Sanyo 24THS32 - Manual

Sanyo 24THS32

Sanyo 24THS32 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

SUBMITTAL SHEET

SYSTEM

INDOOR/OUTDOOR

24THS32

THS2432/CH2432

CEILING SUSPENDED HEAT PUMP

GENERAL DATA

(AT 230V)

POWER V/PH/HZ

230/208/1/60

Circuit Ampacity, Min. (A)

30

Fuse size, Max

(A)

30

COMPRESSOR

Rotary-Hermetic

No. used

1

R.L. Amps - L.R. Amps (A)

9.4 - 66.0

Crankcase Heater

30W

OUTDOOR FAN - TYPE

Propeller

Dia. (in.) - No. used

18-3/32- 1

Type Drive - No. speeds

Direct ñ 2 (AUTO)

No. Poles - RPM (High)

6 - 879

No. Motors ñ HP

1 - 1/7

CFM (High)

1,840

F.L. Amps. (A)

0.9

OUTDOOR COIL ñ TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

Slit Plate - Inner Riffled

Rows - F.P.I.

2- 14.1

Face Area (sq.ft.)

6.78

Tube Size (in.)

3/8

INDOOR FAN ñ TYPE

Centrifugal

Dia. & Length (in.) - No. used

5-1/8 & 4

No. speeds

3 & Auto

No. Poles -RPM (High)

4-1,187

No. Motors - HP

1 - 1/24

CFM (HI/MED/LOW)

540/490/425

F.L. Amps (A)

0.4

INDOOR COIL - TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe type

Slit Plate - Inner Riffled

Rows - F.P.I.

3 - 14.9

Face Area (sq. ft.)

1.81

Tube Size (in.)

3/8

Drain Connection Size (in.)

1-1/4

REFRIGERANT

R22

Lbs. - R22 (O.D. Unit)

6.17

Control

Capillary Tube

Connection

Electronic Refrigerant Control Valve

Line Length, Max (ft.)

165

Lift difference, Max (ft.)

100

Line Size - in. O.D. Discharge

1/4

Line Size - in. O.D. Suction

3/4

DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 7- 15/32 x 51- 6/32 x 26-3/8

-Crated

9- 14/32 x 54- 19/32 x 29-31/32

Outdoor Unit-Uncrated 28-15/16 x 37

x 13-3/8

-Crated

32-17/32 x 40

x 16-12/32

WEIGHT

INDOOR

OUTDOOR

Net

(lbs.)

60.0

157.0

Shipping(lbs.)

77.0

170.0

Shipping Volume (cu.ft.) 8.9

12.3


SS24THS32-1

PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)

COOLING
Total Capacity

(BTU/H)

22,400/21,600

Sensible Capacity (BTU/H)

13,640/12,970

Latent Capacity

(BTU/H)

8,760/8,630

SEER

10.0/10.0

Dehumidification (Pints/H)

6.3/6.2

Amps (A)

10.7/11.3

Power Inputs (W)

2,290/2,250

HEATING
Total Capacity

(BTU/H)

25,400/25,000

HSPF

7.0/7.0

Amps (A)

11.7/12.9

Power Inputs (W)

2,350/2,280

Back-up Strip Heater (KW)

1.80/1.47

Outdoor Sound Rating(bels)

7.6

FEATURE

Controls

Microprocessor

Remote Controller

LCD Wireless type

Temperature Control

IC Thermostat

Timer

ON/OFF, 24 hours

Night Setback

Built-In

Air Louver (Horizontal)

Manual

(Vertical)

Automatic

Power Failure Automatic Restart

Built-In

Self Diagnosis

N/A

OPTION

Refrigerant Line Set

AP2710BH (30 ft)
AP2715BH (50 ft)

Low Ambient Control

Built-In

Fresh Air Intake

N/A

Central Remote ON-OFF Control

Available

Airduct Extension

N/A

Indoor Frame Extension

N/A

Condensate Drain Pump

Available

Non-Removable Remo-con Bracket

RCS5PS4B

OPERATING RANGE

Cooling

Indoor Air

Outdoor Air

Intake Temp.

Intake Temp.

Maximum

95F DB/71F WB

115F DB

Minimum

67F DB/57F WB

23F DB

Heating Maximum 80F DB/67F WB 75F DB/67F WB

Minimum -F DB/ - F WB 17F DB/15F WB