MGC-02029B

Revised 06-03

Catalog Section 75

(00-02-0500)

Generator Control System

FW

Murphy

Description

The compact and powerful MGC2000 generator
control system features a unique, simple-to-install
and setup design and enhanced operation.
The control method for the MGC2000 may be
specified for using either the AS3000 Autostart
automatic controller or the 518APH electrically
tripped annunciator method.
The system is available in two basic configurations:

MGC2000

features mechanical gages:

- MGC2000-A

Automatic Control: with

Murphy’s AS3000 Generator Controller.

- MGC2000-M

Manual Control: with

518APH annunciator control.
Both configurations include standard AC
voltmeter, AC ammeter, and frequency meter.
Available for single-phase, standard three-phase,
and three-phase, re-configurable generators.

MGC2000E

features electric gages:

- MGC2000E-A

Automatic Control: with

Murphy’s AS3000 Generator Controller.

- MGC2000E-M

Manual Control: with

518APH annunciator control.
Both configurations include standard AC volt-
meter, AC ammeter, and frequency meter.
Available for single-phase, standard three-phase,
and three-phase, re-configurable generators.

Features

Dynamic design allows for easy installation

and full operation flexibility.

1/4 inch quick disconnect terminations
Shock mount assemblies to minimize damage
AC voltmeter and ammeter
Phase selector switch
Frequency meter: 45-65hz
Optional hourmeter; DC Voltmeter;

DC ammeter

First-out fault shutdown and indication

(AutoStart models only) of low oil pressure,
high temperature and auxiliary inputs

Inputs can be from engine-mounted fault

switches or panel-mounted SWICHGAGE

®

instruments.

Magnetic pickup or generator AC speed

sensing (AutoStart models only). For automat-
ic crank release and overspeed fault shutdown.
Speed calibration is automatic–adjustment free.
Additional switch inputs allow optional remote
control of crank disconnect and overspeed fault.

Generator AC Hz meter output: 0-1 mA.
User-friendly: Well-thought-out routine for

faster and easier set up.

Interfaces with existing equipment: functions

seamlessly with many other Murphy instru-
ments and controls (AutoStart models only).

Specifications

Pressure Gage: 100°psi (680 kPa) [7 bar]

Mechanical Gage Pressure Connection: 1/8” NPT.

Electric Gage Pressure Connection: 2-wire.

Temperature Gage: 0-250°F (121°C)

Mechanical Gage Temperature Connection: 12ft.

(3.67 m) capillary tubing and sensing bulb.

Electric Gage Temperature Connection: 2-wire.

Enclosure: 16 Ga CRS powder coated.
Optional NEMA 4X Type Enclosure:

Water and dust tight indoor/outdoor enclosure
intended to protect enclosed equipment against
splashing, seepage, falling or hose-directed
water and severe external condensation.

AC Meters: AC ammeter and an AC voltmeter

and a frequency meter are standard features.
Ranges must be specified.

Single or Three Phase: Specify.
Control Method: may be specified:

- AS3000 Autostart automatic controller or
- 518APH Annunciator control method.
NOTE:

Autostart method is highly recommended.

DC Voltage:

12 or 24 volt DC voltage must be specified.

MGC2000

New Dynamic Design Allows for

Easy Installation and Full Operation

Flexibility

Features Murphy’s AS3000 Engine/

Generator Controller

User-Friendly, Well Thought-out

Routine for Faster/Easier Setup

AS3000 Autostart

Generator Controller

Voltmeter

Hourmeter

Pressure Gage

Temperature Gage

Frequency Meter

1 - 3 Phase

Selector Switch

16 ga CRS Enclosure,

NEMA 4 Optional

AC Ammeter

AC Voltmeter

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Hinges for front-opening door option shown in shaded areas.; Mounting Pattern; Standard Enclosure Dimensions (all Models)

Power supply: • Continuous voltage range: 8-35 VDC• Brown out voltage < 5 VDC for 2 secs (recovery to 8V)• Blackout voltage: 0V for 50mS (from 10V, recovery to 5V)• Overvoltage withstand: 50 VDC for 5 seconds (to SAEJ1810 load dump immunity • Reverse voltage withstand: 100 VDC continuousCurrent c...

Page 3 - these two instruments can be selected in any combination.; MOUNTING; NEMA 4X Type Enclosure Dimensions

• DC Voltmeter*• DC Ammeter*• Hourmeter*• Relays. 4 relays, wired for Preheat, Crank, Fuel, and Common Alarm• Keyswitch• Phase select switch, standard for 3-phase units, optional for single- phase units. • Emergency stop switch• NEMA-4X enclosure• Quick disconnect connectors• Hinged front panel• Mag...

Page 4 - Accessories and Replacement Parts; Off-Equipment Mounting Kit; Description; Warranty; F W

MGC-02029B page 4 of 4 How to Order the MGC2000 Phases 1 = Single Phase3 = Three Phase Base ModelMGC2000 = Mechanical Gages MGC2000E = Electric Gages Controller A = AutostartM = Manual DC Voltage 12 = 12 VDC24 = 24 VDC AC Voltmeter 300, 600600D = 600/300 Dual Scale Options AM = DC Ammeter (1) VM = D...