Setting an indoor unit address and installation option
Setting an indoor unit MCU port address
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive option.
3. Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
4. Assign an indoor unit MCU port address by wireless remote controller.
- The initial setting status of indoor unit ADDRESS(MAIN/RMC/MCU port) is “0A0000-100000-200000-300000”. Seg 15 ~ 18 are option for MCU address.
Notice: Also set the MCU and Indoor units address by using Add-on > Change address on S-NET Pro 2. (For more information, see the S-NET Pro 2 Help.)
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
PAGE
-
Setting MCU PORT address
10-digit of MCU address
1-digit of MCU
MCU PORT address
Remote Controller
Display
Indication and
Details
Indication Details
Indication
Details
Indication
Details
Indication
Details Indication
Details
2
0
No MCU port
0~1
10-digit
0~9
1-digit
A~F
PORT
Location
1
MCU port address
setting mode
Example> If you want to set the indoor unit to ‘A’ port of MCU #1. (0A0000 – 100000 – 20101A -30000)
Setting an indoor unit installation option. (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
Added 02 series installation option
1. SEG 3 is Evaporator Drying. When Cooling or dry mode is off. The indoor fan operate in setting minutes.
2. SEG 4 is Minimizing fan operation when thermostat off. Fan stops or operates Ultra low in Cooling when thermostat is off.
3. SEG 15 is Free Cooling control. For free cooling control, Economizer controller is required.
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG3
SEG4
SEG15
Explanation
Evaporator Drying
Use of external room temperature
Setting the output of external control
Indication and
Details
Indication
Details Indication
Details
Indication
Details
Use of External room
temperature sensor
Minimizing fan operation when
thermostat is off
0
Disuse
0
Default
Default
0
External control (Thermo On)
1
Use
Disuse
2
Disuse
Use (Heating)
1
External control (Operation On)
2
Use (5min)
(*1)
3
Use
Use (Heating)
4
Disuse
Use (Cooling)
2
External heater signal
5
Use
Use (Cooling)
4
Use (10min)
(*1)
6
Disuse
Use (Heating / Cooling)
3
External heater signal
7
Use
Use (Heating / Cooling)
8
Disuse
Use (Cooling Ultra Low Fan)
4
Cooling operation signal
6
Use (30min)
(*1)
9
Use
Use (Cooling Ultra Low Fan)
A
Disuse
Use (Heating / Cooling Ultra Low Fan)
5
Free Cooling control (Cooling Thermo On)
B
Use
Use (Heating / Cooling Ultra Low Fan)
6
Free Cooling control (Cooling/Dry Thermo On)
Added 05 series installation option
1. SEG 3 is Cooling only indoor unit for HR. When Indoor unit is directly connected with HR outdoor unit without MCU unit.
2. SEG 23 is forcing FAN Operation for Heating and Cooling mode.
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG3
SEG23
Explanation
Use of Auto Change Over or Cooling only for HR only
Forcing FAN Operation for Heating and Cooling
Indication and
Details
Indication
Details
Indication
Details
Cooling Fan Setting
Heating Fan Setting
0
Disuse
0
Disuse
Disuse
1
Disuse
Use (Fan: User setting)
2
Disuse
Use (Fan: High)
3
Disuse
Use (Fan: Low)
1
Use Auto Change Over for HR only
4
Use (Fan: User setting)
Disuse
5
Use (Fan: User setting)
Use (Fan: User setting)
6
Use (Fan: User setting)
Use (Fan: High)
7
Use (Fan: User setting)
Use (Fan: Low)
8
Use (Fan: High)
Disuse
9
Use (Fan: High)
Use (Fan: User setting)
2
Use Cooling only indoor unit for HR
A
Use (Fan: High)
Use (Fan: High)
B
Use (Fan: High)
Use (Fan: Low)
C
Use (Fan: Low)
Disuse
D
Use (Fan: Low)
Use (Fan: User setting)
E
Use (Fan: Low)
Use (Fan: High)
F
Use (Fan: Low)
Use (Fan: Low)