Page 2 - CONTENTS; REFRIGERANT PIPING INSTALLATION/SERVICING MANUAL
CONTENTS 1 GENERAL INFORMATION ............................................................................... 1 1.1 Specific features ........................................................................................ 1 1.2 How to read the model name ..............................................
Page 3 - GENERAL INFORMATION; Specific features; Connectable indoor capacity; How to read the model name; Inverter and Heat pump type
- 1 - 1 GENERAL INFORMATION 1.1 Specific features (1) The long piping makes the location of the inside and units flexible. ¡ No need for additional charge of refrigerant : 40 type · 30m, 45 type · 20m, 48 type · 40m, 60 type · 30m, 80 type · 40m ¡ Maximum piping length : 40 type · 30m, 45 type · 30m...
Page 4 - SELECTION DATA; Indoor unit
- 2 - 2 SELECTION DATA 2.1 Specifications (1) Indoor unit Models SKM20ZF-S, 22ZF-S, 25ZF-S Item Models SKM20ZF-S SKM22ZF-S SKM25ZF-S Cooling capacity W 2000 2200 2500 Heating capacity W 3000 3200 3400 Noise level Cooling Hi : 37 Me : 30 Lo : 23 dB Hi : 53 Heating Hi : 39 Me : 33 Lo : 27 Hi : 55 Exte...
Page 6 - Models
- 4 - Item Models STM25ZF-S STM35ZF-S STM50ZF-S STM60ZF-S Cooling capacity W 2500 3500 5000 6000 Heating capacity W 3400 4500 5800 6800 Noise level Cooling 35 38 40 47 dB 51 54 56 63 Heating 35 38 40 47 51 54 56 63 Exterior dimensions Main unit 248 × 570 × 570 Height × Width × Depth Panel mm 35 × 70...
Page 8 - Outdoor unit
- 6 - Item Models SCM40ZF-S SCM45ZF-S Cooling capacity W 4000 (1900 ~ 4900) 4500 (700 ~ 5600) Heating capacity W 5000 (1300 ~ 5200) 5600 (700 ~ 6800) Power source 1 Phase 220/230/240V 50Hz Power consumption Cooling W 970 (470 ~ 1470) 1390 (200 ~ 2160) Heating 1150 (450 ~ 1260) 1540 (200 ~ 2340) Runn...
Page 11 - capacity will be proportionally distributed.; Heating
- 9 - Model SCM40ZF-S (a) Heating A room B room Min. Standard Max. Power consumption (W) Standard current (A) Room cooling capacity (kW) Total capacity (kW) Min. Max. 220V 230V 240V Indoor unit combination Cooling capacity (kW) Standard room 2 room 1 20 3.0 – 1.3 3.0 3.9 450 770 1120 3.5 3.4 3.2 22 ...
Page 14 - Cooling
- 12 - Model SCM48ZF-S (b) Cooling A room B room C room Min. Standard Max. Power consumption (W) Standard current (A) Room cooling capacity (kW) Total capacity (kW) Min. Max. 220V 230V 240V Indoor unit combination Cooling capacity (kW) Standard room 3 room 2 room 1 20 2.0 – – 1.1 2.0 2.2 200 640 800...
Page 28 - VIEW A; Remote control; Exterior dimensions
- 26 - VIEW A 45 14.5 60 788 5 60 45 815 A 250 117.5 580 117.5 148.5 216.5 216.5 8.2 44.5 236.1 5.7 450 450 67.5 42.7 47.2 175 44.5 216.5 216.5 148.5 53.5 Piping for Gas Drain hose 540 (ø16) Piping for Liquid 465.1 (ø6.35) Piping hole (ø65) Piping hole (ø65) ( ) 20,22,25,28,35: ø9.52 50: ø12.7 397.1...
Page 31 - Discharge
- 29 - 2.4 Piping system Model SCM40ZF-S Outdoor unit Indoor unit Sensor Sensor (Th I -R 2 ) (Th I -R 1 ) (Th I -A) Sensor Sensor (Th O -C) Check joint Check joint Check joint Sensor (Th O -D) Sensor (Th O -A) Sensor (Th O -R) Heat exchanger Heat exchanger Liquid line Gas line (ø6.35) (ø6.35) (ø9.52...
Page 34 - Gas line
- 32 - Model SCM60ZF-S Gas line Liquid line (ø 6.35) (ø 6.35) (ø 6.35) EEVA Strainer EEVB EEVC Service valve (Gas) Outdoor Unit Indoor Unit Sensor (Th I- R 2 ) Heat exchanger Sensor (Th I-A ) Sensor (Th I-R1 ) Sensor (Th O-D ) Sensor (Th O-A ) Accumlator Sensor (Th o-C ) Service valve (Liquid) Elect...
