Mitsubishi VS-50501- Manual
Mitsubishi VS-50501– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Incorporated Items; Part names
- Page 3 – External dimensions/weight; General specifications and Installation; Installation Location
- Page 4 – Connection of power supply connector; FX; Connection to input/output connector
- Page 5 – Connection to input/output terminal block
- Page 7 – Cautions in input and output wiring
- Page 8 – Use output contacts of the PLC in the common mode.; Terminal Layout; Main units; The I/O wiring is different in the FX; Warranty; For safe use
FX
3UC
(D, DS, DSS) SERIES
PROGRAMMABLE CONTROLLERS
HARDWARE MANUAL
This manual describes the part names, dimensions, mounting,
cabling and specifications for the product. This manual is extracted
from FX
3UC
(D,DS,DSS) Series User's Manual - Hardware Edition.
Refer to FX
3UC
Series User's Manual - Hardware Edition details.
Before use, read this manual and manuals of relevant products fully
to acquire proficiency in the handling and operating the product.
Make sure to learn all the product information, safety information,
and precautions.
And, store this manual in a safe place so that it can be taken out and
read whenever necessary. Always forward it to the end user.
Registration
The company name and the product name to be described in this
ma nu al are t he re gis t er ed t r ad ema r k s or t r ad ema r k s o f ea ch
company.
Effective April 2014
Specifications are subject to change without notice.
© 2013 Mitsubishi Electric Corporation
Safety Precaution
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and
.
Depending on the circumstances, procedures indicated by
may also cause severe injury.
It is important to follow all precautions for personal safety.
Manual Number
JY997D50501
Revision
B
Date
April 2014
Indicates that incorrect handling may cause
hazardous conditions, resulting in death or
severe injury.
Indicates that incorrect handling may cause
hazardous conditions, resulting in medium or
slight personal injury or physical damage.
STARTUP AND
MAINTENANCE
PRECAUTIONS
Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
Before cleaning or retightening terminals, cut off all phases of
the power supply externally.
Failure to do so may cause electric shock.
Before modifying or disrupting the program in operation or
running the PLC, carefully read through this manual and the
associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents.
STARTUP AND
MAINTENANCE
PRECAUTIONS
Do not change the program in the PLC from two or more
peripheral equipment devices at the same time. (i.e. from a
programming tool and a GOT)
Doing so may cause destruction or malfunction of the PLC
program.
Use the battery for memory backup correctly in FX
3UC
Series
User's Manual - Hardware Edition.
- Use the battery only for the specified purpose.
- Connect the battery correctly.
- Do not charge, disassemble, heat, put in fire, short-circuit,
connect reversely, weld, swallow or burn the battery, or apply
excessive forces (vibration, impact, drop, etc.) to the battery.
- Do not store or use the battery at high temperatures or
expose to direct sunlight.
- Do not expose to water, bring near fire or touch liquid
leakage or other contents directly.
- Incorrect handling of the battery may cause heat excessive
generation, bursting, ignition, liquid leakage or deformation,
and lead to injury, fire or failures and malfunctions of facilities
and other equipment.
STARTUP AND
MAINTENANCE
PRECAUTIONS
Turn off the power to the PLC before attaching or detaching the
memory cassette. If the memory cassette is attached or
detached while the PLC's power is on, the data in the memory
may be destroyed, or the memory cassette may be damaged.
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
Turn off the power to the PLC before connecting or
disconnecting any extension cable.
Failure to do so may cause equipment failures or malfunctions.
Turn off the power to the PLC before attaching or detaching the
following devices.
Failure to do so may cause equipment failures or malfunctions.
- Peripheral devices, extension units/blocks, connector
conversion adapter, extension power supply units, special
adapters, and FX Series terminal blocks.
- Battery and memory cassettes
DISPOSAL
PRECAUTIONS
Please contact a certified electronic waste disposal company
for the environmentally safe recycling and disposal of your
device.
When disposing of batteries, separate them from other waste
according to local regulations.
(For details of the Battery Directive in EU countries, refer to
FX
3UC
Series User's Manual - Hardware Edition.)
TRANSPORTATION
AND STORAGE
PRECAUTIONS
Before transporting the PLC, turn on the power to the PLC to
check that the BAT LED is off, and check the battery life.
If the PLC is transported with the BAT LED on or the battery
exhausted, the battery-backed data may be unstable during
transportation.
The PLC is a precision instrument. During transportation, avoid
impacts larger than those specified in Section 2.1. Failure to do
so may cause failures in the PLC.
After transportation, verify the operations of the PLC.
Associated manuals
Associated manuals
FX
3UC
(D, DS, DSS) Series PLC (main unit) comes with this
document (hardware manual).
For a detailed explanation of the FX
3UC
Series hardware and
information on instructions for PLC programming and special
extension unit/block, refer to the relevant documents.
