Rheem Universal Gas - Manual
Rheem Universal Gas – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – MAXIMUM DELIVERY
- Page 3 – RECOVERY CAPACITIES
- Page 4 – D E F G H; DIMENSIONAL INFORMATION
- Page 5 – CLEARANCES TO COMBUSTIBLES; DIMENSIONAL DIAGRAM
- Page 6 – Recommended Specifications (for trade reference only); UNIVERSAL; Limited Warranty
Universal Gas
Commercial Water Heaters
Available in Sizes Ranging From 35 - 100 Gallon Tank-Type Models
98,000 BTU/Hr. thru 400,000 BTU/Hr.
Universal
Gas Commercial Water Heaters are specifically designed to
minimize the difficulty of replacing failed water heaters and are versatile for
new installations. These products are designed for applications requiring
large quantities of hot water.
Construction Features:
• Universal tank design –
maximizes installation adaptability
by offering models with Top, Front
Side and Rear Side Inlet/Outlet
water connections.
• Universal space saver design –
short heights and small jacket
diameters result in greater
installation flexibility.
• Patented multi-flue tank design –
proprietary steel formulation,
patented multi-flue design, and
two coats of high temperature
porcelain enamel to maximize
corrosion resistance result in a
superior heat exchanger design.
• Low profile automatic flue
damper –
low profile design minimizes over-
all product height. New heavy duty
vent hood supports are designed
to withstand rigors of installation.
• Spark-To-Pilot ignition system –
standard on all models. Provides
reliable and energy saving ignition
sequencing by igniting the pilot
only when the thermostat calls for
heat.
• System Sentinel
™
LED
diagnostic system –
our exclusive diagnostic system,
with glowing LED lights, verifies
system operation sequence by
sequence.
• Full port, full flow brass drain
valve
Certifications and Ratings:
• Efficiency –
these models have been tested according to ANSI test
procedures, and meet or exceed the thermal efficiency and standby loss
requirements of current ASHRAE standard (Part of the Federally
mandated Energy Policy Act (EPact)). Also exceeds energy efficiency
codes of all states including California Energy Commission (CEC).
• Safety and construction –
these products are design certified by the
CSA: a) For operation at 180°F. b) To meet all safety and construction
requirements of ANSI Z21.10.3. c) As an automatic storage or instanta-
neous water heater. d) As an automatic circulating tank water heater.
e) For operation on combustible floors and in alcove installations.
All models are North Carolina Code compliant.
CERTIFIED FOR A 150 PSI MAXIMUM WORKING PRESSURE
(160 PSI FOR ASME MODELS).
• Optional constructions –
ASME construction is available on designated
models. UL Sanitation (NSF5) compliant models are available when
equipped with optional leg kit. (Part No. AE35450)
Continued next page.
Small Jacket
Diameters
Short
Floor-to-Vent
Heights
Multiple
Water Connection
Options
(On Selected
Models)
(With Optional
Leg Kit)
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
MODEL TANK CAPACITY INPUT BTU/HR. TEMP. 5 10 15 20 30 45 60 120 180 Min. to Rec. NUMBER GALLONS LITERS NAT. & L.P. RISE UNITS Min. Min. Min. Min. Min. Min. Min. Min. Min. Contents G50-98 50 189 98,000 100°F GAL 43 51 59 67 83 106 130 225 320 32 37.7°C LTR. 162 192 222 252 312 402 492 852 1212 G7...
MODEL INPUT BTU/HR. THERMAL 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F NUMBER NATURAL & L.P. EFFICIENCY UNITS 22°C 28°C 33°C 39°C 45°C 50°C 56°C 61°C 67°C 72°C 78°C G50-98 98,000 80% GPH 238 190 158 136 119 106 95 86 79 73 68 LPH 899 719 600 514 450 400 360 327 300 277 257 G75-1...
WATER CONNECTIONS APPROXIMATE MODEL TOP FRONT REAR SHIPPING WEIGHT NUMBER UNITS A B C D E F G H IN/OUT SIDE SIDE STD. ASME G50-98 inches 62-3/4 57-1/8 22-1/2 22-5/8 5 50-1/2 1/2 15 1 1-1/2 1-1/2 270 lbs. N/A mm 1594 1451 667 575 127 1283 13 381 25 38 38 122 kgs. N/A G75-125 inches 65-1/2 61 26-1/4 2...