Rinnai RSEP1S35P - User Manual

Rinnai RSEP1S35P

Rinnai RSEP1S35P Heater – User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
Page: / 5

Table of Contents:

  • Page 3 – Combustion
  • Page 4 – Submissions - Proof of Performance; radiant heater; — Accessories / Ancillaries; Temperature Control: Indoor Space Heating; maintain the comfort temperature setting within the heat zone; Heater Control: Outdoor Patio Heating Application; up to 4 Heaters or Zones
  • Page 5 – Other Heater Ancillaries; using chain or rod
Loading the manual

1




HVAC Guideline Specifications
SE+ Series
Packaged High Intensity Luminous Infrared Radiant Gas Heater
Commercial/Industrial Applications


Size Range:

23,000 to 35,000 Btuh Input Rating

Models:

Description

Part # NG

Part # LPG

Input (Btuh)

RSEP1S25P/N S/S Screen; Aluminized Steel Covers

RSEP1S25N

RSEP1S25P

23,000

RSEP1S35P/N S/S Screen; Aluminized Covers

RSEP1S35N

RSEP1S35P

35,000


Part 1

— General


1.01 SYSTEM DESCRIPTION

Outdoor / Indoor approved overhead mounted, electrically controlled patio and high intensity infrared
radiant heating unit utilizing gas combustion for heatin g as supplied by Rinnai.

1.02 QUALITY ASSURANCE

A. Heater will be tested and approved in accordance with ANSI Z83.19b / CSA 2.35b (latest version)

High Intensity Gas-Fired Heaters (indoor use), and additionally in accordance with ANSI Z83.26 /
CSA 2.37 (latest version) Outdoor Gas-Fired Patio Heaters and certified by CSA International.

B. Each heater will be subjected to run testing on the assembly line.

C. The heater will be warranted by the manufacturer for defects in material and workmanship fo r a

period of 3 years on the burner assembly and ceramic tiles that comprise the burner panel, and 1
year on all other parts and components.

1.03 DELIVERY, STORAGE, AND HANDLING

Heater will be stored to secure against damage and handled per manufacturer’s recommendations.


Part 2

— Product


2.01 EQUIPMENT (STANDARD)

A. General:

Factory assembled, single-piece infrared radiant heating unit for overhead mounted patio, space or
area heating application. Supplied with the heater will be all necessary factory in stalled wiring,
piping, and controls required prior to field installation and start -up.


B. Heater Body Construction:

1. Models: RSEP1S25P/N and RSEP1S35P/N

a. The heater wrap screen will be constructed of 409 grade stainless steel sheet metal.

b. The end cover, top cover and internal sheet metal components will be constructed of high

grade aluminized steel.

c. All exposed surfaces of exterior sheet metal components will have a coating of high

temperature flat black emissive coating.

C. Burner Construction and Emitting Surface:

1. General:

a. Burner body will be constructed of high grade aluminized steel

b. The radiant surface will be comprised of a panel of porous ceramic burner tiles with

indentation surface technology creating 372 indentations in the tile radiating surface that
increases the emitting surface area by 50%.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 3 - Combustion

3 4. Heater Zone Temperature Control: a. Space Heating: Each heater zone will be controlled by a 24 Vac infrared set -back thermostat (refer Part 4.01), or other 24 Vac thermostat as supplied by the manufacturer b. Outdoor Patio Comfort Heating: Heaters or heater zones will be controlled by a Patio ...

Page 4 - Submissions - Proof of Performance; radiant heater; — Accessories / Ancillaries; Temperature Control: Indoor Space Heating; maintain the comfort temperature setting within the heat zone; Heater Control: Outdoor Patio Heating Application; up to 4 Heaters or Zones

4 (Test B methodology). The convection heat coefficient of the appliance will not be more than 55% for inputs up to 50,000 Btuh. 3.04 Submissions - Proof of Performance The project submission will include written results of the radiant coe fficient testing of the complete heater as produced by CSA I...

Page 5 - Other Heater Ancillaries; using chain or rod

5 a. ELECTRICAL: The Patio Control Panel will provide 24 Vac power to the heaters. The installer will provide a 120V/24V/60HZ transformer with a minimum capacity of 40VA for the first heater plus 20VA for each additional heater to be controlled by the panel. 4.03 Other Heater Ancillaries A. Gas Conn...

Other Rinnai Heaters Models