Page 2 - English; Contents; Safety Information
2 English Contents For information on Samsung’s environmental commitments and product-specific regulatory obligations, e.g. REACH, WEEE, Batteries, visit : samsung.com/uk/aboutsamsung/samsungelectronics/corporatecitizenship/data_corner.html Safety Information 3 General information 3 Installing the u...
Page 3 - General information; WARNING
3 English Sa fe ty In fo rm at io n WARNING • Hazards or unsafe practices that may result in severe personal injury or death. CAUTION • Hazards or unsafe practices that may result in minor personal injury or property damage. Carefully follow the precautions listed below because they are essential to...
Page 4 - Installing the unit
4 Safety Information English Sa fe ty In fo rm at io n • For use in Europe: This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction conc...
Page 5 - Preparation of fire extinguisher; ʒθцΧͱиʒʪθͱθAĮࠕ ̇̈θʪʪуϩ̈͝ ̋Ї̈θ˵ʪθθ˵ɇ̷̷ɵʪ; Ignition sources free
5 English Sa fe ty In fo rm at io n • For installation with handling the refrigerant(R-32), use dedicated tools and piping materials. • Servicing and installation shall be performed as recommended by the manufacturer. In case other skilled persons are joined for servicing, it shall be carried out un...
Page 6 - Leakage detection methods
6 Safety Information English Sa fe ty In fo rm at io n Leakage detection methods • The leakage detector shall be calibrated in a refrigerant-free area. • Make sure that the detector is not a potential source of ignition. • The leakage detector shall be set to the LFL (lower flammability limit). • Th...
Page 7 - Power supply line, fuse or circuit; Step 1 Choosing the installation; Installation location requirements; Installation Procedure
7 English Installation Pr oc edur e Power supply line, fuse or circuit breaker WARNING • Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance with current local safety standards. • Always verify that a suitable earthing c...
Page 8 - Installation Pr; CAUTION
8 Installation Procedure English Installation Pr oc edur e • Install the unit in a location that would not obstruct any passageways or thoroughfares. • Install the unit in a location that would not inconvenience or disturb your neighbors, as they could be affected by the noise or the airflow coming ...
Page 9 - Minimum clearances for the outdoor unit; When installing 1 outdoor unit; • The outdoor unit must be installed according to the
9 English Installation Pr oc edur e Minimum clearances for the outdoor unit When installing 1 outdoor unit (Unit: mm) 300 or mor e 1500 or mor e 300 or mor e 600 or more 2000 or more 1500 or mor e 600 or mor e 300 or more 300 or mor e 1500 or mor e When installing more than 1 outdoor unit (Unit: mm)...
Page 10 - Step 2 Checking and preparing; Step 3 Fixing the outdoor unit in place; NOTE
10 Installation Procedure English Installation Pr oc edur e Step 2 Checking and preparing accessories and tools 3-wire Power Cable (option) 2-wire Assembly Cable (option) Drain Plug Energy Label Rubber Leg Installation Manual Flare Nuts, 15.88mm outer pipe diameter Flare Nuts, 9.52mm outer pipe diam...
Page 11 - Step 4 Connecting the power cables,
11 English Installation Pr oc edur e Optional: Fixing the outdoor unit to a wall with a rack Designed to cut off residual vibration from outdoor unit to rack. (not supplied with product) Anchor bolt Base surface Soft rubber designed to cut off vibration from rack to wall. (not supplied with product)...
Page 12 - Conncting the cables to the outdoor unit
12 Installation Procedure English Installation Pr oc edur e Conncting the cables to the outdoor unit A B C 1(L) 2(N) 1(L) 2(N) 1(L) 2(N) F1 F2 1(L) 2(N) F1 1(L) 2(N) F1 1(L) 2(N) F1 F2 1 2 F1 F2 F1 F2 1 2 2 1 F2 1 2 F1 F2 F1 F2 F2 F1 F2 F1 F2 1 2 1 2 1 2 B C B C B C B C A 1(L) 2(N) F1 F2 F1 F2 F1 F2...
Page 13 - Specification for circuit breaker and power supply cord
13 English Installation Pr oc edur e Specification for circuit breaker and power supply cord • Power supply cord is not supplied with air conditioner. • Select the power supply cord in accordance with relevant local and national regulations. • Wire size must comply with the applicable local and nati...
Page 14 - • Use rated cables only.
14 Installation Procedure English Installation Pr oc edur e • Connect the cables to the terminal board using the compressed ring terminal. • Use rated cables only. • Connect the cables with driver and wrench that can apply the rated torque to the screws. • Make sure that appropriate tightening torqu...
