Sanyo CHDX09663 - Manual

Sanyo CHDX09663

Sanyo CHDX09663 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
53 Page 53
54 Page 54
55 Page 55
56 Page 56
57 Page 57
58 Page 58
59 Page 59
60 Page 60
61 Page 61
62 Page 62
63 Page 63
64 Page 64
65 Page 65
66 Page 66
67 Page 67
68 Page 68
69 Page 69
70 Page 70
71 Page 71
72 Page 72
73 Page 73
74 Page 74
75 Page 75
76 Page 76
77 Page 77
78 Page 78
79 Page 79
80 Page 80
81 Page 81
82 Page 82
83 Page 83
84 Page 84
85 Page 85
86 Page 86
87 Page 87
88 Page 88
89 Page 89
90 Page 90
91 Page 91
92 Page 92
93 Page 93
94 Page 94
95 Page 95
96 Page 96
97 Page 97
98 Page 98
99 Page 99
100 Page 100
101 Page 101
102 Page 102
103 Page 103
104 Page 104
105 Page 105
106 Page 106
107 Page 107
108 Page 108
109 Page 109
110 Page 110
111 Page 111
112 Page 112
113 Page 113
114 Page 114
115 Page 115
116 Page 116
117 Page 117
118 Page 118
119 Page 119
120 Page 120
121 Page 121
122 Page 122
123 Page 123
124 Page 124
125 Page 125
126 Page 126
127 Page 127
128 Page 128
129 Page 129
130 Page 130
131 Page 131
132 Page 132
133 Page 133
134 Page 134
135 Page 135
136 Page 136
137 Page 137
138 Page 138
139 Page 139
140 Page 140
141 Page 141
142 Page 142
Page: / 142

Table of Contents:

