Samsung MXJ-2D2509K - Installation Manual
Samsung MXJ-2D2509K Air Conditioner – Installation Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Installation manual
Please read ‘Safety Precautions’ described in the installation manual of the air conditioner.
• Check and make sure that all parts are included in the package.
• For piping material and size of the refrigerant pipes, refer to the installation manual of
the air conditioner.
Branch joints
Parts
Model name
Type
MXJ-2D2509K
MXJ-3D2509K
MXJ-4D2509K
Liquid side
Gas side
x 3 pieces
1
x 4 pieces
1
x 1 piece
2
x 2 pieces
3
x 2 pieces
4
x 1 piece
2
x 3 pieces
3
x 1 piece
4
x 1 piece
2
x 4 pieces
3
x 3 pieces
1
1
2
3
4
Socket
Condensation may occur on the surface of the insulator
depending on the atmosphere in internal part of the ceiling.
If the internal part of the ceiling has high temperature or humidity rate
is more than 80%, please add proper insulation to prevent water drops.
Weldment must be applied to the stopper part of the pipes and sockets.
EX)
Note
Liquid side branch joint
Connecting method
<How to use socket>
- Connect the pipe to the connecting part of the branch joint or use
provided socket by cutting them according to the diameter of the
connecting pipe.
- When you cut the socket, make sure that the pipe connection part
is over 10 ~15mm.
- After cutting the socket, remove the burr on cut part of the socket.
It is impossible to connect a socket to a pipe when burr removing
process was poor or pipe is deformed.
10 ~15mm
or more
※
Basic specification
<Insertion depth of the connecting pipe>
500mm or more
Main pipe
Connected to outdoor unit
Connected pipe
Before branching
After branching
Connected pipe
Socket
Connected to indoor unit
Socket
Liquid side branch
※
Connect 3 MXJ-2D2509K
branch joints
Keep minimum distance of 500mm or more before
connecting a branch joint.
CAUTION
Do not insert the pipe deeply into the joint.
(Do not insert more than 70mm.)
CAUTION
Connecting pipe
DB98-34641A-04
This marking on the product, accessories or literature indicates that the product
and its electronic accessories (e.g. charger, headset, USB cable) should not be
disposed of with other household waste.
For correct disposal of this product, please visit http://www.samsung.com/weee.pdf