SUBMITTAL SHEET

SYSTEM

INDOOR/OUTDOOR

24XS32

24XS32

24XS32

24XS32A

XS2432/C

XS2432/C

XS2432/C

XS2432/C24

24

24

2432

32

32A

32

CEILING RECESSED (4-WAY) AIR CONDITIONER

GENERAL DATA

(AT 230V)

POWER V/PH/HZ

230/208/1/60

Circuit Ampacity, Min. (A)

30

Fuse size, Max. (A)

30

COMPRESSOR

Rotary-Hermetic

No. used

1

R.L. Amps - L.R. Amps (A)

10.1-66.0

Crankcase Heater -

OUTDOOR FAN - TYPE

Propeller

Dia. (in.) - No. used

18-3/32 - 1

Type Drive - No. speeds

Direct – 3 (AUTO)

No. Poles - RPM (High)

6 - 879

No. Motors - HP

1 - 1/7

CFM (High)

1,900

F.L. Amps. (A)

1.2

OUTDOOR COIL - TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

Slit Plate - Inner Riffled

Rows - F.P.I.

2 - 14.1

Face Area (sq.ft.)

6.63

Tube Size (in.)

3/8

INDOOR FAN - TYPE

Turbo

Dia. & Length (in.) - No. used 19-9/32 -1
No. speeds

3 & Auto

No. Poles -RPM (High)

6-451

No. Motors - HP

1 - 1/25

CFM (HI/MED/LOW)

540/460/360

F.L. Amps (A)

0.6

INDOOR COIL - TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe type

CorrugatedPlate - Inner Riffled

Rows - F.P.I.

2 - 14.9

Face Area (sq. ft.)

3.18

Tube Size (in.)

3/8

Drain Connection Size (in.)

1-1/4

REFRIGERANT

R22

Lbs. - R22 (O.D. Unit)

5.5

Control

Capillary Tube

Connection

Flare

Line Length, Max (ft.)

132

Lift difference, Max (ft.)

82

Line Size - in. O.D. Discharge

1/4

Line Size - in. O.D. Suction

3/4

DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 12-29/32 x 33-27/32 x 33-27/32

-Crated 11-6/32 x 32-14/32 x 32-25/32 (Indoor unit)
4-3/32 x 38-2/32 x 39-11/32 (Indoor Grille)

Outdoor Unit –Uncrate 28-15/16 x 37 x 13-3/8

-Crated 32-17/32 x 40 x 16-12/32

WEIGHT

INDOOR OUTDOOR

Net

(lbs.)

60.0

152.0

Shipping (lbs.)

57.0/18.0(Grille) 168.0

Shipping Volume (cu.ft.) 6.9/ 3.5 (Grille) 12.3


SS24XS32- 2

PERFORMANCE DATA @ ARI STANDARD CONDITIONS

(230/208V)

COOLING
Total Capacity

(BTU/H)

24,000/23,400

Sensible Capacity

(BTU/H)

13,740/13,300

Latent Capacity

(BTU/H)

10,360/10,100

SEER

10.0/10.2

Dehumidification

(Pints/H)

7.1/6.9

Amps

(A)

11.6/12.2

Power Inputs

(W)

2,440/2,380

Outdoor Sound Rating(bels)

7.6

FEATURE

Controls

Microprocessor

Remote Controller

LCD Wireless type

Temperature Control

IC Thermostat

Timer

ON/OFF, 24 hours

Night Setback

Built-In

Air Louver

(Horizontal)

-

(Vertical)

Automatic

Power Failure Automatic Restart

Built-In

Self Diagnosis

N/A

OPTION

Refrigerant Line Set

AP2710BH (30 ft)
AP2715BH (50 ft)

Low Ambient Control

Available

Fresh Air Intake

CMB-GSJ80T

Central Remote ON-OFF Control

Available

Airduct Extension

Available

Indoor Frame Extension

N/A

Condensate Drain Pump

Available

Non-Removable Remo-con Bracket

RCS5PS4B

Wired Remote Controller

RCS-102WD/RCS-302WD

OPERATING RANGE

Cooling

Indoor Air

Outdoor Air

Intake Temp.

Intake Temp.

Maximum 95F DB/71F WB 115F DB
Minimum 67F DB/57F WB 67F DB

CERTIFICATION

24XS3 2 A

AIRCONDITIONING PRODUCTS

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.