Page 17 - ߢעࡡߣߣߡࣗߣߥߡǤࡡߦߡ2і; Step 5 Optional: Extending the power
17 English Installation Pr oc edur e Outdoor-to-indoor power and communication cables specifications Indoor power supply Power supply Max/Min (V) Indoor power cable ߢעࡡߣߣߡࣗߣߥߡǤࡡߦߡ²і ±10% ߢࢋߦ͔͔ࠟ१ࡡߤӥθʪϑ Communication cable 0.75 to 1.5 mm², 2 wires • Power supply cords of parts of appliances for outdo...
Page 18 - Method 2
18 Installation Procedure English Installation Pr oc edur e 3 Insert both sides of core wire of the power cable into the connection sleeve. • Method 1: Push the core wire into the sleeve from both sides. • Method 2 : Twist the wire cores together and push it into the sleeve. Method 1 Method 2 Connec...
Page 19 - Step 6 Connecting the refrigerant pipe; âߢߡߡŵAâߦk
19 English Installation Pr oc edur e Step 6 Connecting the refrigerant pipe ६âߢߡߡŵAâߦk 1 Piping outside diameter Indoor unit Out unit Power supply Ø, V, Hz Outside diameter Liquid Gas **07/09/ 12******** AJ016/020/026 /035RB*DEG AJ100RCJ5EG 1,220-240, 50 1/4" 3/8" AJ052RB*DEG 1/2” A B (h) (...
Page 20 - Step 7 Optional: Cutting and flaring
20 Installation Procedure English Installation Pr oc edur e CAUTION • 3 m as minimum pipe length: It will reduce noise and vibration. • Tighten the nuts to the specified torques. If overtightened, the nuts could be broken so refrigerant may leak. • Protect or enclose refrigerant tubing to avoid mech...
Page 21 - Step 8 Connecting up and removing air; Model Name
21 English Installation Pr oc edur e • Make sure that the spaces where the refrigerant pipes are installed comply with national gas regulations. • Be sure to perform works such as additional refrigerant charging and pipe welding under the conditions of good ventilation. • Be sure to perform welding ...
Page 22 - Outer diameter; Step 9 Performing the gas leak test
22 Installation Procedure English Installation Pr oc edur e CAUTION • Make the electrical connection and leave the system into “stand by mode”. Do not turn on the system! This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve - EEV -). Vacuum Pump Tightening ...
Page 23 - LEAK TEST WITH NITROGEN (before opening valves); ƊϩʪΧߢߡʒʒ̈͝ ̋θʪ ̇θ̈ ̋ʪθɇ͝ϩ࣍ŵࣗߤߣ࣎; Precautions on adding the R-32 refrigerant; Ã͝ ̇ͱθ͔Їθʪθ̈ ̇θцθϩʪ͔ʀͱ͝ϩɇ̈͝θߦϩAĮࠕʪͱθ͔ͱθʪͱ ̇
23 English Installation Pr oc edur e LEAK TEST WITH NITROGEN (before opening valves) In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-32, it is the responsibility of the installer to pressurize the whole system with nitrogen (using a cylinder with pres...
Page 24 - ϩAĮࠕʪ; Calculating the quantity of refrigerant to add; øƟ॒ߤߡ͔
24 Installation Procedure English Installation Pr oc edur e Please fill in the following with indelible ink on the refrigerant charge label supplied with this product and on this manual. • : The factory refrigerant charge of the product. • : The additional refrigerant amount charged in the field. • ...
Page 25 - Step 11 Connecting the drain hose to
25 English Installation Pr oc edur e Step 11 Connecting the drain hose to the outdoor unit When heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate.For adequate draining, do the following : 1 Insert the drain plug into the drain hole on the under...
Page 26 - Step 13 Setting an indoor unit address; Setting the indoor unit addresses automatically; • This product is prohibited one indoor unit installation.; YEL
26 Installation Procedure English Installation Pr oc edur e Step 13 Setting an indoor unit address and installation option Setting the indoor unit addresses automatically CAUTION • This product is prohibited one indoor unit installation. Don't use pipe checking operation and auto addressing mode whe...
Page 27 - ߢɵ̧̈̈͝͝ ̋२ߣθʪʀͱ͝ʒθͱ ̇ ̇२ߤɵ̧̈̈͝͝ ̋२ߦθʪʀͱ͝ʒθ; Setting the indoor unit addresses manually
27 English Installation Pr oc edur e • A part Green LED indicates which pipe failed to be checked. ť̈Χʪࡠߢɵ̷̧̈̈͝͝˝२ߣϑʪʀͱ͝ʒϑͱ˙˙२ߢɵ̷̧̈̈͝͝˝ť̈Χʪ9ࡠߣɵ̷̧̈̈͝͝˝२ߣϑʪʀͱ͝ʒϑͱ˙˙२ߣɵ̷̧̈̈͝͝˝ť̈ΧʪAࡠߤɵ̷̧̈̈͝͝˝२ߣϑʪʀͱ͝ʒϑͱ˙˙२ߤɵ̷̧̈̈͝͝˝ If one or more pipes fail to be checked, A part Green LED will blink in the order of faile...