Page 36 - obtained in the following way.; Net capacity = Capacity shown on specification
- 34 - 2.5 Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling and ...
Page 37 - outdoor heat exchanger.; Air inlet temperature of
- 35 - (2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor units. (3) Correction relative to frosting on outdoor heat exc...
Page 38 - ELECTRICAL DATA; Meaning of marks; Parts name; Electrical wiring
- 36 - 3 ELECTRICAL DATA Meaning of marks • Outdoor Unit • Indoor Unit FM I CF I SM Tr ZNR F Parts name Fan motor Capacitor (for FM I ) Flap motor Transformer Varistor Fuse Symbol DM FS Th I -A Th I -R 1 Th I -R 2 Parts name Drain motor Float switch Sensor (room temp.) Sensor (indoor H.X temp.) Sens...
Page 39 - SM; Color symbol
- 37 - HEATEXCHANGER Power line(Outdoor unit) CNM F (250V 3.15A) Printed circuit board 1 52C-4 N ~ ~ ZNR WH 2/N 3 SM FM I BK RD WH Y/GN RD 1 3 4 5 6 WH BL CNU YL BK TB RD J Y/G G BK CNE CNG CNF Back upswitch Th I -A Th I -R 2 Th I -R 1 Display Wireless R-Amp Black BrownRedWhite Yellow/Green BK BRRDW...
Page 45 - HI POWER; Indication section; OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER; Operation control function by remote control switch
- 43 - LO MED HI AUTO HI POWER ECONO ON OFF AM PM FAN SPEED button Each time the button is pushed, the indi- cator is switched over in turn. • The above illustration shows all controls, but in practiceonly the relevant parts are shown. OPERATION MODE select button Each time the button is pushed, the...
Page 46 - area are shown in the figure for the sake of explanation.; Pull the cover downward to open it.
- 44 - Weekly timer display Displays the settings of the weekly timer. [Vent Indicator] Indicates operation in the Ventilation mode. Operation/Stop switch This switch is used to operate and stop the air conditioning system. Press the switch once to operate the system and press it once again to stop ...
Page 47 - Unit indication section
- 45 - RUN (HOT KEEP) light (green) • Illuminates during operation. • Blinks at air flow stop due to the ‘HOT KEEP’. ECONO light (orange) Illuminates during ECONOMY operation. TIMER light (yellow) Illuminates during TIMER operation. HI POWER light (green) Illuminates during HIGH POWER operation. Mod...
Page 48 - When the drain motor has run for 5 minutes.
- 46 - ¡ SRRM model 4.2 Unit ON/OFF button When the remote control batteries become weak, or if the remote control is lost or malfunctioning, this button may be used to turn the unit on and off. (1) Operation Push the button once to place the unit in the automatic mode. Push it once more to turn the...
Page 49 - Power blackout auto restart function; Air scroll
- 47 - Thick line : Rapid movement Thin line : Slow movement Stops for approximately5 seconds in thehorizontal position. Stops for approximately5 seconds in thisposition. Thick line : Rapid movement Thin line : Slow movement Thick line : moves quickly Thin line : moves slowly Stops at this position ...
Page 50 - Memory flap; Recommendable stopping angle of the flap; SKM model; Flap moves in upward and downward directions continuously.; Comfortable timer setting; Cooling operation; Summary; Mode switching; coefficient to the indoor unit command speed.; SKM model
- 48 - (2) Memory flap While the flap is operating if the AIRFLOW button is pushed once, it stops swinging at an angle. As this angle is memorized in the microcomputer, the flap will be automatically set to the angle when next operation is started. ¡ Recommendable stopping angle of the flap Horizont...
Page 53 - Heating operation
- 51 - (2) Mode switching Within the selected mode, the unit operates using the values shown below which were obtained by multiplying a conversion coefficient to the indoor unit command speed. (a) SCM40ZF-S, 45ZF-S ◆ SKM model Model (Indoor) Operation Mode Automatic High Medium Low Hi power Econo 12...
Page 55 - Hot keep operation; indoor unit heat exchanger (detected with Th; Operation of major functional components in heating mode; C or less for 3 continuous minutes after 37; ) During defrosting acceleration
- 53 - (4) Hot keep operation If the hot keep operation is selected during the heating operation, the indoor fan is controlled based on the temperature of the indoor unit heat exchanger (detected with Th I -R 1 ) Functional components Operation Command speed Indoor unit fan Compressor Outdoor unit f...