Certification of UL, cUL standards
FX
3UC
series main units, FX
3U
series special adapter, extension
power supply unit and FX
2N
/FX
2NC
series input/output extension
blocks supporting UL, cUL standards are as follows:
UL, cUL file number: E95239
Models:
MELSEC FX
3U(C)
series manufactured
FX
3UC
-
MT/D
FX
3UC
-
MT/DSS
Where
indicates: 16, 32, 64, 96
FX
3UC
-16MR/D-T
FX
3UC
-16MR/DS-T
FX
3U
-232ADP(-MB)
FX
3U
-485ADP(-MB)
FX
3U
-CF-ADP
FX
3U
-ENET-ADP
FX
3U
-4AD-ADP
FX
3U
-4DA-ADP
FX
3U
-3A-ADP
FX
3U
-4AD-PT-ADP
FX
3U
-4AD-PTW-ADP FX
3U
-4AD-PNK-ADP
FX
3U
-4AD-TC-ADP
FX
3UC
-1PS-5V
Models:
MELSEC FX
2NC
series manufactured
FX
2NC
-16EX(-DS)
FX
2NC
-32EX(-DS)
FX
2NC
-16EYT(-DSS) FX
2NC
-32EYT(-DSS)
FX
2NC
-16EX-T(-DS)
FX
2NC
-16EYR-T(-DS)
Models:
MELSEC FX
2N
series manufactured
FX
2N
-8ER-ES/UL
FX
2N
-8EX-ES/UL
FX
2N
-8EYR-ES/UL
FX
2N
-8EYR-S-ES/UL
FX
2N
-8EYT-ESS/UL
FX
2N
-8EX-UA1/UL
FX
2N
-16EX-ES/UL
FX
2N
-16EYR-ES/UL
FX
2N
-16EYT-ESS/UL FX
2N
-16EYS
Compliance with EC directive (CE Marking)
This document does not guarantee that a mechanical system
including this product will comply with the following standards.
Compliance to EMC directive and LVD directive of the entire
mechanical system should be checked by the user / manufacturer.
For more details please contact the local Mitsubishi Electric sales
site.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct
testing (of the identified standards below) and design analysis
(through the creation of a technical construction file) to the European
Directive for Electromagnetic Compatibility (2004/108/EC) when
used as directed by the appropriate documentation.
Attention
This product is designed for use in industrial applications.
Note
Manufactured by:
Mitsubishi Electric Corporation
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan
Manufactured at:
Mitsubishi Electric Corporation Himeji Works
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan
Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
Type:
Programmable Controller (Open Type Equipment)
Models:
MELSEC FX
3U(C)
series and FX
2NC
series
manufactured
from May 1st, 2005
FX
3U
-FLROM-16
FX
3U
-FLROM-64L
from June 1st, 2005
FX
3U
-232ADP
FX
3U
-485ADP
FX
3U
-4AD-ADP
FX
3U
-4DA-ADP
FX
3U
-4AD-PT-ADP FX
3U
-4AD-TC-ADP
FX
3U
-FLROM-64
TRANSPORTATION
AND STORAGE
PRECAUTIONS
When transporting lithium batteries, follow required
transportation regulations.
(For details of the regulated products, refer to FX
3UC
Series
User's Manual - Hardware Edition.)
How to obtain manuals
For the necessary product manuals or documents, consult with
your local Mitsubishi Electric representative.
Manual name
Manual No.
Description
FX
3UC
Series
User's Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains FX
3UC
Series
PLC specification details
for I/O, wiring, installation,
and maintenance.
FX
3S
/FX
3G
/FX
3GC
/
FX
3U
/FX
3UC
Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC
programming for basic/
applied instructions STL/
SFC programming and
devices.
MELSEC-Q/L/F
Structured
Programming Manual
(Fundamentals)
SH-080782
MODEL CODE:
13JW06
Programming methods,
specifications, functions,
etc. required to create
structured programs.
FXCPU Structured
Programming Manual
[Device & Common]
JY997D26001
MODEL CODE:
09R925
Devices, parameters, etc.
provided in structured
projects of GX Works2.
FXCPU Structured
Programming Manual
[Basic & Applied
Instruction]
JY997D34701
MODEL CODE:
09R926
Sequence instructions
provided in structured
projects of GX Works2.
FXCPU Structured
Programming Manual
[Application
Functions]
JY997D34801
MODEL CODE:
09R927
Application functions
provided in structured
projects of GX Works2.
FX Series User’s
Manual - Data
Communication
Edition
JY997D16901
MODEL CODE:
09R715
Explains N:N link, parallel
link, computer link, no
protocol communication
by RS instructions/FX
2N
-
232IF.
FX
3S
/FX
3G
/FX
3GC
/
FX
3U
/FX
3UC
Series
User's Manual
- Analog Control
Edition
JY997D16701
MODEL CODE:
09R619
Describes specifications
for analog control and
programming methods for
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/
FX
3UC
Series PLC.
FX
3S
/FX
3G
/FX
3GC
/
FX
3U
/FX
3UC
Series
User's Manual
- Positioning Control
Edition
JY997D16801
MODEL CODE:
09R620
Explains the specifications
for positioning control of
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/
FX
3UC
Series and
programming procedures
JY997D50501B
Side
B
Side
A
Side
B
JAPANESE
ENGLISH
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
from April 1st, 2007 FX 3U -232ADP-MB FX 3U -485ADP-MB from September 1st, 2007 FX 3UC - MT/D FX 3UC - MT/DSS Where indicates: 16, 32, 64, 96 from October 1st, 2007 FX 3UC -1PS-5V FX 2NC - EX FX 2NC - EYT FX 2NC - EX-DS FX 2NC - EYT-DSS Where indicates: 16, 32 FX 2NC -16EX-T ...
1.2 External dimensions/weight Main units (Connector type) Main units (Terminal block type) FX 2NC input/output extension blocks (Connector type) FX 2NC input/output extension blocks (Terminal block type) No. Name [1] Memory cassette dummy cover [2] Special adapter connecting hooks [3] Special adapt...
Space in enclosure Extension devices can be connected on the left and right sides of thePLC main unit.If you intend to add extension devices in the future, keep extra spaceon the left and right sides open. 2.3 Procedures for installing to and detaching from DIN rail The main unit can be installed on...