Page 28 - Setting of PCB Display of the outdoor unit; ࢘ͱθ͔ͱθʪ̈͝ ̇ͱθ͔ɇϩ̈ͱ͝ͱ ̇ϩ˵ʪAͱͱ̷ͱθ2ʪɇϩƟθцθЇ͝ϩʪθϩࡡθʪ ̇ʪθϩͱΧɇ ̋ʪߤߦࢋ; ࣍ߡॉࢤߢॉ9ࢤߣॉAࢤߤॉUࢤߥॉk࣎
28 Installation Procedure English Installation Pr oc edur e Setting of PCB Display of the outdoor unit • Key option of PCB Display ࣚ K1: Function button - K3: Reset button Key Push K1 K3 1 Pipe Checking Operation Reset 2 Cool Mode Try run 3 Heat Mode Try run 4 Pump Down 5 Finish Key Operation ࢘ͱθ͔ͱ...
Page 29 - Ɗʪϩϩ̈͝ ̋ĮΧϩ̈ͱ࣍͝ŵࡐࡐࢥâࡐࡐࡐŵ9ߢUkࢥâࡐࡐࡐŵ9ĘUk࣎; Option setting mode; Mode button
29 English Installation Pr oc edur e Ɗʪϩϩ̈͝˝ĮΧϩ̈ͱ࣍͝ŵࡐࡐࢥâࡐࡐࡐŵ9ߢUkࢥâࡐࡐࡐŵ9ĘUk࣎ Option setting mode Entering mode for setting option op n q r <AR***XPX****> <AR***XWX****> Mode button Ionizer buttonWind-Free button High Temp button Low Temp button o p n q r Mode buttonSingle user buttonWin...
Page 30 - Setting Option; The procedure of setting option; Operation
30 Installation Procedure English Installation Pr oc edur e Setting Option 1 Remove batteries from the remote controller 2 Insert batteries and enter the option setting mode while pressing button and button. 3 Each time you press button, 7-seg on left side is increased by “1” and each time you press...
Page 33 - Option
33 English Installation Pr oc edur e Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation Page Mode Setting main address 100-digit of indoor unit address 10-digit of indoor unit A single digit of indoor unit Indication and details Indication Details Indication De...
Page 34 - Check whether power is supplied or not.
34 Installation Procedure English Installation Pr oc edur e Setting an indoor unit installation option (suitable for the condition of each installation location) 1 Check whether power is supplied or not. ࣚ When the indoor unit is not plugged in, there should be additional power supply in the indoor ...
Page 35 - ΧΧθͱӱ͔ɇϩʪ̷цߩईঐ; Cool
35 English Installation Pr oc edur e Step 14 Cool and Heat modes operation test After installing the outdoor and indoor units, test the Cool and Heat modes. • When you test the Cool mode, set the set temperature of the indoor unit to the lowest one. And when you test the Heat mode, set the set tempe...
Page 36 - Step 16 Optional: Power improvement mode; Setting the power improvement mode
36 Installation Procedure English Installation Pr oc edur e Step 16 Optional: Power improvement mode The power improvement mode has the following power reduction effects. • Reduced power at Thermo off ࣚ When the air conditioner operates in Cool , Dry and Auto mode, if Thermo off is reached during co...
Page 37 - edur; Extra Procedures; Pumping down refrigerant; Relocating the indoor and outdoor; Pumping down
37 English Extra proc edur es Extra Procedures Pumping down refrigerant WARNING • After installing the product, be sure to perform leak tests on the piping connections. After pumping down refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the connecte...
Page 38 - Using the stop valve; Opening the stop valve; Outer Diameter; Closing the stop valve
38 Extra Procedures English Extra proc edur es Using the stop valve Opening the stop valve 1 Open the cap and turn the stop valve anticlockwise by using a hexagonal wrench. 2 Turn it until the axis is stopped. Tightening torque for body cap (Refer to the table) Charging core Tightening torque for ch...
Page 39 - ppendix; Troubleshooting; Explanation; Appendix
39 English A ppendix Troubleshooting The table below list the self-diagnostic routines. For some of error, you must contact an authorized service center.If an error occurs during the operation, it is displayed on the outdoor unit HUB PCB. ࣚ The error codes in the list are for reference only. They ar...
Page 42 - Samsung Electronics
SAMSUNG ELECTRONICS CO., LTD. 107, Hanamsandan 6beon-ro, Gwangsan-gu, Gwangju-si, Korea 62218 Samsung Electronics Service DepartmentPO Box 12987, Blackrock, Co. Dublin. IrelandorBlackbushe Business Park, Yateley, GU46 6GG. UK This appliance is filled with R-32.