Page 56 - ) Operation of function component in defrosting
- 54 - F1 F1 R2rps Decision rps 300 pulse EEV control Opening in relation to conditions R1rps Decision rps 0rps Outdoor unit speed After compressor software has started According to rps Outdoor unit fan OFF ON 4-way valve OFF 470 pulse fully opened 250 pulse Electronic expansionvalve EEV(Operating u...
Page 57 - ) Conditions for finishing defrosting; Outline of automatic operation; Determination of operation mode
- 55 - 4) Conditions for finishing defrosting When any of the following conditions is met, the defrosting finishing operation will start. 1 When the temperature of the outdoor heat exchanger sensor (Tho-R) is 20 ° C or more. 2 When 10 minutes has passed after the start of defrosting. 3 When the temp...
Page 58 - Determining the operating mode; Example of operating pattern
- 56 - 4.10 Determining the operating mode The cooling and heating operating modes are the remote control switch mode that have been previously determined. If a mode differing from these is selected after this, the selected mode will appear in the display of the remote control, but only the fan will...
Page 60 - Control and protection functions; Frost prevention for indoor heat exchanger
- 58 - 4.13 Control and protection functions (1) Frost prevention for indoor heat exchanger (During cooling or dehumidifying) ⽧ < I > (a) Operating condition After the indoor command speed is other than 0 rps for 9 minutes, when the indoor heat exchanger (Th I -R 1 ) is 2 ° C or lower for 1min...
Page 62 - Freezing cycle system protective control; Crankcase heater
- 60 - (5) Freezing cycle system protective control (a) Operating conditions: When both of following conditions have continued for more than 5 minutes later than 5 minutes after the start of operation. 1) Indoor command speed is higher than 0 rps 2) During cooling, dehumidifying: Indoor heat exchang...
Page 63 - II
- 61 - < II > (a) Operating conditions: When the outdoor air temperature sensor (Th O -A) is 22 ° C or lower continues for 30 seconds while decision speed is other than 0 rps. (b) Detail of operation: 1 The lower limit of decision speed is set to B (or D) rps and even if the speed becomes lowe...
Page 64 - Indoor unit side
- 62 - (13) Current safe control (a) When converter in port current is detected at the current sensor (CT) and it exceeds the set amperage, the decision speed is reduced. This is rechecked after one second and if it still exceeds the set amperage, the decision speed is reduced 2 rps. (b) If the deci...
Page 65 - (17) Power transistor overheat protection; (18) Serial transmission abnormality protection
- 63 - (17) Power transistor overheat protection (a) Purpose: In order to prevent the power transistor overheating during operation, faulty controller operations, deterioration, damage and so on occurs. (b) Detail of operation: 1 Power transistor sensor temperature => 110 ° C The compressor is st...
Page 66 - compressor lock has occurred and the compressor is stopped.; (20) Discharge pipe sensor disconnection protection control; When the decision speed is other than 0 rps.
- 64 - (19) Compressor lock If the motor for the compressor does not turn 1/12 revolution 0.044 seconds after it has been started, it is determined that a compressor lock has occurred and the compressor is stopped. (20) Discharge pipe sensor disconnection protection control (a) When the decision spe...
Page 68 - WARNING; When working at high place, be careful not to drop tools.; CAUTION
- 66 - 5 APPLICATION DATA SAFETY PRECAUTIONS ¡ Please read these “Safety Precautions” first then accurately execute the installation work. ¡ Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are related to the strong possibility...
Page 69 - Caution for installation; gap of at least 3mm in each pole.; Installation of indoor unit; Drill a hole with a 65 whole
- 67 - 5.1 Installation of indoor unit (1) Wall mounted type (SKM) (a) Caution for installation 1) The system should be applied to places as households, residences and the like. 2) The equipment shall be installed in accordance with national wiring regulations. 3) The connection to the fixed wiring ...
Page 70 - Cautions when piping from the left and the rear center of the unit; Left Side Piping; Harmonized cable type; ) Shaping the pipe and drain hose
- 68 - 3) Mounting of interconnecting wires (Field wiring) a) Remove the lid.b) Remove the terminal block cover.c) Connect the connection wire securely to the terminal block. Cautions when piping from the left and the rear center of the unit Pipe Drain hose Left Side Piping Left rear piping Right re...
Page 71 - Too high
- 69 - ¡ Pour water in the drain pan below the heat exchanger and confirm that the water is drained outside. ¡ If the extension drain hose is indoors, make sure it is insulated using a shielding pipe (not supplied). 5) Securing the Indoor Unit to the Installation Board Drainage Too high It curves li...
