SUBMITTAL SHEET

SYSTEM

INDOOR/OUTDOOR

42XS32A

XS4232/C4232A

CEILING RECESSED (4-WAY) AIR CONDITIONER

GENERAL DATA

(AT 230V)

POWER V/PH/HZ

230/208/1/60

Circuit Ampacity, Min. (A)

30

Fuse size, Max.

(A)

50

COMPRESSOR

Scroll-Hermetic

No. used

1

R.L. Amps - L.R. Amps (A)

18.1 -131

Crankcase Heater

-

OUTDOOR FAN - TYPE

Propeller

Dia. (in.) - No. used

18-3/32 - 2

Type Drive - No. speeds

Direct – 2 (AUTO)

No. Poles - RPM (High)

6 - 879

No. Motors - Watts

2 - 110

CFM (High)

3,450

F.L. Amps. (A)

1.8

OUTDOOR COIL - TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

Slit Plate - Inner Riffled

Rows - F.P.I.

2 - 12.7

Face Area (sq.ft.)

11.63

Tube Size (in.)

3/8

INDOOR FAN - TYPE

Turbo

Dia. & Length (in.) - No. used

19-9/32 -1

No. speeds

3 & Auto

No. Poles -RPM (High)

6 - 560

No. Motors - Watts

1- 60

CFM (HI/MED/LOW)

980/830/650

F.L. Amps (A)

0.9

INDOOR COIL - TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe type

Slit Plate - riffled

Rows - F.P.I.

2 - 14.9

Face Area (sq. ft.)

5.17

Tube Size (in.)

5/16

Drain Connection Size (in.)

3/4

REFRIGERANT

R22

Lbs. - R22 (O.D. Unit)

9.7

Control

Capillary Tube

Connection

Flare

Line Length, Max (ft.)

165

Lift difference, Max (ft.)

100

Line Size - in. O.D. Discharge

3/8

Line Size - in. O.D. Suction

3/4

DIMENSIONS (in.)

H

x

W

x

D

Indoor Unit -Uncrated 14-3/32 x 45-9/32 x 33-27/32

-Crated

12-7/16 x 43- 27/32 x 32-25/32(Indoor unit)

4-3/32 x 49-1/2

x 39-11/32(Indoor Grille)

Outdoor unit -Uncrated 48-5/8 x 37

x 13-3/8

-Crated

52 -7/32 x 40

x 16-3/8

WEIGHT

INDOOR

OUTDOOR

Net

(lbs.)

75

198

Shipping (lbs.)

71/29(Grille)

223

Shipping Volume (cu.ft.)

10.4/4.6(Grille)

19.8

SS42XS32A-2

PERFORMANCE DATA @ ARI STANDARD CONDITIONS

(230/208V)

COOLING

Total Capacity

(BTU/H)

42,000/40,500

Sensible Capacity(BTU/H)

22,360/21,470

Latent Capacity

(BTU/H)

19,640/19,030

SEER

10.2/10.3

Dehumidification (Pints/H)

14.6/14.8

Amps (A)

20.8/21.1

Power Inputs (W)

4,230/4,120

Outdoor Sound Rating (bels)

7.9

FEATURE

Controls

Microprocessor

Remote Controller

LCD Wireless type

Temperature Control

IC Thermostat

Timer

ON/OFF, 24 hours

Night Setback

Built-In

Air Louver (Horizontal)

-

(Vertical)

Automatic

Power Failure Automatic Restart

Built-In

Self Diagnosis

N/A

OPTION

Refrigerant Line Set

AP3210BH (30 ft)

AP3215BH (50 ft)

Low Ambient Control

N/A

Fresh Air Intake

CMB-GS140T-

Airduct Extension

Available

Condensate Drain Pump

Built-In

Non-Removable Remo-con Bracket

RCS5PS4B

Wired Remote Control

RCS-102WD/RCS-302WD

OPERATING RANGE

Cooling

Indoor Air

Outdoor Air

Intake Temp.

Intake Temp.

Maximum

95 F DB/71 F WB

115 F DB

Minimum

67 F DB/57 F WB

67 F DB

CERTIFICATION

42XS32A

AIRCONDITIONING PRODUCTS