  • Page 2 – Please Read Before Starting; accidental injury or death.; SPECIAL PRECAUTIONS; WARNING; Ground the unit; CAUTION
  • Page 3 – Check of Density Limit; ii
  • Page 4 – CONTENTS
  • Page 5 – iv
  • Page 6 – Control Functions; Contents; Controls
  • Page 7 – Required settings for Test Run
  • Page 8 – (1) Delayed start of outdoor units in the same system; The units do not start simultaneously; Simultaneous stop of multiple outdoor units; Selecting an Outdoor Unit for Operation
  • Page 9 – -1. Compressors Mounted in the Outdoor Units; Capacity; Examples of accumulated operating time: ODU=Outdoor Unit; Compressor Control
  • Page 10 – -4. Inverter Compressor Capacity Control; This control is performed every 15 seconds.
  • Page 12 – Discharge Temperature Protection
  • Page 14 – -2. System Refrigerant Oil Recovery Control
  • Page 15 – System employs
  • Page 19 – Meaning; Operation when oil level is not 2.
  • Page 20 – This valve is OFF when the outdoor unit is stopped.; Operation of Solenoid Valves
  • Page 22 – -1. Types of Electronic Thermostatic Expansion Valves; Outdoor Unit Electronic Thermostatic Expansion Valves
  • Page 23 – (2) Operation when discharge temperature is high
  • Page 24 – -4. Operation after Fixed Initial Fan Mode; high, and is decreased when the pressure sensor temperature is low.; (1) When all indoor units are operating in cooling mode; -6. When the Compressor Magnet Switch Seizing Alarm Occurs; Outdoor Fan Control
  • Page 26 – Indoor Unit Control of the Electronic Control Valve
  • Page 28 – Gas tube valve; Rap Valve Kit Control
  • Page 29 – This control is carried out regularly in cooling mode only.; Indoor Unit Refrigerant Oil Self Recovery Control
  • Page 30 – (1) Discharge temperature protection alarm; Discharge temperature protection list; (2) Discharge sensor trouble detection control; Discharge sensor failure list; Compressor 1; Discharge Temperature
  • Page 31 – An alarm occurs when overcurrent or lock current is detected.; Current Protection
  • Page 32 – High-pressure sensor failure; Pressure Sensor Failure
  • Page 33 – Backup Operation; (1) Alarms that result in automatic backup operation
  • Page 35 – This setting controls the operation of the drain pump.; Service Maintenance Functions
  • Page 37 – Setting
  • Page 38 – Automatic cancel; • Symptoms of insufficient gas; (3) Outdoor unit PCB LED indications in judgment mode
  • Page 39 – – MEMO –
  • Page 40 – Outdoor Unit Repair Procedures; OUTDOOR UNIT REPAIR PROCEDURES; Panels
  • Page 42 – Removing Electrical Component Box and Duct; (1) Remove the electrical component box cover
  • Page 44 – Discharging Compressor Oil; The low-pressure outlet port is at the Lo side of the right side.; Acceptance/rejection criteria for the oil
  • Page 45 – Switch on outdoor unit control PCB
  • Page 47 – Backup operation settings for each compressor; INV compressor
  • Page 48 – Recovering Refrigerant; The following equipment and tools are required:; the jumper wire. Then restore electrical power to the outdoor unit.
  • Page 50 – If it is in heating, follow the step and later procedures.; NOTE
  • Page 51 – Repeat steps and and complete pump down for all outdoor units.; N O T E
  • Page 52 – -3. Recovery of Refrigerant from Entire System; to the outdoor units.
  • Page 53 – Checking for Leakage After Repair; -1. Pressure Check for Leakage of Outdoor Unit; are any leaks, bubbles will show on the tubing surface.
  • Page 55 – Charging Compressor Oil; -1. If Refrigerant Has Already Been Charged to Outdoor Unit; The oil charging procedures are given below.
  • Page 56 – (3) Charging compressor oil into outdoor unit
  • Page 57 – -2. If Outdoor Unit Has Not Been Charged with Refrigerant; into the oil container.
  • Page 58 – Remaining oil in the removed compressor: 0.58 gal; Model name
  • Page 59 – Pumping Out Refrigerant from Outdoor Unit; Required equipment and tools:
  • Page 60 – the outdoor unit power.
  • Page 61 – Faulty outdoor unit
  • Page 62 – 0-1. Compressor Trouble Diagnosis and Check Methods; Reference: Symptoms of motor burning
  • Page 63 – pressor Oil,” and charge with oil if necessary.
  • Page 64 – At this time, be careful that air does not enter the tubing.
  • Page 65 – door units. Measure the amount of drained oil.; Remove the manifold gauge.
  • Page 66 – (A) If a ball valve is installed on the outdoor unit; * Color sample sheet for degree of stain
  • Page 67 – (B) If a ball valve is not installed on the outdoor unit; Cleaning dry core; on the previous page.
  • Page 68 – Removal; 0-3. Removing and Installing Compressors; * For all types 90 and 140, follow the replacement procedure below.
  • Page 69 – Installation; Install the crankcase heater onto the new compressor.; Shape the tubes and insert them at the 2 brazing locations.
  • Page 70 – (7) Disconnect the 3 brazed locations shown in the figure 25.; (Compressor 2 on remote controller alarm display); Remove the crankcase heater.
  • Page 71 – Set up the leg of the new compressor onto the 2 cushion rubbers.; Remove the 2 brazed tube caps (2 pieces) from the compressor.
  • Page 72 – Perform copper brazing at the 3 brazing locations.
  • Page 74 – High and Low Pressure Sensors; 1-1. Removing the High and Low Pressure Sensor; the outdoor unit employs a Schrader-type valve.; 1-2. Installing the High and Low Pressure Sensors
  • Page 75 – Protect the check valves as shown in the figure 30.; the Installation Instruc-; that came with the outdoor unit and the refrigerant recovery unit.
  • Page 76 – Protect the check valves as shown in the figure 31.
  • Page 78 – Outdoor Unit Maintenance Remote Controller; OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER; Operations
  • Page 79 – About the outdoor unit maintenance remote controller; to the outdoor unit PCB.; System diagram
  • Page 80 – Functions on the ordinary display
  • Page 81 – Ordinary Display Controls and Functions; The connection is shown in the figure below.
  • Page 82 – LED
  • Page 83 – Use the temperature setting; Item code
  • Page 85 – Display of unit Nos. 1 − 20
  • Page 86 – Monitoring Operations
  • Page 88 – Outdoor Unit Alarm History Monitor
  • Page 89 – Setting mode 1
  • Page 90 – Setting mode 2
  • Page 92 – Remote Controller Functions; REMOTE CONTROLLER FUNCTIONS
  • Page 93 – Simple Settings Function
  • Page 94 – List of Simple Setting Items
  • Page 95 – Detailed Settings Function
  • Page 96 – List of Detailed Setting Items
  • Page 100 – Simple setting items; Filter sign ON times for each model
  • Page 101 – Enabled only in 2WAY MULTI heat-pump models.; Set mode at priority remote controller; Cooling or dry
  • Page 106 – Remote Controller Servicing Functions; List of Servicing Functions; Functions
  • Page 107 – Test Run Function
  • Page 108 – Sensor Temperature Display Function
  • Page 110 – Trouble Diagnosis; TROUBLE DIAGNOSIS; Pin
  • Page 111 – Contents of Remote Controller Switch Alarm Display
  • Page 113 – Outdoor Unit Control Panel LED Display; Display meaning
  • Page 114 – Sensor temperature display function (displayed
  • Page 115 – Sensor Temperature Relationship Table
  • Page 116 – With type 72, the INV compressor is compressor 1.; Alarm code
  • Page 136 – Blinking Inspection Display on the Remote Controller
  • Page 137 – Inspection of Parts; or
  • Page 138 – Output
  • Page 139 – Thermister Characteristics Curve; Temperature sensor
  • Page 140 – Heat exchanger temperature, Heat exchanger temperature sensor
Loading the manual

