SUBMITTAL SHEET

SYSTEM

INDOOR/OUTDOOR

36TS3

2A

TS3632/C363

2A

CEILING SUSPENDED AIR CONDITIONER

GENERAL DATA

(AT 230V)

POWER V/PH/HZ

230/208/1/60

Circuit Ampacity, Min. (A)

35

Fuse size, Max.

(A)

35

COMPRESSOR

Rotary-Hermetic

No. used

1

R.L. Amps - L.R. Amps (A)

12.5 ñ 95.0

Crankcase Heater

30W

OUTDOOR FAN - TYPE

Propeller

Dia. (in.) - No. used

18-3/32 - 2

Type Drive - No. speeds

Direct ñ 3 (AUTO)

No. Poles - RPM (High)

6 - 879

No. Motors ñ HP

2 - 110

CFM (High)

3,670

F.L. Amps.

(A)

1.8

OUTDOOR COIL - TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

Slit Plate - Inner Riffled

Rows - F.P.I.

2 - 12.7

Face Area (sq.ft.)

11.63

Tube Size (in.)

3/8

INDOOR FAN - TYPE

Cross - Flow

Dia. (in.) - No. used

5-29/32 & 39-4

No. speeds

3 & Auto

No. Poles -RPM (High)

4 - 1,015

No. Motors ñ HP

1 - 100

CFM (HI/MED/LOW)

900/790/680

F.L. Amps (A)

0.7

INDOOR COIL ñ TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe type

Slit Plate - Inner Riffled

Rows - F.P.I.

2 - 12.7

Face Area (sq. ft.)

3.51

Tube Size (in.)

5/16

Drain Connection Size (in.)

1-1/4

REFRIGERANT

R22

Lbs. - R22 (O.D. Unit)

9.48

Control

Capillary Tube

Connection

Flare

Line Length, Max (ft.)

165

Lift difference, Max (ft.)

100

Line Size - in. O.D. Discharge

3/8

Line Size - in. O.D. Suction

3/4

DIMENSIONS (in.)

H

x

W

x

D

Indoor Unit

-Uncrated 9-7/16

x 62

x 26-3/8

-Crated

12

x 65-20/32 x 29-3/4

Outdoor Unit -Uncrated 48-5/8

x 37

x 13-3/8

-Crated

52ñ7/32 x 40

x 16-12/32

WEIGHT

INDOOR

OUTDOOR

Net

(lbs.)

84.0

198.0

Shipping (lbs.)

97.0

223.0

Shipping Volume (cu.ft.)13.6

19.8

SS36TS32

A

-

2

PERFORMANCE DATA @ ARI STANDARD CONDITIONS

(230/208V)

COOLING
Total Capacity

(BTU/H)

34,800/33,000

Sensible Capacity

(BTU/H)

22,320/21,700

Latent Capacity

(BTU/H)

11,680/11,300

SEER

10.6/10.9

Dehumidification

(Pints/H)

10.6/10.8

Amps

(A)

15.0/15.5

Power Inputs

(W)

3,340/3,130

Outdoor Sound Rating (bels)

7.9

FEATURE

Controls

Microprocessor

Remote Controller

LCD Wireless type

Temperature Control

IC Thermostat

Timer

ON/OFF, 24 hours

Night-Setback

Built-In

Air Louver (Horizontal)

Manual

(Vertical)

Automatic

Power Failure Automatic Restart

Built-In

Self Diagnosis

N/A

OPTION

Refrigerant Line Set

AP3210BH (30 ft)
AP3215BH (50 ft)

Low Ambient Control

Available

Fresh Air Intake

Available

Central Remote ON-OFF Control

Available

Airduct Extension

N/A

Indoor Frame Extension

N/A

Condensate Drain Pump

Available

Non-Removable Remo-con Bracket

Available

OPERATING RANGE

Cooling

Indoor Air

Outdoor Air

Intake Temp.

Intake Temp.

Maximum

95 F DB/71 F WB

115 F DB

Minimum

67 F DB/57 F WB

67 F DB

CERTIFICATION