line size does not increase the available sub-cooling. The unif...
Page 36 - Evaporator Piping; Install the TXV directly to the unit liquid connection.; Figure 19. Typical Coil Piping For Dual Circuit Units
36 SS-SVX09A-EN Installation Evaporator Piping 1. Install the TXV directly to the unit liquid connection. 2. Locate the TXV bulb midway between the 90 degrees bends on top of the suction line as illustrated in Figure 19 and Figure 20 . 3. Secure the bulb to the suction line with two clamps provided ...
Page 37 - Hot Gas Bypass for Commercial Comfort-Cooling Applications
SS-SVX09A-EN 37 Installation Hot Gas Bypass for Commercial Comfort-Cooling Applications Hot gas bypass is not recommended for use on RAUC units. Frostat™ is the preferred method of protecting the evaporator from freeze-up. It turns off compressors when the coil frosting is sensed. The compressor is ...
Page 38 - Brazing Procedures; carefully reamed to remove any burrs.
38 SS-SVX09A-EN Installation Brazing Procedures WARNING Hazard of Explosion and Deadly Gases! Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines establi...
Page 39 - Leak Testing Procedure; refrigerant to raise the high side pressure to 12 to 15 psig.
SS-SVX09A-EN 39 Installation Leak Testing Procedure WARNING Hazard of Explosion! Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrig...
Page 40 - Chilled Water Piping; Figure 9
40 SS-SVX09A-EN Installation 7. If a leak is located, use proper procedures to remove the refrigerant/nitrogen mixture, break the connection and remake as a new joint. Retest for leaks after making repairs. 8. Open the liquid line service valve and the compressor discharge service valve. Chilled Wat...
Page 41 - Figure 21. Evaporator Water-Pressure Drop
SS-SVX09A-EN 41 Installation Note: Factor to convert “Feet of Water” to “Lbs. per Sq. Inch” (PSI): 2.3 Feet of Water = 1 PSI Figure 21. Evaporator Water-Pressure Drop
Page 42 - Install a flow switch or other flow sensing device, illustrated in
42 SS-SVX09A-EN Installation Air Vents Vents must be installed at high points in the piping system to facilitate air purging during the filling process. Water Pressure Gauges Install pressure gauge(s) to monitor the entering and leaving chilled water pressure. NOTICE To prevent evaporator damage, do...
Page 43 - Freezestat; for the recommended location.; Figure 22. Typical Piping Recommendations
SS-SVX09A-EN 43 Installation NOTICE Failure to use thermal paste could result in erratic temperature sensing resulting in equipment damage. Freezestat A Bulb-well (located inside the remote panel) must be installed in the leaving water piping as close to the chiller barrel as possible. It should be ...
Page 44 - Final Water Piping Connections; Connect the water pipe to the EVP chiller.; Figure 23. Optional Flow Switch Illustration
44 SS-SVX09A-EN Installation NOTICE Failure to use thermal paste could result in erratic temperature sensing resulting in equipment damage. Final Water Piping Connections 1. All water piping to the system should be flushed thoroughly before making the final connections. NOTICE If an acidic commercia...
Page 45 - Field Installed Power Wiring; Figure 3; Disconnect Switch External Handle (Factory Mounted Option)
SS-SVX09A-EN 45 Installation 3. Install the drain plug, (if no drain is used) or ensure the drain shutoff valve is closed. 4. While filling the chiller system with solution, vent the air from the system at the highest points. NOTICE To prevent possible damage to the equipment, do not use untreated o...
Page 46 - Main Unit Power Wiring; Table 7
46 SS-SVX09A-EN Installation Main Unit Power Wiring WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing co...
Page 47 - Power Wire Sizing and Protection Device; Equations; LOAD 1 = CURRENT OF THE LARGEST MOTOR (COMPRESSOR OR FAN MOTOR); MCA
SS-SVX09A-EN 47 Installation Power Wire Sizing and Protection Device Equations To correctly size the main power wiring for the unit, use the appropriate calculation(s) listed below. Read the load definitions that follow and use Calculation #1 for determining the MCA (Minimum Circuit Ampacity), MOP (...
Page 48 - Electrical Service Sizing Data
48 SS-SVX09A-EN Installation Calculation #2 Disconnect Switch Sizing (DSS) DSS = 1.15 X (LOAD 1 + LOAD 2 + LOAD 4) Table 8. Electrical Service Sizing Data Model Electrical Charac. Unit Characteristics Condenser Fan Motor Compressor Motor Allow- able Voltage Range Min. Circuit Amp Max. Over- currentP...
