SUBMITTAL SHEET
SYSTEM
INDOOR/OUTDOOR
24KS62R
KS2462R/C2462R
WALL MOUNTED AIR CONDITIONER
GENERAL DATA (AT 230V)
POWER V/PH/HZ 230/208/1/60
Circuit Ampacity, Min. (A) 35
Fuse size, Max. (A) 35
COMPRESSOR Scroll
No. used 1
R.L. Amps - L.R. Amps (A) 12.5 - 61.0
Crankcase Heater 30W
OUTDOOR FAN TYPE Propeller
Dia. (in.) - No. used 18-3/32 - 1
Type Drive - No. speeds Direct – 2 (AUTO)
No. Poles - RPM (High) 6 - 879
No. Motors – W 1 - 110
CFM (High) 1660
F.L. Amps. (A) 0.9
OUTDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Riffled
Rows - F.P.I. 2 – 14.1
Face Area (sq.ft.) 8.72
Tube Size (in.) 3/8
INDOOR FAN - TYPE Cross-flow
Dia. & Length (in.) - No. used 4 & 33-3/8 -1
No. speeds 3 & Auto
No. Poles -RPM (High) 4 – 1,324
No. Motors - W 1 - 30
CFM (HI/MED/LOW) 559/---/---
F.L. Amps (A) 0.38
INDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe type Slit Plate - Inner Riffled
Rows - F.P.I. 2 – 19.5
Face Area (sq. ft.) 2.30
Tube Size (mm ) 7
Drain Connection Size (in.) 23/32
REFRIGERANT R410A
Lbs. - R22 (O.D. Unit) 6.6
Control Capillary Tube
Connection Flare
Line Length, Max (ft.) 132
Lift difference, Max (ft.) 50
Line Size - in. O.D. Discharge 3/8 (Insulated tube)
Line Size - in. O.D. Suction 3/4 (Insulated tube)
DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 13 x 44-7/8 x 8-31/32
-Crated 12-25/32 x 48-15/32 x 15-31/32
Outdoor Unit -Uncrated 36-5/8 x 37 x 13-3/8
-Crated 39-3/4 x 39-3/8 x 15-3/4
WEIGHT
INDOOR OUTDOOR
Net (lbs.) 40.0 150.0
Shipping (lbs.) 44.0 190.0
Shipping Volume(cu.ft.) 5.7 14.1
SS24KS62R-
2
PERFORMANCE DATA @ ARI STANDARD CONDITIONS
(230/208V)
COOLING
Total Capacity (BTU/H) 27,000 / 26,000
Sensible Capacity (BTU/H) 15,980 / 15,350
Latent Capacity (BTU/H) 11,020 / 10,650
SEER 13.0 / 13.0
Dehumidification (Pints/H) 6.5 / 6.4
Amps (A) 10.2 / 10.9
Power Inputs (W) 2,240 / 2,200
Outdoor Sound Rating (bels) 7.6
FEATURE
Controls Microprocessor
Remote Controller LCD Wireless type
Temperature Control IC Thermostat
Timer Progrum 24h, 1-hour off
Night Setback Built-in
Air Louver (Horizontal) Manual
(Vertical) Automatic
Power Failure Automatic Restart Built-In
Self Diagnosis N/A
OPTION
Refrigerant Line Set AP3210BH (30 ft)
AP3215BH (50 ft)
Low Ambient Control N/A
Fresh Air Intake N/A
Central Remote ON-OFF Control N/A
Airduct Extension N/A
Indoor Frame Extension N/A
Condensate Drain Pump N/A
Non-Removable Remo-con Bracket N/A
Wired remote RCS-KS2432AWD
OPERATING RANGE
Cooling Indoor Air Outdoor Air
Intake Temp. Intake Temp.
Maximum 95F DB / 71F WB 115F DB
Minimum 67F DB / 57F WB 23F DB (0F DB)
CERTIFICATION
24KS62R
AIRCONDITIONING PRODUCTS
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.