Page 2 - Contents
2 Correct Disposal of This Product (Waste Electrical & Electronic Equipment) (Applicable in the countries with separate collection systems) This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g. charger, headset, USB cable) should n...
Page 3 - Safety precautions; Important safety symbols and precautions:; Hazards or unsafe practices that may result in; severe personal injury; Hazards or unsafe practices that may result; in minor personal injury; FOR INSTALLATION; WARNING; Extending the power line may result in electric shock or fire.
3 ENGLISH Safety precautions Before using your new air conditioner, please read this manual thoroughly to ensure that you know how to safely and efficiently operate the extensive features and functions of your new appliance.Because the following operating instructions cover various models, the chara...
Page 4 - This may result in electric shock or fire.; CAUTION
4 Safety precautions FOR INSTALLATION WARNING Do not install this appliance near a heater, inflammable material. Do not install this appliance in a humid, oily or dusty location, in a location exposed to direct sunlight and water (rain drops). Do not install this appliance in a location where gas ma...
Page 5 - FOR POWER SUPPLY; FOR USING
5 ENGLISH FOR POWER SUPPLY WARNING When the circuit breaker is damaged, contact your nearest service center.Do not pull or excessively bend the power line. Do not twist or tie the power line. Do not hook the power line over a metal object, place a heavy object on the power line, insert the power lin...
Page 8 - This may result in property damage.; conditioner for long periods of time.; This may result in harm to humans, animals or plants.; FOR CLEANING; Failing to do so may result in electric shock or fire.
8 Safety precautions FOR USING CAUTION Do not use this air conditioner to preserve precision equipment, food, animals, plants or cosmetics, or for any other unusual purposes. This may result in property damage. Avoid directly exposing humans, animals or plants from the air flow from the air condit...
Page 9 - maintaining the air conditioner’ section.
9 ENGLISH FOR CLEANING CAUTION Take care when cleaning the surface of the heat exchanger of the outdoor unit since it has sharp edges. To avoid cutting your fingers, wear thick cotton gloves when cleaning it. Do not clean the inside of the air conditioner by yourself. For cleaning inside the app...
Page 10 - Checking before use; Operation ranges; be operated within.; Maintaining your air conditioner; Internal protections via the unit control system
10 Checking before use Operation ranges The table below indicates the temperature and humidity ranges the air conditioner can be operated within. Refer to the table for efficient use. • The standardized temperature for heating is 7˚C/45˚F. If the outdoor temperature drops to 0˚C/32˚F or below, the h...
Page 11 - Tips on using air conditioner; TOPIC
11 ENGLISH Tips on using air conditioner Here are some tips that you would follow when using your air conditioner. TOPIC RECOMMENDATION Cooling • If current outside temperatures are much higher than the selected indoor temperature, it may take time to bring the inner temperature to the desired cooln...
Page 12 - Viewing the parts; GLOBAL DUCT; Type
12 Viewing the parts • Your air conditioner and display may look slightly different from the illustration shown above depending on your model. NOTE Congratulations on the purchase of the air conditioner. We hope you enjoy the features of your air conditioner and stay cool or warm with optimal effici...
Page 13 - Cleaning and maintaining the air conditioner
13 ENGLISH Cleaning and maintaining the air conditioner GLOBAL DUCT (Plastic Type) 1. Press both hooks and take the filter downward. 2. Clean the Air filter with a vacuum cleaner or soft brush. If dust is too heavy, then rinse it with running water and dry it in a ventilated area. • For best conditi...
Page 14 - detailed information, see the installation part in the manual.; Periodical checks
14 If the air conditioner will not be used for an extended period of time, dry the air conditioner to maintain it in best condition. Dry the air conditioner thoroughly by operating in Fan mode for 3 to 4 hours and then turn off the power. There may be internal damage if moisture is left in compone...
Page 15 - Appendix; Troubleshooting; PROBLEM
15 ENGLISH Appendix Troubleshooting Refer to the following chart if the air conditioner operates abnormally. This may save time and unnecessary expenses. PROBLEM SOLUTION The air conditioner does not operate immediately after it has been restarted. • Because of the protective mechanism, the applianc...
Page 17 - Model specification (Dimension and weight)
17 ENGLISH Model specification (Dimension and weight) Dimension and weight Type Model Net dimension (WxDxH) (mm) Net weight (kg) Indoor unit AM036ANMPKH/EU 850 x 700 x 250 27.9 AM045ANMPKH/EU 850 x 700 x 250 27.9 AM056ANMPKH/EU 850 x 700 x 250 27.9 AM071ANMPKH/EU 850 x 700 x 250 27.9 AM090ANMPKH/EU ...
Page 18 - Indoor unit installation
18 INSTALLATION PARTS Indoor unit installation When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account. 1 Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. 2 Insert bolt anchors. Use existi...
Page 19 - Performing leak test & insulation; Leak test
19 ENGLISH Performing leak test & insulation Once you have checked that there are no leaks in the system, you can insulate the piping and hose. 1 To avoid condensation problems, place T13.0 or thicker Acrylonitrile Butadien Rubber separately around each refrigerant pipe. 2 Wind insulating tape a...
