GENERAL DATA
(AT 230V)
POWER V/PH/HZ
230/208/1/60
Circuit Ampacity, Min. (A)
30
Fuse size, Max
(A)
30
COMPRESSOR
Rotary-Hermetic
No. used
1
R.L. Amps - L.R. Amps (A)
9.4 - 66.0
Crankcase Heater
30W
OUTDOOR FAN - TYPE
Propeller
Dia. (in.) - No. used
18-3/32- 1
Type Drive - No. speeds
Direct ñ 2 (AUTO)
No. Poles - RPM (High)
6 - 879
No. Motors ñ HP
1 - 1/7
CFM (High)
1,840
F.L. Amps. (A)
0.9
OUTDOOR COIL ñ TYPE
Aluminum Fin & Copper Pipe
Fin Type - Pipe Type
Slit Plate - Inner Riffled
Rows - F.P.I.
2- 14.1
Face Area (sq.ft.)
6.78
Tube Size (in.)
3/8
INDOOR FAN ñ TYPE
Centrifugal
Dia. & Length (in.) - No. used
5-1/8 & 4
No. speeds
3 & Auto
No. Poles -RPM (High)
4-1,187
No. Motors - HP
1 - 1/24
CFM (HI/MED/LOW)
540/490/425
F.L. Amps (A)
0.4
INDOOR COIL - TYPE
Aluminum Fin & Copper Pipe
Fin Type - Pipe type
Slit Plate - Inner Riffled
Rows - F.P.I.
3 - 14.9
Face Area (sq. ft.)
1.81
Tube Size (in.)
3/8
Drain Connection Size (in.)
1-1/4
REFRIGERANT
R22
Lbs. - R22 (O.D. Unit)
6.17
Control
Capillary Tube
Connection
Electronic Refrigerant Control Valve
Line Length, Max (ft.)
165
Lift difference, Max (ft.)
100
Line Size - in. O.D. Discharge
1/4
Line Size - in. O.D. Suction
3/4
DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 7- 15/32 x 51- 6/32 x 26-3/8
-Crated
9- 14/32 x 54- 19/32 x 29-31/32
Outdoor Unit-Uncrated 28-15/16 x 37
x 13-3/8
-Crated
32-17/32 x 40
x 16-12/32
WEIGHT
INDOOR
OUTDOOR
Net
(lbs.)
60.0
157.0
Shipping(lbs.)
77.0
170.0
Shipping Volume (cu.ft.) 8.9
12.3
SS24THS32-1
PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)
COOLING
Total Capacity
(BTU/H)
22,400/21,600
Sensible Capacity (BTU/H)
13,640/12,970
Latent Capacity
(BTU/H)
8,760/8,630
SEER
10.0/10.0
Dehumidification (Pints/H)
6.3/6.2
Amps (A)
10.7/11.3
Power Inputs (W)
2,290/2,250
HEATING
Total Capacity
(BTU/H)
25,400/25,000
HSPF
7.0/7.0
Amps (A)
11.7/12.9
Power Inputs (W)
2,350/2,280
Back-up Strip Heater (KW)
1.80/1.47
Outdoor Sound Rating(bels)
7.6
FEATURE
Controls
Microprocessor
Remote Controller
LCD Wireless type
Temperature Control
IC Thermostat
Timer
ON/OFF, 24 hours
Night Setback
Built-In
Air Louver (Horizontal)
Manual
(Vertical)
Automatic
Power Failure Automatic Restart
Built-In
Self Diagnosis
N/A
OPTION
Refrigerant Line Set
AP2710BH (30 ft)
AP2715BH (50 ft)
Low Ambient Control
Built-In
Fresh Air Intake
N/A
Central Remote ON-OFF Control
Available
Airduct Extension
N/A
Indoor Frame Extension
N/A
Condensate Drain Pump
Available
Non-Removable Remo-con Bracket
RCS5PS4B
OPERATING RANGE
Cooling
Indoor Air
Outdoor Air
Intake Temp.
Intake Temp.
Maximum
95F DB/71F WB
115F DB
Minimum
67F DB/57F WB
23F DB
Heating Maximum 80F DB/67F WB 75F DB/67F WB
Minimum -F DB/ - F WB 17F DB/15F WB