Page 2 - English; Contents; Safety Information
2 English Contents Safety Information 3 Installation Procedure 6 Step 1 Choosing the installation location 6 Step 2 Unpacking 9 Step 3 Checking and preparing accessories 9 Step 4 Drilling a hole through a wall 9 Step 5 Taping the pipes, cables, and drain hose 9 Step 6 Connecting the refrigerant pipe...
Page 3 - mation; WARNING; General information
3 English Safety Infor mation Safety Information Carefully follow the precautions listed as below because they are essential to guarantee the safety of SAMSUNG product. WARNING • Always disconnect the air conditioner from the power supply before servicing it or accessing its internal components. • V...
Page 4 - Installing the unit; Power supply line, fuse or circuit breaker; CAUTION
4 English Safety Information Safety Infor mation Installing the unit IMPORTANT : When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines. Always disassemble the electric lines before the refrigerant tubes. • Upon receipt, inspect the product to ver...
Page 5 - Checking auxiliary power switch; NOTE; Operating temperature and humidity; Operation Features
5 English Safety Infor mation Checking auxiliary power switch ON 1 phase circuit breaker 3 phase 4 wire circuit breaker Turn on the auxiliary power switch which is installed separately. NOTE Auxiliary power switch (ELCB, ELB) • Auxiliary power switch is not included in the package. Purchase and inst...
Page 6 - Instal; Step 1 Choosing the installation; Indoor unit; Top view; Outdoor unit; Installation Procedure
6 English Instal lation Pr oc edure Step 1 Choosing the installation location Determine the installation location considering the following conditions and obtain the user approval. Indoor unit • Install the unit where the pipes and cables can be easily connected to the outdoor unit. • Install the un...
Page 7 - Outdoor unit installation request; When installing 1 outdoor unit
7 English Instal lation Pr oc edure Outdoor unit installation request • The suggested space is based on the outdoor temperature of 35°C while in operation. If the outdoor temperature is higher than 35°C, secure more space. • Be sure to secure sufficient clearance for a person and air flow passage. •...
Page 8 - Fixing the outdoor unit in place
8 English Installation Procedure Instal lation Pr oc edure WARNING • Should adopt bar type louver. Don’t use a type of rain resistance louver. [Bar type louver] [Rain resistance louver] • Louver specifications. – Angle criteria : less than 20° – Opening ratio criteria : greater than 80% WARNING • Af...
Page 9 - Step 2 Unpacking; Unpacking the indoor unit; Step 3 Checking and preparing; Accessories in the indoor unit package; Step 4 Drilling a hole through a wall; drain hose
9 English Instal lation Pr oc edure Step 2 Unpacking Unpacking the indoor unit 1 Open the indoor unit package. 2 Remove the top and middle cushions. 3 Remove the bottom cushion. Unpacking the outdoor unit 1 Pull out the outdoor unit from the package. 2 Remove the top cushion. 3 Remove the 4 screws f...
Page 10 - Step 6 Connecting the refrigerant
10 English Installation Procedure Instal lation Pr oc edure 2 Wind the refrigerant pipes, power cable, communication cable, and drain hose with vinyl tape to make a pipe bundle. Pipe insulator Vinyl tape Drain hose Indoor/outdoor unit communication cable NOTE • Be sure to insulate the pipes without ...
Page 12 - Step 7 Optional: Cutting and flaring
12 English Installation Procedure Instal lation Pr oc edure Step 7 Optional: Cutting and flaring the pipes 1 Make sure that you have the required tools; pipe cutter, reamer, flaring tool, and pipe holder. 2 If you want to shorten the pipes, cut it with a pipe cutter, making sure that the cut edge re...
Page 13 - Outdoor-to-indoor power and communication
13 English Instal lation Pr oc edure AC100BNPDKH (1-phase) F2 F1 1(L) 2(N) N L F1 F2 V1 V2 F3 F4 1(L) 2(N) Indoor Unit Cable clamp Indoor power cable Main power cable Communication cable Cable tie AC140BNPDKH (3-phase) F1 F2 V1 V2 F3 F4 1(L) 2(N) N L3(T) 1(L) 2(N) L2(S) L1(R) F2 F1 Indoor Unit Cable...
Page 14 - Connecting the cable to the power terminal; Connecting the cables; Entire system diagram; Power wiring diagram
14 English Installation Procedure Instal lation Pr oc edure Thickness of the wire (mm²) B (mm) d2 (mm) 2.5 Less than 9.5 More than 4.5 4.5 Less than 9.5 More than 4.5 6.0 Less than 9.5 More than 4.5 10.0 Less than 15 More than 8.4 Connecting the cable to the power terminal Connect the cables to the ...
Page 15 - Indoor and outdoor unit connection diagram
15 English Instal lation Pr oc edure Indoor and outdoor unit connection diagram Indoor unit Outdoor unit 1(L) 2(N) L F1 F1 F2 V1 V2 F3 F4 1(L) 2(N) N F2 AC140BXPDNH • This product uses a 3-phase 4-wire electrical system, with 380 to 415V supply. • When connecting the outdoor-to-indoor power cables, ...