Page 49 - Field Installed Control Wiring; Controls Using 115 VAC; Electrical Service Sizing Data (continued)
SS-SVX09A-EN 49 Installation Field Installed Control Wiring WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before serv...
Page 50 - Hot Gas Bypass
50 SS-SVX09A-EN Installation liquid line solenoid valve(s). Supply Fan Interlock (Control options utilizing an Air Handler) The normally open evaporator fan interlock auxiliary contacts and the evaporator fan controls; system On/Off switch, fan starter/contactor, and overloads, must be wired as illu...
Page 51 - Controls using 24 VAC; Controls using DC Analog Input/Outputs; AC Conductors
SS-SVX09A-EN 51 Installation Controls using 24 VAC WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing cou...
Page 52 - These components may include:; Economizer Actuator Circuit; Table 10. DC Conductors
52 SS-SVX09A-EN Installation These components may include: Field installed Discharge Duct Sensor (6RT1 CV units); Field installed Return Duct Sensor (6RT6 CV units); Field installed Discharge Air Sensor (6RT3 VAV units); Field installed Chilled Water Sensor (6RT2 EVP units); 1. Wiring for the compon...
Page 53 - No System Control; Temperature Control Parameters; Economizer Actuator Circuit Legend
SS-SVX09A-EN 53 Installation No System Control Temperature Control Parameters Each unit ordered with the “No Controls” option, requires a field provided and field wired temperature controller. Single refrigerant circuit units require a 2-step control device, and dual refrigerant circuit units requir...
Page 54 - Refer to Wiring Notes on
54 SS-SVX09A-EN Installation Refer to Wiring Notes on p. 55 Figure 25. Field Connection Diagram or RAUC-C20 - C60 “No System Controls” Applications
Page 55 - Field Connection Diagram Notes for all System Control Options
SS-SVX09A-EN 55 Installation Field Connection Diagram Notes for all System Control Options
Page 56 - Variable Air Volume Control (Honeywell W7100A)
56 SS-SVX09A-EN Installation Variable Air Volume Control (Honeywell W7100A) In a variable air volume system, the desired space temperature is maintained by varying the amount of conditioned air being delivered to the space. As the cooling requirements of the space decreases, less air is delivered to...
Page 57 - Suction Line Thermostat; Before installing any connecting wiring, refer to; Night Setback; Figure 26. 6RT3 Discharge Air Sensor Assembly
SS-SVX09A-EN 57 Installation Suction Line Thermostat Each unit ordered with variable air volume controls (digit 9 in the model number) is shipped with a suction line thermostat (6S63) that must be field installed. Locate the thermostat close to the expansion valve bulb on a slightly flattened portio...
Page 58 - Refer to Wiring Notes on Page; EVP Chiller Control; EVP Remote Panel w/ W7100G Controller
58 SS-SVX09A-EN Installation Refer to Wiring Notes on Page p. 55 EVP Chiller Control Each unit ordered for EVP Chiller applications (digit 9 in the model number), is shipped with the following controls: EVP Remote Panel w/ W7100G Controller Freezestat (6S12) Chiller Water Temperature Sensor (6RT2) F...
Page 59 - connection diagram illustrated in; W7100G Discharge Chilled Water Controller
SS-SVX09A-EN 59 Installation connection diagram illustrated in Figure 29 for the interconnecting points between the remote panel and the unit’s control panel. WARNING Ground Wire! All field-installed wiring must be completed by qualified personnel. All field-installed wiring must comply with NEC and...
Page 60 - Chilled Water Temperature Sensor (Honeywell 6RT2); diagram illustrated in; Figure 28. EVP Chiller Remote Panel
60 SS-SVX09A-EN Installation Chilled Water Temperature Sensor (Honeywell 6RT2) With the sensor installed in its proper location within the chilled water piping ( Figure 18 ), connect shielded cable (Belden 8760 or equivalent) from the sensor leads to the leads inside the remote panel. Refer to Figur...
Page 61 - Outside Air Thermostat (5S57 Field Provided)
SS-SVX09A-EN 61 Installation Outside Air Thermostat (5S57 Field Provided) The setpoint for the outside air thermostat is based upon the working ambient selected when the unit was ordered. A Zero (“0”) in the 11th digit of the model number indicates the system is designed for standard ambient operati...