Page 72 - PANEL; Drilling of holes in the wall and fixture of sleeve; Mounting of interconnecting wires (Field wiring)
- 70 - (b) Installation of indoor unit 1) Installation dimensions To be installed at site Ceiling opening 660 (For conventional ceiling) Hanging bolt pitch 530 Control box Drain hose(accessory) Inspection port(For conventional ceiling) PANEL Air outlet Air intake Hanging fixture 45 or more 197 137 1...
Page 75 - C. Attaching the panel; Remove the level gauge before you attach the panel.
- 73 - C. Attaching the panel 1) <Accessory items> (It is attached to the panel.) a) Make sure that the unit main body is positioned at the correct height and the opening on the ceiling is made to the correct dimensions with the level gauge supplied with the main body. Remove the level gauge b...
Page 76 - ) A location that allows room for maintenance.; Chain; Plan; Front
- 74 - k) Attach two chains to the intake grille with two screws. [ Figure 7]l) Replace the corner panels. Please also close a chain with a screw together then. m) Close the intake grille. (3) Ducted type (SRRM) (a) Caution for installation Install the unit with the customer's consent at location th...
Page 78 - NOTE; Installation of remote control; Mounting method of battery
- 76 - 6) Installing the Main Unit • Attach the washers and nuts to the ceiling hanging bolts. • Attach the hanging tool to the above nuts, and tighten the nuts. • If it is not leveled, the float switch may malfunction or may not start. 8) Connecting the Drain Hose • Insert the drain hose as far as ...
Page 79 - Installation of outdoor unit; Selection of installation location
- 77 - (2) Installation of outdoor unit (a) Make sure that sufficient space for installation and service is secured. (b) Fix the leg sections of the unit on a firm base which will not play. Attach cushion pads, etc. between the unit and the mounting fixtures not to transmit vibration to the building...
Page 80 - Electrical wiring; Connecting the outside/inside crossover wires; CENELEC code for cables required field cables.; Connection of the power lines; An earth leakage breaker and a circuit breaker must be installed.
- 78 - 5.4 Electrical wiring [POWER SUPPLY CODE] CENELEC code for cables required field cables. H05RNR3G4.0 (e) After connecting the power supply wires, make sure to secure the wires with wiring clamps. (2) Connecting the outside/inside crossover wires (a) Ensure that crossover wiring is matched wit...
Page 81 - Refrigerant Piping; Limit; the outdoor units are as shown below.; The diameter of the refrigerant pipe:; Connection of refrigerant piping; [Examples of use of variable diameter joints]; A dimensions
- 79 - 5.5 Refrigerant Piping (1) Limit The maximum permissible length of the refrigerant pipes for the outdoor units, and the maximum permissible height difference for the outdoor units are as shown below. * If the total length for all the rooms exceeds the length of chargeless refrigerant pipe, ad...
Page 82 - Additional refrigerant charge; Air purging; Conduct air purging for all connected indoor units.; Procedure; Remove the charge hose from service port.
- 80 - (4) Additional refrigerant charge ¡ SCM40, 48 typeAdditional refrigerant charge is not required at all ¡ SCM45, 60, 80 type (a) When the total refrigerant pipe length for all the rooms exceeds the length of the uncharged pipe, additional refrigerant is required. (b) For this multi type room a...
Page 84 - Modifying the indoor unit’s printed circuit board
- 82 - D unit D CB A C unit B unit A unit Outdoor unit Indoor unit Indoor unit PipingWiring D unit D CB A C unit B unit A unit Outdoor unit Z Y X Z Y X Z Y X Z Y X Z Y X Z Y X Z Y X Indoor unit (1)Address [0] Red White Black Remote controller Indoor unit (2)Address [1] Indoor unit (16)Address [F] Re...
Page 85 - Installation of wired remote control (Optional parts); Black wire; Precation in Extending the Remote control cord; The shielded wire should be grounded at one side only.
- 83 - 2) Recessed fitting a) The Electrical box and remote control (shield wire must be use in case of extension) are first embedded. (2) Installation of wired remote control (Optional parts) (a) Selection of installation location Avoid the following locations1) Direct sunlight.2) Close to heating ...
Page 86 - Setting functions using the wired remote control; installation manual and set to your desired setting.
- 84 - (3) Setting functions using the wired remote control (a) The default settings of this unit's functions are as follows: If you want to charge a setting, follow the procedure found in the installation manual and set to your desired setting. For the method of setting, please refer to the install...
