Table of Contents:

  • Page 2 – CONNECTION; BACNET NETWORK; FIGURE 2: MAC ADDRESS EXAMPLES; SOFTWARE SETUP; MAC Address of 21; TABLE 1: BAUD RATE SELECTION SETTINGS
  • Page 3 – FLASH MEMORY MANAGEMENT; ADDITIONAL CAPABILITY; MODBUS COMMUNICATION ALARM; Simplicity
  • Page 4 – Johnson Controls Unitary Products; TABLE 2: POINTS LIST IN DESCRIPTION ORDER
  • Page 10 – TABLE 3: POINTS LIST IN OBJECT ORDER
  • Page 15 – Intelli-Comfort Gas Valve #1 Input Status
  • Page 16 – TROUBLESHOOTING
  • Page 17 – LINC GATEWAY LED LOCATION
Loading the manual

514067-UAD-A-0509

APPLICATION GUIDE

OVERVIEW

The

Simplicity

®

LINC Gateway operates as a Modbus® Client

providing an interface between a BACnet® MS/TP control system
and devices that communicate using the Modbus RTU protocol.
The

Simplicity

®

LINC allows monitoring and control by a third-party

BACnet Building Automation System (BAS).

The

Simplicity

®

LINC is preconfigured to provide an interface to UP

products equipped with

Simplicity

®

controllers manufactured after

4/2/2008 as well as prior

Simplicity

®

Elite™ and

Simplicity

®

with

Intelli-Comfort™ controllers.

The

Simplicity

®

LINC mounts inside the control panel of the UP

unit and utilizes 24 VAC power from the unit’s control transformer.
One port is connected to the UP controller. The other port must be
connected to the BACnet MS/TP network.

The

Simplicity

®

LINC Gateway is preconfigured to obtain

operational data points from the controller and expose them on a
BACnet MS/TP network.

NOTE:

Not all

Simplicity

®

operating parameters are controlled/

monitored by the

Simplicity

®

LINC.

FIGURE 1: WIRE CONNECTIONS

24 — must be grounded
close to the

Simplicity

LINC

®

T h e s h i e l d m u s t b e
c o n n e c t e d t o g ro u n d a t
e a c h d e v i c e .

R
C

24V power is polarity sensitive, incorrect
wiring could result in board damage.

Simplicity

®

LINC GATEWAY

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - CONNECTION; BACNET NETWORK; FIGURE 2: MAC ADDRESS EXAMPLES; SOFTWARE SETUP; MAC Address of 21; TABLE 1: BAUD RATE SELECTION SETTINGS

514067-UAD-A-0509 2 Johnson Controls Unitary Products CONNECTION The Simplicity ® LINC has 2 ports, one for connection to the BAS network (BACnet) and one to the Simplicity ® board (Modbus). BACNET NETWORK The only connection required in the field is to the BACnet (BAS) network. NOTE: Proper termina...

Page 3 - FLASH MEMORY MANAGEMENT; ADDITIONAL CAPABILITY; MODBUS COMMUNICATION ALARM; Simplicity

514067-UAD-A-0509 Johnson Controls Unitary Products 3 FLASH MEMORY MANAGEMENT The Flash Memory chip used in the Simplicity ® controllers has a 1,000,000 write cycle rating. To prevent premature failure of the flash memory, it should not be written to more often than once every 10 minutes, on average...

Page 4 - Johnson Controls Unitary Products; TABLE 2: POINTS LIST IN DESCRIPTION ORDER

514067-UAD-A-0509 4 Johnson Controls Unitary Products TABLE 2: POINTS LIST IN DESCRIPTION ORDER Read/ Write BACnet Object Type BACnet Object Inst Descriptor Default Min Max Point Description R (2) AV 14 ACC_OVER_TME – – – Accumulated Unoccupied Override Time (in hours) R (2) AV 15 ACTIVE_ALARM – – –...