Page 65 - for installation and; . As shipped form the
SS-SVX09A-EN 65 Installation Discharge Air Sensor (Honeywell 6RT1) A discharge air sensor ships with each unit when the constant volume control option is ordered. The sensor should be installed in a turbulent free area of the discharge air duct at a location that will provide accurate supply air sen...
Page 67 - Figure 33. 6RT1 Discharge Air Sensor Assembly
SS-SVX09A-EN 67 Installation Figure 33. 6RT1 Discharge Air Sensor Assembly
Page 68 - System Pre-Start Procedures; for the pressure control settings and the unit wiring diagram,; EVP Chiller Applications
68 SS-SVX09A-EN System Pre-Start Procedures Use the checklist provided below in conjunction with the “General Unit Requirement” checklist” to ensure that the unit is properly installed and ready for operation. Be sure to complete all of the procedures described in this section before starting the un...
Page 69 - System Evacuation Procedures
SS-SVX09A-EN 69 System Pre-Start Procedures before filling with water to displace any air in the barrel. Close vent ports or replace the vent plug after purging or filling. [ ] Once the system has been filled, inspect the entire chilled water piping system for leaks. Make any necessary repairs befor...
Page 70 - illustrates three possible results of the “standing; Figure 34. Typical Vacuum Pump Hookup
70 SS-SVX09A-EN System Pre-Start Procedures Note: It is unlawful to release refrigerant into the atmosphere. When service procedures require working with refrigerants, the service technician must comply with all Federal, State, and local laws. Refer to the General Service Bulletin MSCU-SB-1 (latest ...
Page 71 - Discharge Air Controller Checkout (Honeywell W7100A); for terminal and control dial identification.; Figure 35. Evacuation Time vs. Pressure Rise
SS-SVX09A-EN 71 System Pre-Start Procedures Discharge Air Controller Checkout (Honeywell W7100A) Note: The following checkout procedure must be performed in its entirety and in the sequence given. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing...
Page 73 - switch to the “OFF” position.; Figure 36. W7100A Discharge Air Controller
SS-SVX09A-EN 73 System Pre-Start Procedures In approximately 5 minutes; measure the voltage across terminals R (-) & W (+). The measured voltage should drop to approximately 0.2 VDC. 20. Turn the control circuit switch 1S2, in the unit control panel, and the main power disconnect switch to the “...
Page 74 - Discharge Air Sensor Checkout (Honeywell Sensor); Use the conversion chart in; Economizer Actuator Checkout; restore power to the system.
74 SS-SVX09A-EN System Pre-Start Procedures Discharge Air Sensor Checkout (Honeywell Sensor) WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failur...
Page 75 - EVP Chiller Control Checkout (Honeywell W7100G); and T1 to simulate a discharge air temperature of 60oF.
SS-SVX09A-EN 75 System Pre-Start Procedures EVP Chiller Control Checkout (Honeywell W7100G) Note: The following checkout procedure must be performed in its entirety and in the sequence given. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Fol...
Page 76 - cooling outputs stage “On”.
76 SS-SVX09A-EN System Pre-Start Procedures 10. “Close” the main power disconnect switch and turn the control circuit switch 1S2, in the unit control panel, “ON”. WARNING High Voltage is Present at Terminal Block 1TB1 or Unit Disconnect Switch 1S1. To prevent injury or death form electrocution, it i...
Page 77 - Chilled Water Sensor Checkout (Honeywell Sensor); Figure 38. W7100G Chilled Water Controller
SS-SVX09A-EN 77 System Pre-Start Procedures Chilled Water Sensor Checkout (Honeywell Sensor) WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failur...
Page 78 - Master Energy Control Checkout; for terminal
78 SS-SVX09A-EN System Pre-Start Procedures Master Energy Control Checkout WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect po...
Page 79 - Zone Thermostat Checkout (Honeywell T7067)
SS-SVX09A-EN 79 System Pre-Start Procedures 10. Measure the voltage again across Terminals R (-) and W (+). The measured voltage should now be approximately 0.2 VDC. 11. Turn the control circuit switch 1S2, in the unit control panel, to the “OFF” position. 12. Remove the wires from Terminals R, B, W...
