Components

Product Name

Circuit board

Circuit board case

Wiring harness

Screw

Installation manual

Q'TY

1EA

1EA

1EA for Each Wire

2EA

1EA

Shape

Installation

1.

Mount the circuit board case ( ) with screws ( ) inside the outdoor unit control box or at another

appropriate location (Figure 1).

2.

Align the circuit board( ) with the case and lock it into place using the locking tab.

Figure 1. Mounting the circuit board case

Figure 2. Wiring the module

Screw

Circuit board case

Additional holes to use if necessory

Holes for

installing

screws

Connect wire

Connect wire

3.

Connect the 2-pin wiring harness( ) to the interface module at CN83 (Figure 2) and to the outdoor

unit at "GAS LEAK" connector (Main PCB).

4.

Connect the 4-pin wiring harness( ) to the interface module at CN81 (Figure 2) and to the outdoor

unit at "PUMP DOWN" connector (Main PCB).

5.

Restore power to the outdoor unit.

Shut off power to the outdoor unit before wiring the module.

WARNING

• Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout

procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before

servicing could result in death or serious injury.

Installation option setting of outdoor unit

Turn on the outdoor unit and configure outdoor unit options.

Refer to Table 1 and the option section of the outdoor

unit installation manual.
Table 1. Option setting of outdoor unit for MIM-B14A

Input unit SEG1 SEG2 SEG3 SEG4

Function of the option

Remarks

Main

1

9

0

0

Disabled (Factory default)

If the gas leak occurred it should be

entered in the pumpdown operation.

0

1

Enabled

About interface module

MIM-B14A is an interface module that has 2 outputs and 1 input. It is mainly applied to refrigerant leak detector system.

External Contact Interface Module (MIM-B14A)

Example of refrigerant leak detector operation

Figure 3. External contact interface module wiring diagram

1.

The refrigerant leak detection signal is sent to the outdoor unit - through the DDC RL#2 port.

2.

The lock signal of the high pressure valve is output from the - port of the outdoor unit.

3.

The lock signal of the low pressure valve is output from the - port of the outdoor unit.

(Dry Contact output)

Digital Output (

RL#3

)

Digital Input (

DI#2

)

Digital Output

(

RL#0

)

Digital Output

(

RL#1

)

Digital Output

(Dry Contact)

(

RL#2)

DI#1

DO#2 DO#1

(Dry Contact/

Relay output)

(Dry Contact/

Relay output)

(Dry

Contact

input)

DDC

※ Terms and description

DDC : Direct Digital Control

DO : Digital Output

DI : Digital Input

RL : RELAY

[ B14A Relay's contact function/specification ]

- :Dry Contact Output, NORMAL OPEN TYPE (

DO#1

)

- : Dry Contact Output, NORMAL OPEN TYPE (

DO#2

)

- : Dry Contact Input (

DI#1

)

[ DDC Relay's contact function/specification ]
RL#0

: Digital Output, outputs controls that lock the high pressure valve.

RL#1

: Digital Output, outputs controls that lock the low pressure valve.

RL#2

: Digital Output, outputs signals that can detect the refrigerant

leak (to outdoor)

RL#3

: Digital Output, outputs signals that can detect the

refrigerant leak (to external control system)

DI#0

: Digital Input, inputs signals that lock the high pressure valve.

DI#1

: Digital Input, inputs signals that lock the low pressure valve.

DI#2

: Digital Input, resets the DDC status (reset outputs of RL#0 to #3)

Example of the RLD System connection

EXTERNAL CONTROL SYSTEM

MODBUS/TCP

TCP/IP (Daisy Chain)

(Field supplied)

(Low pressure valve)

(High pressure valve)

(Field supplied)

(RL#3)

(RL#2)

(DI#0)

DI

Detector

Relay

(Field supplied)

Sensor

RL

(RL#0)

(RL#1)

(DI#1)

Master DDC

Slave DDC

Interface

Module

(MIM-B14A)

This marking on the product, accessories or

literature indicates that the product and its

electronic accessories (e.g. charger, headset,

USB cable) should not be disposed of with

other household waste.
For correct disposal of this product, please

visit http://www.samsung.com/weee.pdf

Points de collecte sur www.quefairedemesdechets.fr

!

À DÉPOSER

EN MAGASIN

À DÉPOSER

EN DÉCHÈTERIE

OU

FR

Cet appareil,

ses accessoires,

piles et cordons

se recyclent

DB68-07112A-01

This product is India RoHS compliant

DB68-07112A-01_IM_External Contact Interface Module_EU_L02_.indd 22-23

DB68-07112A-01_IM_External Contact Interface Module_EU_L02_.indd 22-23

2022-11-28 오후 6:47:36

2022-11-28 오후 6:47:36

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Samsung MIM-B14A

Other Samsung Air Conditioners Models