Components
Product Name
Circuit board
Circuit board case
Wiring harness
Screw
Installation manual
Q'TY
1EA
1EA
1EA for Each Wire
2EA
1EA
Shape
Installation
1.
Mount the circuit board case ( ) with screws ( ) inside the outdoor unit control box or at another
appropriate location (Figure 1).
2.
Align the circuit board( ) with the case and lock it into place using the locking tab.
Figure 1. Mounting the circuit board case
Figure 2. Wiring the module
Screw
Circuit board case
Additional holes to use if necessory
Holes for
installing
screws
Connect wire
Connect wire
3.
Connect the 2-pin wiring harness( ) to the interface module at CN83 (Figure 2) and to the outdoor
unit at "GAS LEAK" connector (Main PCB).
4.
Connect the 4-pin wiring harness( ) to the interface module at CN81 (Figure 2) and to the outdoor
unit at "PUMP DOWN" connector (Main PCB).
5.
Restore power to the outdoor unit.
Shut off power to the outdoor unit before wiring the module.
WARNING
• Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout
procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before
servicing could result in death or serious injury.
Installation option setting of outdoor unit
Turn on the outdoor unit and configure outdoor unit options.
Refer to Table 1 and the option section of the outdoor
unit installation manual.
Table 1. Option setting of outdoor unit for MIM-B14A
Input unit SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Main
1
9
0
0
Disabled (Factory default)
If the gas leak occurred it should be
entered in the pumpdown operation.
0
1
Enabled
About interface module
MIM-B14A is an interface module that has 2 outputs and 1 input. It is mainly applied to refrigerant leak detector system.
External Contact Interface Module (MIM-B14A)
Example of refrigerant leak detector operation
Figure 3. External contact interface module wiring diagram
1.
The refrigerant leak detection signal is sent to the outdoor unit - through the DDC RL#2 port.
2.
The lock signal of the high pressure valve is output from the - port of the outdoor unit.
3.
The lock signal of the low pressure valve is output from the - port of the outdoor unit.
(Dry Contact output)
Digital Output (
RL#3
)
Digital Input (
DI#2
)
Digital Output
(
RL#0
)
Digital Output
(
RL#1
)
Digital Output
(Dry Contact)
(
RL#2)
DI#1
DO#2 DO#1
(Dry Contact/
Relay output)
(Dry Contact/
Relay output)
(Dry
Contact
input)
DDC
※ Terms and description
DDC : Direct Digital Control
DO : Digital Output
DI : Digital Input
RL : RELAY
[ B14A Relay's contact function/specification ]
- :Dry Contact Output, NORMAL OPEN TYPE (
DO#1
)
- : Dry Contact Output, NORMAL OPEN TYPE (
DO#2
)
- : Dry Contact Input (
DI#1
)
[ DDC Relay's contact function/specification ]
RL#0
: Digital Output, outputs controls that lock the high pressure valve.
RL#1
: Digital Output, outputs controls that lock the low pressure valve.
RL#2
: Digital Output, outputs signals that can detect the refrigerant
leak (to outdoor)
RL#3
: Digital Output, outputs signals that can detect the
refrigerant leak (to external control system)
DI#0
: Digital Input, inputs signals that lock the high pressure valve.
DI#1
: Digital Input, inputs signals that lock the low pressure valve.
DI#2
: Digital Input, resets the DDC status (reset outputs of RL#0 to #3)
Example of the RLD System connection
EXTERNAL CONTROL SYSTEM
MODBUS/TCP
TCP/IP (Daisy Chain)
(Field supplied)
(Low pressure valve)
(High pressure valve)
(Field supplied)
(RL#3)
(RL#2)
(DI#0)
DI
Detector
Relay
(Field supplied)
Sensor
RL
(RL#0)
(RL#1)
(DI#1)
Master DDC
Slave DDC
Interface
Module
(MIM-B14A)
This marking on the product, accessories or
literature indicates that the product and its
electronic accessories (e.g. charger, headset,
USB cable) should not be disposed of with
other household waste.
For correct disposal of this product, please
visit http://www.samsung.com/weee.pdf
Points de collecte sur www.quefairedemesdechets.fr
!
À DÉPOSER
EN MAGASIN
À DÉPOSER
EN DÉCHÈTERIE
OU
FR
Cet appareil,
ses accessoires,
piles et cordons
se recyclent
DB68-07112A-01
This product is India RoHS compliant
DB68-07112A-01_IM_External Contact Interface Module_EU_L02_.indd 22-23
DB68-07112A-01_IM_External Contact Interface Module_EU_L02_.indd 22-23
2022-11-28 오후 6:47:36
2022-11-28 오후 6:47:36
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.