2-WAY ECO-i

MULTI SYSTEM

Outdoor Units

Refrigerant R410A is used in the outdoor units.
* Salt-Air Damage Resistant Specifications.

**

96

72

Class

C

ECO-i W-2WAY

CHDX07263

CHDX09663

CHDXR07263

CHDXR09663

*

*

CHDX07263

CHDX09663

CHDXR07263

CHDXR09663

*

*

85464849280000

SM830180-00

Indoor Units

9

Class

UM

XM

Mini Semi-Concealed

U

X

XHX3652

A

T

D

F

FM

K

7

SERVICE MANUAL

12

15

18

24

19

36

48

54

4-Way Air Discharge
Semi-Concealed
4-Way Air Discharge

1-Way Air Discharge
Semi-Concealed

Concealed Duct Type

Slim Concealed
Duct Type
Concealed-Duct High
Static Pressure

Ceiling-Mounted

Wall-Mounted Type

Floor-Standing Type

Concealed-Floor
Standing Type

UMHX0762

UHX0762

AHX0752

UHX0962

AHX0952

UMHX0962

KHX0752

KHX0952

FHX0762

FHX0962

FMHX0962

FMHX0762

KHX1252

UMHX1262

UHX1262

XHX1252

XMHX1252

AHX1252

UHX1562

UMHX1562

THX1252

UMHX1862

UHX1862

XHX1852

KHX1962

KHX1862

THX1852

FHX1862

FMHX1862

FHX1562

FMHX1562

FMHX1262

FHX1262

XHX2452

XMHX1852

UHX2462

UHX3662

UHX4862

UHX5462

DHX4852

DHX3652

THX2452

KHX2452

FHX2462

FMHX2462

**

Necessary to install the External Electronic Expansion Valve Kit (Optional:ATK-SVRK56BA).

REFERENCE NO.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Please Read Before Starting; accidental injury or death.; SPECIAL PRECAUTIONS; WARNING; Ground the unit; CAUTION

Please Read Before Starting This air conditioning system meets strict safety and operat-ing standards. As the installer or service person, it is animportant part of your job to install or service the system so it operates safely and efficiently. Carefully read this instruction booklet before beginni...

Page 3 - Check of Density Limit; ii

Check of Density Limit The room in which the air conditioner is to beinstalled requires a design that in the event of refrig-erant gas leaking out, its density will not exceed a setlimit. The refrigerant (R410A), which is used in the aircondition-er, is safe, without the toxicity or combustibility o...

Page 4 - CONTENTS

— CONTENTS — Section 1: CONTROL FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 -2 2. Selecting Outdoor Unit f...

Other Sanyo Models