Murphy MGC921 Series - Manual
Murphy MGC921 Series – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
MGC-95093B
Revised 03-00
Catalog Section 75
(00-02-0134)
Generator Panel
MGC921 Series
■
Available in Manual or Auto Start
– 12 or 24 VDC Battery Voltage
– Single Phase or 3-Phase
■
Compact
■
Full Featured
Description
The MGC921 provides economical engine and
generator control for applications not requiring
NFPA-99 or NFPA-110 approval. Models are
available for Manual or Automatic start designed
for 3-phase, 4-wire or 1-phase, 3-wire genera-
t o r s . M o d e l s M G C 9 2 1 f e a t u r e m e c h a n i c a l
SWICHGAGE
®
s for engine oil and coolant tem-
perature. Models MGC921E feature EGS elec-
tric SWICHGAGE
®
s. The panels are housed in a
13 x 10 x 11 in. (330 x 254 x 279 mm) shock
mounted NEMA 1 drip-proof enclosure. Current
transformers (CT’s) are not included.
Features
■
Auto-Start Panel includes the following features.
• ASM150, auto-start controller with:
– Optically-isolated noise resistant inputs.
– Outputs for fault annunciator.
– Crank/rest cycle timer, 4 to 25 sec. adjustable.
– Shutdown time delay, 1 to 25 seconds
(adjustable), locks out low oil pressure
and high temperature on start-up.
– Crank disconnect and overspeed
sensing operates from a magnetic pickup
signal (requires 2 Vrms minimum).
• Auxiliary starter relay. Contact rating: 12 volt,
40 amp/24 volt 16 amp.
• Oil pressure SWICHGAGE
®
, 2-1/16 in. (52
mm) dial, 0-100 psi (0-689 kPa) [6.89 bar].
• Temperature SWICHGAGE
®
, 2-1/16 in (52
mm) dial, 130-250°F (54-121°C), 12 ft.
(3.7 m) capillary.
• TEST-OFF-AUTO selector switch.
• Two 2-1/16 in. (52 mm) dia. holes, plugged.
■
Manual Start Panel includes the
following features.
• Power OFF-ON toggle switch and start
push button.
• 518APH TATTLETALE
®
annunciator.
• Auxiliary starter relay. Contact rating: 12 volt,
40 amp/24 volt 16 amp.
• Oil Pressure SWICHGAGE
®
, 2 in (51 mm)
dial, 0-100 psi (0-689 kPa) [6.89 bar].
• Temperature SWICHGAGE
®
, 2 in (51 mm)
dial, 130-250°F (54-121°C), 12 ft. (3.7 m)
capillary.
• Two (2) 2-1/16 in. (52 mm) diameter holes,
plugged.
■
AC meters
• AC voltmeter, 3-1/2 in. (89 mm) dial, ±2%
full scale (specify range: 300 V or 600 V).
• AC ammeter, 3-1/2 in. (89 mm) dial, ±2%
full scale (specify range: 50 to 4000 A).
• AC frequency meter, 120 V, 3-1/2 in. (89
mm) dial, ±0.6% Hz, 45–65 Hz.
• Frequency meter rheostat.
Options
■
AC ammeter-voltmeter phase selector switch*.
Requires 2 additional CTs.
■
Hourmeter, 2 in. (51 mm) dial, 5-digit.
■
Battery voltmeter, 2 in (51 mm) dial (range
determined by battery voltage).
■
Battery ammeter, 2 in (51 mm), 60-0-60.
*Standard (included) with 3-phase models.
Specifications
■
Auto-Start Panel
• Power Requirements:
– 12 VDC battery for 12 V models.
– 24 VDC battery for 24 V models.
• Inputs: Ground or positive inputs for high
temperature or low pressure sensors.
• Outputs:
– Auxiliary starter relay. Contact rating:
12 volt, 40 amp/24 volt 16 amp.
– 300 mA transistors for fault annunciation
• Operating Temperature: -4 to 140°F (-20 to
60°C).
• Cycle Crank Timer: Up to 8 attempts.
Recrank on false starts (fixed 30 seconds).
• Crank/Rest Cycle Timing: 4 to 25 seconds
(adjustable).
• Shutdown Time Delay: 1 to 25 seconds
(adjustable). Locks out low oil pressure and
high temperature on start up.
• Crank Disconnect Speed Setting:
From 30 to 8500 Hz.
• Overspeed Trip Point Setting:
From 30 to 8500 Hz.
• Magnetic Pickup Input:
Requires 2 Vrms minimum.
■
Manual Start Panel
• Power Requirements:
– 12 VDC battery for 12 V models.
– 24 VDC battery for 24 V models.
• Operating Temperature: -4 to 140°F
(-20 to 60°C).
®
FRANK W.
MFR.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.