Page 80 - Discharge Air Sensor Checkout (Honeywell 6RT1)
80 SS-SVX09A-EN System Pre-Start Procedures Discharge Air Sensor Checkout (Honeywell 6RT1) WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure ...
Page 82 - Voltage Imbalance; The percentage of Imbalance equals:; Electrical Phasing
82 SS-SVX09A-EN System Pre-Start Procedures Voltage Imbalance Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of...
Page 83 - Sequence of Operation; monitoring the discharge air temperature sensor and; Economizer Cycle
SS-SVX09A-EN 83 System Start-Up Sequence of Operation VAV W7100A Discharge Air Controller (7U11) The discharge air controller used in Variable Air Volume applications is a Honeywell W7100A. This microprocessor controller is designed to maintain an average discharge air (D/A) temperature by: 1. monit...
Page 84 - How well the expansion valve is controlling the refrigerant flow.
84 SS-SVX09A-EN System Start-Up Chilled Water Temperature Controller (6U11) The chilled water temperature controller used with EVP chiller applications is a Honeywell W7100G. This microprocessor controller is designed to maintain an average leaving water temperature using an integrating control band...
Page 85 - Condenser Fans; illustrates the
SS-SVX09A-EN 85 System Start-Up a. Could cause serious compressor damage due to refrigerant floodback. b. Removes working surface from the evaporator normally used for heat transfer. Systems operating with superheat in excess of 16 degrees: c. Could cause excessive compressor cycling on internal win...
Page 86 - Figure 43. Condenser Fan Locations
86 SS-SVX09A-EN System Start-Up Low Ambient Dampers Low Ambient Dampers are available as a factory installed option or can be field-installed. Dampers are used to extend the operation of these units from the standard operational temperatures to a minimum of 0ºF without hot gas bypass or 10ºF with ho...
Page 87 - Low Ambient Damper Adjustment (Factory or Field Installed); for the damper locations.; Loosen the damper shaft “Locking” set screws on the actuator
SS-SVX09A-EN 87 System Start-Up Low Ambient Thermostats In addition to the low ambient dampers on 25, 30, 50 & 60 Ton units, a low ambient thermostat is installed to further restrict the airflow across the condenser by cycling the 2B3 condenser fan on 25 & 30 Ton units plus 2B6 on 50 & 6...
Page 88 - Check the flow device to ensure it opens and close properly.; Freezestat Setting; Figure 44. Evaporator Pressure Drops
88 SS-SVX09A-EN System Start-Up EVP Chiller Applications Start the chilled water circulating pump by closing the field provided pump disconnect switch and turn the pump control circuit switch 5S1 “On”. Check the flow device to ensure it opens and close properly. With water circulating through the sy...
Page 89 - “Air Over” Evaporator Application; Verifying Proper Supply Fan Rotation; Turn the 115 volt control circuit switch 1S2 to the “On” position.; a. Measure the actual fan RPM; Measure the difference between the pressures at both locations.
SS-SVX09A-EN 89 System Start-Up “Air Over” Evaporator Application Verifying Proper Supply Fan Rotation 1. Ensure that the “System” selection switch at the remote panel is in the “Off” position and the “Fan” selection switch for the appropriate controls application is in the “Auto” position. (VAV uni...
Page 90 - CAUTION
90 SS-SVX09A-EN System Start-Up 3. Plot this value onto the appropriate component pressure drop curve that shipped with the Air Handling equipment. Use the data to assist in calculating a new fan drive if the CFM is not at design specifications. 4. Plug the holes after the proper CFM has been establ...
Page 93 - or optional factory mounted disconnect switch.; Compressor Oil; The scroll compressor uses; Compressor Crankcase Heaters; Table 13. Pressure Control Switch Settings
SS-SVX09A-EN 93 System Start-Up 14. Turn the 115-volt control circuit switch 1S2 to the “OFF” position and open the field provided or optional factory mounted disconnect switch. 15. After shutting the system off, check the compressor oil appearance. Discoloration of the oil indicates that an abnorma...
Page 94 - Table 16. Compressor Sequence
94 SS-SVX09A-EN System Start-Up UnitSize With HGBP No HGBP With HGBP No HGBP 20-60 45° 40° 10° 0° Note: Minimum starting ambients in degrees F and is based on the unit operating at minimum step of unloading and 5 mph wind across condenser. Table 16. Compressor Sequence Unit Size Control Step Circuit...
