  • Page 2 – : BEFORE PERFORMING THE WIRING OPERATION TURN THE POWER SOURCE; CAUTION; Battery; Battery; Battery; Battery; Coil; Magnetic Pickup Input; If replacing an SS100 Series; Energize to Run Solenoid; Frequency/RPM Input Source; Figures 4 and 5; . Ignition switch must be turned off to unlatch.
  • Page 3 – . The air shutoff device must be manually reset to; Figure 7; Dual Set Point Oil Pressure Switch; A dual set point oil pressure switch is shown in; Figure 8; . Engine speed is controlled by OPL pressure; SS300-AD with Clutch Engager; Figure 6; Common
  • Page 4 – SPEED SETTING ADJUSTMENT; LED; Warranty
Loading the manual

SS-97028N page 1 of 4

Installation and Operation Instructions for
SELECTRONIC

®

Speed Switches

SS300 Series

SS-97028N

Revised 05-04

Section 20

00-02-0286

Please read the following information before installing

.

A visual inspection of this product for damage during shipping is rec-

ommended before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to NEC
and local codes.

GENERAL INFORMATION

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

Disconnect all electrical power to the machine.

Make sure the machine cannot operate during installation.

Follow all safety warnings of the machine manufacturer.

Read and follow all installation instructions.

SPEED SWITCH

1

PICKUP

INPUT

-BATT

+BATT

GND. FOR

T/D

POS. TO

LATCH

ENERGIZE

SPEED

ADJ.

DE-ENERGIZE

2

3

4

5

6

7

8

SS300-AD

Description

The SS300 Series are single set point speed switches with SPDT relay dry contact
output. The trip point is set by a potentiometer. An LED indicates when the signal
source is present. A second LED turns on when the trip point is reached.

See Table 1

for available models and requirements. An optional time delay is on board to delay
operation of the relay for 2-6 seconds after the set point has been reached.

The SS300 Series speed switch is intended for installation within a weatherproof
enclosure to protect it from rain, dust, etc.

Overspeed Shutdown

The SS300 Series shuts down the engine if RPM exceeds the pre-set limit.

Speed Sensitive Pull-in/Drop-out

Engage or disengage PTO’s, 4-wheel drives, other switch points, etc. according
to speed of engine being monitored.

Engine and Transmission Alarm/Shutdowns

Oil pressure in some engines and transmissions varies widely between running
and idle speeds. The SS300 Series can select between two pressure switch set
points according to speed of the engine or transmission and thus give maximum
protection to the equipment while at operating RPM and eliminate nuisance
alarms when at idle.

Adjustable Differential Model

The (“AD”) can be adjusted to change the speed range over which the pull-in and
drop-out differential of the relay will operate. A typical application is to insure
that engine speed is above a minimum RPM before applying a load but allows a
drop in speed of several hundred RPM without disconnecting the load.

Table 1: Models Available and Input Signal

Specifications

Power Requirements:

12 VDC (9-16 VDC).
24 VDC (18-30 VDC).

Frequency Signal:

Voltage (all models):

• Minimum Input Voltage Signal:

4.5 Vrms.

• Maximum Input Voltage Signal:

50 Vrms.

Reset Differential Magnetic Pickup Signal Models:

“Standard Models:

2 Hz Differential.

“AD” Models (Adjustable Differential): 6

50-8900 Hz Adjustable

Reset Differential Alternator Models:

“LF” Models (Low Frequency):

2 Hz Differential

“AD-LF” Models (Adjustable Differential Low Frequency):

50-1900 Hz Adjustable.

Output:

Relay contact, SPDT, resistive load, 6 A, 30 VDC.

Time Delay:

When terminal 7 is grounded, the relay operation is delayed for

2-6 seconds after rpm set point is reached.

Adjustment:

20–turn potentiometer(s).

Temperature Range:

-4° to 185°F (-20° to 85°C).

Relative Humidity:

0 to 95% Non-condensing.

Case:

Black, ABS plastic.

Model Number

Distributor

Ignition

Magnetic

Pickup

Alternator

SS300 (std. model)

SS300-LF (low frequency)

SS300-AD (adjustable differential)

SS300-AD-LF (low frq. & Adjst. diff.)

Voltage

12 24

Maximum Current

12V

24V

Pull In

46 mA

46 mA

Pickup only

10.5 mA

16 mA

Frequency Range in Hz

Model Number

25-2000

SS300-LF
SS300-AD-LF

625-9000

SS300-AD
SS300

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - : BEFORE PERFORMING THE WIRING OPERATION TURN THE POWER SOURCE; CAUTION; Battery; Battery; Battery; Battery; Coil; Magnetic Pickup Input; If replacing an SS100 Series; Energize to Run Solenoid; Frequency/RPM Input Source; Figures 4 and 5; . Ignition switch must be turned off to unlatch.

SS-97028N page 2 of 4 MOUNTING DIMENSIONS The SS300 Series models can be mounted to a flat surface withinthe panel using two #8 screws. Mounting screws are not supplied. TYPICAL WIRING INSTALLATION CAUTION : BEFORE PERFORMING THE WIRING OPERATION TURN THE POWER SOURCE OFF AND STOP YOUR ENGINE. CAUTI...

Page 3 - . The air shutoff device must be manually reset to; Figure 7; Dual Set Point Oil Pressure Switch; A dual set point oil pressure switch is shown in; Figure 8; . Engine speed is controlled by OPL pressure; SS300-AD with Clutch Engager; Figure 6; Common

SS-97028N page 3 of 4 TYPICAL WIRING INSTALLATION (continued) Non Latching Overspeed Switch withAir Shutoff Solenoid A non-latching overspeed switch with air shutoff solenoid application isshown in Figure 6 . The air shutoff device must be manually reset to open/run position. Non Latching Overspeed ...

Page 4 - SPEED SETTING ADJUSTMENT; LED; Warranty

SS-97028N page 4 of 4 SPEED SETTING ADJUSTMENT For Models SS300 and SS300-LF NOTE: The adjustment control(s) is a 20-turn potentiometer(s) andhave no stops when the extreme settings are reached. Always turn afull 20 turns. 1. Make sure the PICKUP LED light is “ON”. The PICKUP LED will be flashing fo...

Other Murphy Models

All Murphy Other