Page 20 - Drainpipe and drain hose installation
20 Pipe Pipe size Insulation Type (Heating/Cooling) Remarks Standard [30°C, 85%] High humidity [30°C, over 85%] EPDM, NBR Liquid pipe Ø6.35 ~ Ø9.52 9t 9t Internal temperature is higher than 120°C Ø12.7 ~ Ø19.05 13t 13t Gas pipe Ø6.35 13t 19t Ø9.52 19t 25t Ø12.70 Ø15.88Ø19.05 ◆ When installing insula...
Page 21 - Without the drain pump; Flexible hose; Drainpipe Connection; With the drain pump
21 ENGLISH Drainpipe and drain hose installation 1. Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m. 2. Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit. 3. Do not install the drainpipe to upward position. ...
Page 22 - Testing the drainage; Centralized Drainage
22 Drainpipe and drain hose installation Prepare 2 liters of water. 1 Pour water into the base pan in the indoor unit as shown in figure. 2 Confirm that the water flows out through the drain hose. Testing the drainage 1 Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger ...
Page 23 - Wiring work; Power and communication cable connection
23 ENGLISH Wiring work Silver solder Norminal dimensions for cable (mm 2 ) Norminal dimensions for screw (mm) B D d1 E F L d2 t Standard dimension (mm) Allowance (mm) Standard dimension (mm) Allowance (mm) Standard dimension (mm) Allowance (mm) Min. Min. Max. Standard dimension (mm) Allowance (mm) M...
Page 24 - Specification of electronic wire
24 Power supply MCCB ELB or ELCB Power cable Earth cable Communication cable Max : 242V Min : 198V X A X A, 30mmA 0.1 s 2.5mm2 2.5mm2 0.75~1.5mm2 Decide the capacity of ELCB(or MCCB+ELB) by below formula. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychl...
Page 25 - Adjusting air flow; Performing the Automatic Air-Volume function.
25 ENGLISH Adjusting air flow Automatic Air-Volume 1).Press the and buttons at the same time for more than 3 seconds and then a Main menu will be displayed.2).Press the / button to select and then press button to enter a Sub-menu setting screen.3).Press the / button to select and then press button t...
Page 27 - Easy Tuning; EASY Tuning
27 ENGLISH Easy Tuning EASY Tuning If the more cooling and heating airflow rate which set up when installing is wanted, or if the more Silent operation which sets up when installing is wanted, air conditioner is tuned for comfort.Indoor unit airflow rate for high, mid, low mode increases or decrease...
Page 28 - Setting the indoor unit option code
28 Setting the indoor unit option code In order to set the indoor unit option code use the wired remote controller and follow the directions below. 1) Press the and buttons at the same time for more than 3 seconds and then a Main menu will be displayed. 2) Press the / button to select and then press...
Page 29 - Setting an indoor unit address; Setting an indoor unit address and installation option; Setting an indoor unit installation option
29 ENGLISH Set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice when setting indoor unit address and installation ...
Page 31 - The procedure of option setting
31 ENGLISH Set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice when setting indoor unit address and installation ...
Page 32 - Option setting
32 Setting an indoor unit address and installation option Option setting Status 1. Setting SEG2, SEG3 optionPress Low Fan button( ∨ ) to enter SEG2 value. Press High Fan button( ∧ ) to enter SEG3 value. Each time you press the button, … will be selected in rotation. 2. Setting Cool mode Press ...
Page 35 - 2 series installation option
35 ENGLISH 1. Check whether power is supplied or not. - When the indoor unit is not plugged in, there should be additional power supply in the indoor unit. 2. The panel(display) should be connected to an indoor unit to receive option. 3. Set the installation option according to the installation cond...
Page 38 - 5 series installation option
38 SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 5 Use of Auto Change Over for HR only in Auto mode (When setting SEG3) Standard heating temp. Offset (When setting SEG3) Standard cooling temp. Offset (When setting SEG3) Standard for mode change Heating → Cooling SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 1 (When setting SE...
Page 41 - Changing a particular option
41 ENGLISH SEG 3, 4, 5, 6, 8, 9 additional information When the SEG 3 is set as "1" and follow Auto Change Over for HR only operation, it will operate as follows. Cooling/Heating mode can be changed when Thermo Off status is maintained during the time with SEG9. A : Set with SEG4 B : Set wit...
Page 42 - QUESTIONS OR COMMENTS?
QUESTIONS OR COMMENTS? DB68-09552A-05 Samsung, PO Box 12987, Blackrock, Co. Dublin. IE or Euro QA Lab. Saxony Way, Yateley, Hampshire GU46 6GG, UK COUNTRY CALL OR VISIT US ONLINE AT AUSTRIA 0800 72 67 864 (0800-SAMSUNG) www.samsung.com/at/support BELGIUM 02-201-24-18 www.samsung.com/be/support (Dutc...
Page 43 - Air Conditioner; user manual; imagine; Duct Type Series