Page 96 - Figure 47. 20 Ton Pressure Curve
96 SS-SVX09A-EN System Start-Up Figure 47. 20 Ton Pressure Curve
Page 97 - Figure 48. 25 Ton Pressure Curve
SS-SVX09A-EN 97 System Start-Up Figure 48. 25 Ton Pressure Curve
Page 98 - Figure 49. 30Ton Pressure Curve
98 SS-SVX09A-EN System Start-Up Figure 49. 30Ton Pressure Curve
Page 99 - Figure 50. 40 Ton Pressure Curve per Circuit
SS-SVX09A-EN 99 System Start-Up Figure 50. 40 Ton Pressure Curve per Circuit
Page 100 - Figure 51. 50 Ton Pressure Curve per Circuit
100 SS-SVX09A-EN System Start-Up Figure 51. 50 Ton Pressure Curve per Circuit
Page 101 - Figure 52. 60 Ton Pressure Curve per Circuit
SS-SVX09A-EN 101 System Start-Up Figure 52. 60 Ton Pressure Curve per Circuit
Page 102 - Final System Setup; Table 17. Recommended Operating Setpoints
102 SS-SVX09A-EN System Start-Up Final System Setup After completing the Pre-start and Start-up procedures outlined in the previous sections, perform these final checks before leaving the unit: [ ] Turn the 115 volt control circuit switch 1S2 “Off”. [ ] Program the Night Setback (NSB) panel (if appl...
Page 103 - Table 18. Sample Maintenance Log
SS-SVX09A-EN 103 System Start-Up Table 18. Sample Maintenance Log Date Current Ambient Temp. (F) Refrigerant Circuit #1 Refrigerant Circuit #2 Compr. Oil level Suct. Press. (Psig) Disch. Press. (Psig) Liquid Press. (Psig) Super- heat (F) Subcool (f) Compr. Oil level Suct. Press. (Psig) Disch. Press....
Page 104 - Service & Maintenance; Compressor Operational Sounds; At Low Ambient Start-Up; Scroll Compressor Replacement
104 SS-SVX09A-EN Service & Maintenance Compressor Operational Sounds Because of the scroll compressor design, it emits a higher frequency tone (sound) than a reciprocating compressor. It is designed to accommodate liquids, both oil and refrigerant, without causing compressor damage. The followin...
Page 105 - Table 19. Compressor Circuit Breaker Data
SS-SVX09A-EN 105 Service & Maintenance Table 19. Compressor Circuit Breaker Data Voltage Comp RLA LRA Must Must Tons Hold Trip 200 9 41.4 269.0 50.4 58.0 230 9 41.4 251.0 50.4 58.0 460 9 18.1 117.0 22.0 25.3 575 9 14.4 94.0 17.5 20.2 380/415 9 17.2 110.0 20.9 24.1 200 14 60.5 404.0 73.7 84.7 230...
Page 106 - Fuse Replacement Data; Air Handling Equipment; Over lubrication can be just as harmful as not enough grease.
106 SS-SVX09A-EN Service & Maintenance Fuse Replacement Data Table 20 lists the replacement fuses for the control circuit, compressors, and condenser fans. Monthly Maintenance Air Handling Equipment Before completing the following checks, turn the system control circuit switch 1S2 and 5S1 to the...
Page 108 - a. do not allow sprayer pressure to exceed 600 psi.; System operation
108 SS-SVX09A-EN Service & Maintenance WARNING Hazardous Pressures! Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution temperature under 150°F to avoid excessive pressure in the coil. Failure to follow these safety precautions could result in coil burs...
Page 109 - WARRANTY AND LIABILITY CLAUSE; Manager - Product Service
SS-SVX09A-EN 109 WARRANTY AND LIABILITY CLAUSE COMMERCIAL EQUIPMENT RATED 20 TONS AND LARGER AND RELATED ACCESSORIES PRODUCTS COVERED - This warranty* is extended by Trane Inc. and applies only to commercial equipment rated 20 Tons and larger and related accessories. The Company warrants for a perio...
Page 110 - Index
110 SS-SVX09A-EN Symbols “EVP” Chiller Units 29 ”No Controls” Units 29 Numerics 115 Volt Control Wiring (All Units) 29 A AC Conductors 51 Access Valves (Ports) 32 Air Handling Equipment 106 Air Vents 42 B balancing cock 42 Balancing Valves 42 Ball Shutoff Valves 32 C Chilled Water Controller 59 Chil...