  • Page 2 – Crank Disconnect Relay; Figure 1; illustrates the use of a low-current pilot relay to; Overspeed and Underspeed Relay; Figure 2; MOUNTING DIMENSIONS; Align the plastic standoffs on the HD9063 with the 4 mounting; Mounting; RELAY FUNCTIONS
  • Page 3 – PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF”; MAGNETIC PICKUP INSTALLATION; Magnetic Pickup Installation; Drill and tap a hole in the flywheel housing (See; Gap Adjustment; See; Murphy Magnetic Pickup Specifications Chart; WIRING; THREAD; GAP; Figure 3
  • Page 4 – ADJUSTING THE SPEED SWITCH; Crank Disconnect Set Point Adjustment; VERSPEED; highest; NDERSPEED; lowest; Figure 6; Warranty
Loading the manual

HD-96044N page 1 of 4

Installation and Operation Instructions for
Dual Set Point Speed Switch

HD9063 Series

HD-96044N

Revised 03-01

Section 20

(

00-02-0179)

Please read the following information before installing

.

A visual inspection of this product for damage during shipping is recommended

before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to NEC and local codes.

GENERAL INFORMATION

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

Disconnect all electrical power to the machine.

Make sure the machine cannot operate during installation.

Follow all safety warnings of the machine manufacturer.

Read and follow all installation instructions.

Description

The HD9063 Series is a unitized two set point speed switch with
SPDT relay outputs. HD9063 is a PC-board configuration with
standoffs for mounting in a control panel or cabinet.

Models are available for crank disconnect/overspeed and for
underspeed/overspeed applications. Trip points can be field
adjusted on all models. LED’s next to the set point potentiometers
indicate that the trip point has been reached and the relay(s) have
operated. An overspeed test circuit is built-in; it will actuate the
output relay at a point below actual overspeed set point.

The

HD9063

can disconnect the starter on automatic start engine

applications and shutdown the engine if an overspeed situation
occurs. Re-engagement of the starter is inhibited until RPM
returns virtually to zero.

HD9063-USOS

models allow operation of control circuits

according to the speed of the driver or as a pre-alarm.
Two separate adjustable speed switches are included on one
common board.

Specifications

Power Supply:

Voltage:

8-30 VDC

Maximum Current:

150 mA

Frequency Signal:

Voltage, Magnetic Pickup Signal Models

• Minimum:

0.35 Vrms

• Maximum:

60 Vrms

Maximum Current, Magnetic Pickup Signal Models:

4.8 µA.

Adjustment Range, Magnetic Pickup Signal Models

• HD9063 Model

Crank Disconnect:

250-6,000 Hz

Overspeed:

1,100-10,000 Hz

• HD9063-USOS Model

Underspeed:

200-5,800 Hz

Overspeed:

1,100-10,000 Hz

Reset Differential, Magnetic Pickup Signal Models

• HD9063 Model

Crank Disconnect:

Dropout 160 Hz ± 5%

Overspeed:

200 Hz Differential

• HD9063-USOS Model

Underspeed:

+5% of Set point Differential

Overspeed:

155 Hz ± 10% Differential

Output:

Relay Contact, SPDT, Resistive Load:

(2) 5 A, 30 VDC

Adjustment:

(2) 270°–turn potentiometer

Temperature Range:

14 to 158°F (-10 to 70°C)

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Crank Disconnect Relay; Figure 1; illustrates the use of a low-current pilot relay to; Overspeed and Underspeed Relay; Figure 2; MOUNTING DIMENSIONS; Align the plastic standoffs on the HD9063 with the 4 mounting; Mounting; RELAY FUNCTIONS

HD-96044N page 2 of 4 Crank Disconnect Relay An understanding of the crank disconnect function for your par-ticular system is critical to speed switch installation. It is alsoimportant to consider the 5 A current limitation of K1 relay con-tacts. Figure 1 illustrates the use of a low-current pilot r...

Page 3 - PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF”; MAGNETIC PICKUP INSTALLATION; Magnetic Pickup Installation; Drill and tap a hole in the flywheel housing (See; Gap Adjustment; See; Murphy Magnetic Pickup Specifications Chart; WIRING; THREAD; GAP; Figure 3

HD-96044N page 3 of 4 CAUTION: PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF” MAGNETIC PICKUP INSTALLATION A magnetic pickup is an AC generator. It is normally installedinto the flywheel housing of an internal combustion engine, sothat the starter ring gear acts upon it to generate a volta...

Page 4 - ADJUSTING THE SPEED SWITCH; Crank Disconnect Set Point Adjustment; VERSPEED; highest; NDERSPEED; lowest; Figure 6; Warranty

HD-96044N page 4 of 4 ADJUSTING THE SPEED SWITCH Adjustment of the Dual Set point Speed Switch is performedwhen the system is otherwise operational in all respects.See Figure 6 for location of Crank Disconnect, Underspeed and Overspeed potentiometers. Crank Disconnect Set Point Adjustment 1. If engi...