Rheem 100 - Manual
The Installation Manual for Rheem-Ruud AdvantagePlus sealed-combustion gas-fired commercial water heaters covers essential technical aspects like efficiency ratings, safety certifications, and operational specifications. Key areas include recovery rates for hot water delivery, maximum output capacities over time, venting requirements (such as side or vertical roof vent setups), and installation dimensions to ensure proper fitment. The document also addresses compatibility with booster kits for high-temperature sanitation needs and outlines warranty details for tank integrity.
Table of Contents:
- Page 1 – Sealed-Combustion Water Heater Features and Certifications
- Page 2 – Technical Specifications for Water Heater Models
- Page 3 – Installation Diagrams and Booster Setup
- Page 4 – Booster Installation Kit and Warranty Information
AdvantagePlus
Sealed-Combustion Gas-Fired Commercial Water Heaters
Available in Sizes Ranging From 45 - 119 Gallon Models
100,000 BTU/Hr. thru 199,000 BTU/Hr.
Rheem-Ruud AdvantagePlus
TM
Gas Commercial Water Heaters are
specifically designed to provide customers with maximum savings on
operation, space and installation. Designed with the most advanced
technology available, these products optimize efficiency and operating
reliability.
Construction Features:
•
316L stainless steel tank
construction (requires no
anode rods).
•
No chimney required; direct
vent using plastic pipe.
•
Thermal efficiency of 95%
dramatically reduces
operating costs.
•
85 equivalent feet of vent length.
•
Low NOx emissions. Meets
SCAQMD Rule 1146.2.
•
High impact plastic jacket
eliminates dents.
•
2” of non-CFC, polyurethane
foam insulation.
•
Less than 1/2 degree per
hour heat loss (R17).
•
Corrosion resistant, high
efficiency 90/10 cupronickel
heat exchanger.
•
Self-diagnostic electronic
control with digital readout for
water temperature, set point
and differential.
•
Removable front cover allows
easy access to equipment
(24" service clearance
recommended).
•
Temperature range from 70°F to
160°F (maximum temperature
setting of 180°F available on
HE45-160 and HE45-199
booster models only).
•
Zero clearance to all
combustible surfaces.
•
Factory installed AGA/ASME
rated T&P relief valve.
•
Booster installation kit provided
with HE45-160 and HE45-199
booster models.
No Chimney Required
Vents Up To 40 Feet
Using 3" Schedule 40
PVC, CPVC or ABS Pipe
100,000 BTU and
130,000 BTU Models
Are Certified To
Vent With 2"
Schedule 40 PVC,
CPVC or ABS Pipe
Certifications and Ratings:
The water heaters are UL/ULC listed and meet or exceed thermal efficiency
and standby loss requirements of current ASHRAE standards. All water
heaters are supplied with an AGA/ASME rated temperature and pressure
relief valve. The control panel is an integrated solid state temperature and igni-
tion control device with integral diagnostics, LED fault display capability and a
digital display of temperature settings. All models are North Carolina Code
compliant. Meet all safety and construction requirements of ANSI Z21.10.3.
CERTIFIED FOR A 150 PSI MAXIMUM WORKING PRESSURE.
®
Continued next page.
Heat Exchanger /
Combustion Chamber
Control Well and E.C.O.
Air Inlet Connector
Gas Valve
Combustion Blower
Gas Burner
Gas Inlet Nipple 1/2”
Hot Surface Ignitor
Flame Probe
Exhaust Outlet Connector
Control Board
Vent Over-Temp
Reset Switch
Exhaust Elbow and Drain
Pressure Switch
Transformer
Condensate Connector
Hose
Condensate Connector
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Was this manual helpful?
About this manual
- Brand
- Rheem
- Model
- 100
- Document type
- Manual
- Language(s)
- English
- Pages
- 4
- File size
- 143.6 KB
- Format
Summary
Details on sealed-combustion gas-fired commercial water heaters, construction features, high thermal efficiency, low emissions, and safety certifications including UL, NSF, and GAMA. Exploded diagram of internal components is illustrated.
Technical specifications covering water recovery rates, maximum water delivery amounts over time, physical dimensions, weight, venting requirements, and maximum setpoint temperatures for various gas water heater models.
Technical diagrams and specifications for appliance installation, including dimensional information, side and vertical roof venting options with concentric vent kits, and a booster setup for high-temperature sanitation rinse for dishwashers.