Ranco ETC-111000-000 - Installation Manual
Ranco ETC-111000-000 Thermostat – Installation Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 4 – CONTROL WIRING; General; CONTROL MOUNTING
- Page 5 – FIELD REPAIRS; SENSOR MOUNTING
- Page 6 – SPECIFICATIONS; EXTENDING SENSOR; Checkout Procedure; SENSOR REPLACEMENT; Sensor Replacement; Replacement Sensor - Order
- Page 7 – DONNÉES D'INSTALLATION; CONTRÔLE DE LA TEMPÉRATURE; APPLICATIONS; Caractéristiques électriques; INFORMATIONS DE COMMANDE CTE; Rétroéclairage
- Page 10 – CÂBL AGE DE CONTRÔLE; Généralités; Câblage d'entrée et de sortie; Sortie analogique; MONTAGE DE LA COMMANDE
- Page 11 – RÉPARATIONS SUR LE TERRAIN; MONTAGE DU CAPTEUR
- Page 12 – SPÉCIFICATIONS; Procédure de contrôle; REMPLACEMENT DU CAPTEUR; Remplacement du capteur; Capteur de remplacement – Commande
INSTALLATION DATA
ETC SINGLE STAGE ELECTRONIC
TEMPERATURE CONTROL
The Ranco® ETC is a microprocessor-based
family of electronic temperature controls,
designed to provide on/off control
for commercial heating, cooling, air
conditioning and refrigeration. The ETC
is equipped with a liquid crystal display
(LCD) that provides a constant read
out of the sensed temperature, and a
touch keypad that allows the user to
easily and accurately select the setpoint
temperature, differential and heating/
cooling mode of the operation. Models
are available that operate on either line
voltage (120/208/240V AC) or low voltage
(24V AC).
APPLICATIONS
With its wide temperature setpoint range
and selectable heating or cooling modes,
the ETC can be used for a wide variety of
applications including refrigerated display
cases, walk-in and reach-in refrigerators,
milk coolers, refrigerated warehouses,
chillers, beer and beverage coolers,
tank heating, space and return air temperature
controls and condenser fan cycling.
FEATURES
• Wide setpoint temperature range (-30°F to 220°F) and differential
adjustment (1°F to 30°F)
• Simple keypad programming of setpoint temperature, differential
and cooling/heating modes
• LCD display readout of sensor temperature, control settings,
relay status and onboard diagnostics
• LED (Light Emitting Diode) backlight to improve visibility of the display
in low light ambient applications.
• IP67 rated (water and dust resistant) thermistor-based probe to
remotely monitor temperature
• The sensor probe can be retrofitted in the field by the use of factory
installed interconnect
• Remote temperature sensing up to 400 feet
• SPDT output relay
• User-selectable Fahrenheit/Celsius scales
• Lockout switch to prevent tampering by unauthorized personnel
• Choice of line voltage and low voltage models available
• Optional 0 to 10 volt analog output available for remote temperature
indication
• Anti-short Cycle Compressor Delay for cooling applications
SPECIFICATIONS
Input Voltage
120 or 208/240V AC (24V AC optional), 50/60 Hz
Temperature Range -30°F to 220°F
Differential Range 1°F to 30°F
Switch Action
SPDT
Sensor
Thermistor, 1.94in. long x 0.25 in. diameter with
8 ft. cable, IP67 rated
Power Consumption 120/208/240V AC:
100 Milliamps
24V AC:
2 - 6 VA
1
Relay Electrical Ratings
120V 208/240V
NO Contact
Full-load Amps
16 Amps
8 Amps
Locked rotor Amps
96 Amps
48 Amps
Resistive Amps
15 Amps
8 Amps
Horsepower
1 HP
1 HP
NC Contact
Full-load Amps
5.8 Amps
2.9 Amps
Locked rotor Amps
34.8 Amps
17.4 Amps
Resistive Amps
5.8 Amps
2.9 Amps
Horsepower
1/4 HP
1/4 HP
Pilot Duty: 125 VA at 120/208/240V AC
Control Ambient Temperature
Operating
-20°F to 140°F (-29°C to 60°C)
Storage
-40°F to 176°F (-40°C to 80°C)
Ambient Humidity
0 to 95%, RH, Non-condensing
0 to 10V Output Impedance 1K
Enclosure
NEMA 1, Plastic
Agency Approvals
UL Listed, File E94419, Guide XAPX
CSA Certified, File LR68340, Class 4813 02
ETC ORDERING INFORMATION
Uni-Line
OEM
Input
No. of
0 - 10 V
Numbers
Numbers
Voltage
Stages
Output
ETC-111000-000 ETC-111020-000 120/240
1
No
ETC-111100-000
ETC-111120-000
120/240
1
Yes
ETC-112000-000 ETC-112020-000
24
1
No
ETC-112100-000
ETC-112120-000
24
1
Yes
OPERATION
Liquid Crystal Display (LCD)
The LCD display provides a constant read out of the sensor temperature
and indicates if the output relay is energized. When the S1 annunciator
is constantly illuminated during operation, the relay is energized. The
display is also used with the keypad to allow the user to adjust the
setpoint temperature, differential and heating/cooling modes.
Backlight
When any of the 3 mode keys are pressed, the backlight is activated
and the ETC is in control mode. Press the SET key to begin program
mode.
Control Setup
The temperature setpoint refers to the temperature at which the
normally open (NO) contacts of the output relay will open. Determine
the load (s) to be controlled and the operating mode required, cooling
or heating. Refer to Figure 1 for a visual representation.
• When the cooling mode is chosen, the differential is above the
setpoint. The relay will de-energize as the temperature falls to the
setpoint.
• Anti-short Cycle Compressor Delay for cooling. After a relay
de-energizes, the ETC will prevent the relay from turning on until a
configurable time has occurred to protect compressor.
• When the heating mode is chosen, the differential is below the
setpoint. The relay will de-energize as the temperature rises to the
setpoint.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Was this manual helpful?
About this manual
- Brand
- Ranco
- Model
- ETC-111000-000
- Document type
- Installation Manual
- Category
- Thermostat
- Language(s)
- English, French
- Pages
- 12
- Format
Summary
4 CONTROL WIRING General • All wiring should conform to the National Electric Code and local regulations. • The total electrical load must not exceed the maximum rating of the control (see Specifications). • Use copper conductors only.• Electrical leads should not be taut; allow slack for temperatur...
5 Figure 5: Typical Wiring Diagram for 24V AC Power Input and Line Voltage Switching. Figure 7: Typical Wiring Diagram for 24V AC Power Input and Line Voltage Switching. Figure 4: Typical Voltage Wiring Diagram. Figure 8: 0-10 V Analog Output Located on Power (Lower) Circuit Board. Figure 6: Differe...
Customer Service Telephone 1.800.304.6563 Customer Service Facsimile 1.800.426.0804 [email protected] Robertshaw®, Ranco®, Paragon® and Uni-Line® are trademarks of Robertshaw, its subsidiaries and/or affiliated companies. All other brands mentioned may be the trademarks of their res...