Page 16 - Step 9 Optional: Extending the power
16 English Installation Procedure Instal lation Pr oc edure NOTE 1 Voltage range • Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits 2 Maximum allowable voltage variation between phases is 2%. 3 Wire size & type mus...
Page 18 - Step 10 Setting the indoor unit
18 English Installation Procedure Instal lation Pr oc edure Step 10 Setting the indoor unit addresses and the installation options You cannot set both of the indoor unit addresses and the installation options in a batch: set both of them respectively. Common steps for setting the addresses and optio...
Page 23 - Setting the indoor unit addresses
23 English Instal lation Pr oc edure Setting the indoor unit addresses Option No. for an indoor unit address: 0AXXXX-1XXXXX-2XXXXX-3XXXXX Before installing an indoor unit, be sure to set an address for the indoor unit by taking the following steps: 1 Make sure that the power is supplied to the indoo...
Page 24 - Setting the installation options in a batch
24 English Installation Procedure Instal lation Pr oc edure Setting the installation options in a batch Option No. for an indoor unit address: 02XXXX-1XXXXX-2XXXXX-3XXXXX 1 Make sure that the power is supplied to the indoor unit. If the indoor unit is not plugged in, it must include a power supply. ...
Page 25 - Emergency Temperature Output (ETO) function; Setting up the ETO
25 English Instal lation Pr oc edure Emergency Temperature Output (ETO) function CAUTION • In order to deploy the ETO function, the MIM-B14, an external contact interface module, must be installed in each indoor unit. – The ETO is a concept of emergency operation of indoor units. If the indoor unit ...
Page 26 - ETO operation specifications
26 English Installation Procedure Instal lation Pr oc edure ETO operation specifications 1 Main indoor unit – Based on the external contact control settings, the main indoor unit decides whether to generate output when an error (indoor unit stop) occurs. – Based on the ETO settings, the main indoor ...
Page 27 - Step 11 Checking the earthing; Step 12 Performing gas leakage test
27 English Instal lation Pr oc edure Step 11 Checking the earthing If the power distribution circuit does not have a earthing or the earthing does not comply with specifications, an earthing electrode must be installed. The corresponding accessories are not supplied with the air conditioner. 1 Selec...
Page 28 - Step 13 Evacuating the air; Step 14 Charging the refrigerant; Important information regulation regarding
28 English Installation Procedure Instal lation Pr oc edure Step 13 Evacuating the air 1 Connect the manifold gauge to a vacuum pump. 2 Purge the air from the system using the vacuum pump for about 30 minutes. • Make sure that pressure gauge shows -0.1006 Mpa after about 30 minutes. • Use a vacuum p...
Page 29 - Pressure table for each temperature; Cooling operation
29 English Instal lation Pr oc edure Indoor unit Outdoor unit (Scale) Ref. Vacuum pump Liquid side service valve Gas side service valve Manifold gaugeHigh pressure side Low pressure side Open the manifold gauge valve connected to the liquid service valve and add refrigerant to reach the fixed quanti...
Page 30 - Step 15 Fixing and insulating the; Step 16 Installing and connecting the
30 English Installation Procedure Instal lation Pr oc edure Step 15 Fixing and insulating the connection part for refrigerant pipes CAUTION • Before wrapping the connection part for refrigerant pipes, be sure to check whether there is gas leakage on the connection part. 1 Wrap the foam insulation ar...
Page 31 - Step 17 Performing drainage test; Step 18 Checking the earthing
31 English Instal lation Pr oc edure 2 Insert the end of the drain hose to the extension drain hose to make a connection. 3 Tightly wrap the connection part with a cable tie or tape for fixing. Connecting drain hose Insulation (foamed polyethylene) Drain hole for duct (polypropylene) Drain hose • Wh...
Page 32 - Step 19 Performing the final check
32 English Installation Procedure Instal lation Pr oc edure Step 19 Performing the final check and trial operation 1 Check the power supply between the outdoor unit and the auxiliary circuit breaker. • 1 phase power supply: L, N • 3 phases power supply: R, S, T, N 2 Check the indoor unit. • Check th...
Page 35 - Step 20 Pumping down refrigerant
35 English Instal lation Pr oc edure Step 20 Pumping down refrigerant WARNING • After installing the product, be sure to perform leak tests on the piping connections. After pumping down refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the connected ...
Page 36 - Appendix; Troubleshooting; Appendix
36 English Appendix Appendix Troubleshooting The table below lists the self-diagnostic routines. For some of error codes, you must contact an authorized service centre. If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB. No. Error Cod...
Page 38 - PRODUCT FICHE (ENERGY LABELLING OF AIR CONDITIONERS)
38 English Appendix Appendix COMMISSION DELEGATED REGULATION (EU) No 626/2011 i) PRODUCT FICHE (ENERGY LABELLING OF AIR CONDITIONERS) ii) A Supplier's name - Samsung B Model name (Indoor/Outdoor) - AC100BNPDKH/AC100BXPDKH C Sound Power Level (Indoor/Outdoor) dB(A) 60 / 70 D Refrigerant name ¹⁾ - R-4...