Sanyo C4232A - Manual
Sanyo C4232A – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
SUBMITTAL SHEET
SYSTEM
INDOOR/OUTDOOR
42TS3
2A
TS4232/C4232
A
CEILING SUSPENDED AIR CONDITIONER
GENERAL DATA
(AT 230V)
POWER V/PH/HZ
230/208/1/60
Circuit Ampacity, Min. (A)
30
Fuse size, Max.
(A)
50
COMPRESSOR
Scroll-Hermetic
No. used
1
R.L. Amps - L.R. Amps (A)
18.1 ñ 131
Crankcase Heater
-
OUTDOOR FAN - TYPE
Propeller
Dia. (in.) - No. used
18-3/32 - 2
Type Drive - No. speeds
Direct ñ 3 (AUTO)
No. Poles - RPM (High)
6 - 879
No. Motors - Watts
2 - 110
CFM (High)
3,450
F.L. Amps. (A)
1.8
OUTDOOR COIL - TYPE
Aluminum Fin & Copper Pipe
Fin Type - Pipe Type
Slit Plate - Inner Riffled
Rows - F.P.I.
2 - 12.7
Face Area (sq.ft.)
11.63
Tube Size (in.)
3/8
INDOOR FAN - TYPE
Centrifugal
Dia. (in.) - No. used
5-29/32-4
No. speeds
3 & Auto
No. Poles -RPM (High)
4 - 1,015
No. Motors - Watts
1 - 100
CFM (HI/MED/LOW)
900/790/680
F.L. Amps (A)
0.7
INDOOR COIL - TYPE
Aluminum Fin & Copper Pipe
Fin Type - Pipe type
Slit Plate - Inner Riffled
Rows - F.P.I.
3 - 14.9
Face Area (sq. ft.)
3.51
Tube Size (in.)
5/16
Drain Connection Size (in.)
3/4
REFRIGERANT
R22
Lbs. - R22 (O.D. Unit)
9.7
Control
Capillary Tube
Connection
Flare
Line Length, Max (ft.)
165
Lift difference, Max (ft.)
100
Line Size - in. O.D. Discharge
3/8
Line Size - in. O.D. Suction
3/4
DIMENSIONS (in.)
H
x
W x
D
Indoor Unit
-Uncrated
9-7/16 x 62
x 26-3/8
-Crated
12-15/32 x 66-1/16x 31-1/16
Outdoor Unit -Uncrated
48-5/8 x 37
x 13-3/8
-Crated
52ñ7/32 x 40
x 16-3/8
WEIGHT
INDOOR OUTDOOR
Net
(lbs.)
84
205
Shipping (lbs.)
97
229
Shipping Volume (cu.ft.)
13.6
19.8
SS42TS32
A
-
2
PERFORMANCE DATA @ A
RI STANDARD CONDITIONS
(230/208V)
COOLING
Total Capacity
(BTU/H)
42,000/40,500
Sensible Capacity (BTU/H)
22,500/21,530
Latent Capacity
(BTU/H)
19,500/18,970
SEER
10.2/10.3
Dehumidification
(Pints/H)
14.8/14.6
Amps
(A)
20.6/21.0
Power Inputs
(W)
4,190/4,100
Outdoor Sound Rating (bels)
7.9
FEATURE
Controls
Microprocessor
Remote Controller
LCD Wireless type
Temperature Control
IC Thermostat
Timer
ON/OFF, 24 hours
Night-Setback
Built-In
Air Louver
(Horizontal)
Manual
(Vertical)
Automatic
Power Failure Automatic Restart
Built-In
Self Diagnosis
N/A
OPTION
Refrigerant Line Set
AP3210BH (30 ft)
AP3215BH (50 ft)
Low Ambient Control
Built-In
Fresh Air Intake
Built-In
Airduct Extension
N/A
Condensate Drain Pump
N/A
Non-Removable Remo-con Bracket
RCS5PS4B
Wired Remote Control
RCS-102WD/RCS-302WD
OPERATING RANGE
Cooling
Indoor Air
Outdoor Air
Intake Temp.
Intake Temp.
Maximum
95 F DB/71 F WB
115 F DB
Minimum
67 F DB/57 F WB
67 F DB
CERTIFICATION
42TS
32
A
AIRCONDITIONING PRODUCTS
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.