Page 87 - AUTO RUN SET; FUNCTION; AUTO RUN SET Ó is selected.
- 85 - (b) Function setting method 1) Stop the air conditioner 2) Press the SET and MODE buttons simultaneously for 3 seconds or longer. The screen display will be switched as follows: “ SELECT ITEM” “ SET" “FUNCTION SET ” 3) Press the SET button. The unit will enter the function setting mode. T...
Page 88 - EXTERNAL INPUT SET” is selected.; EXTERNAL INPUT SET; LEVEL INPUT
- 86 - When “I/U FUNCTION ” is selected. 1 The screen display will be switched as follows:“ I/U SELECT” “ SET” “I/U No.00” (blinking) 2 Press either or button. Select the indoor unit number that you want to change settings. If only one indoor unit is connected, the indoor unitnumber will not charge,...
Page 89 - Changing the remote control’s temperature setting range
- 87 - 12 Function No. A (Example) If the upper limit is set at 28˚C Function Contents B Setting Contents C TEMP RANGE SET DISP CHANGE NO DISP CHANGE Control Contents The remote control’s display and sent data upper limit changes to 28 ° C. The remote control’s display upper limit remains at 30ºC an...
Page 91 - Name
- 89 - (d) Installation procedure 1) Mount the duct for the air inlet grille to the indoor unit using the 10 tapping screws provided. The tapping screws on the drain pan receiver side are also used for mounting the duct for the air inlet grille. They must first be removed and reinstalled after the d...
Page 92 - Duct joint for air outlet plate; Rear inlet filter set
- 90 - Indoor unit (Flat surface drawing) 215 310 215 125 230 97 455 570 310 130 130 97 Round duct connection port 95 95 190 ø 150 (3) Duct joint for air outlet plate (a) Part No. : RFJ22 This duct joint is to be used for the connection of a round duct (ø 150 mm) to an indoor unit. (b) Part list (d)...
Page 93 - Air inlet grille air flow and friction loss characteristics
- 91 - ◆ Air flow and external static pressure characteristics (Heating: Hi) ◆ Air inlet grille air flow and friction loss characteristics (Part No.: RTS12) Air flow (m 3 /min) Pressure loss Pa 2 3 4 5 6 7 8 9 10 30 20 10 0 SRRM50ZE-S SRRM60ZE-S SRRM35ZE-S SRRM25ZE-S ! " " ! " " # $ ...
Page 94 - Control
- 92 - (4) Drain up kit (a) Part No. : RDU12E (b) Accessories (d) Installation of drain up kit 1) Fix the drain up kit on the right side of the inside unit with tap screws. 2) Insert the drain hose fully and securely to the drain sockets of the inside unit and the drain up kit. 3) Connect the drain ...
Page 96 - MAINTENANCE DATA
- 94 - 6 MAINTENANCE DATA 6.1 Trouble shooting (1) Trouble shooting to be performed prior to exchanging PCB, (Printed circuit board) [Common to all models] All the models described in this chapter are controlled by a microcomputer. When providing maintenance service to customers it is necessary to u...
Page 97 - Indication of self diagnosis
- 95 - (2) Indication of self diagnosis Indoor unit indicator Outdoor unit indicator (LED 5) Wired remote control display(optional parts) Description of trouble Cause Conditions of flashing On for 4 sec-onds and off for 4 seconds Outdoor heat exchan-ger sensor error Indoor heat exchanger sensor (1) ...
Page 98 - Inspection procedures corresponding to detail of trouble; Sensor error; S e n s o r t e m p e r a t u r e c h a r a c t e r i s t i c s; Indoor fan motor error
- 96 - (3) Inspection procedures corresponding to detail of trouble Sensor error [Broken sensor wire,connector poor connection] (Shortcircuit) (Broken wire) Is connector connection good? YES YES NO NO Replace PCB. Correct connection. Replace sensor. Is sensor resistance value good? ◆ S e n s o r t e...
Page 101 - Phenomenon observed after shortcircuit, wire breakage on sensor
- 99 - Rotor lock [Compressor defect, outdoorunit circuit defect] Outdoor fan motor error [Defective fan motor, connectorpoor connection, defective PCB] Is connector connection good? YES NO NO Is the output of the outdoor unit’sprinted circuit board normal? Normal NO YES YES Correct connector connec...
Page 102 - FM; CNU; Blue
- 100 - (5) Checking the indoor electrical equipment (a) Indoor unit circuit board check procedure Is there voltage between terminal blocks 1 and 2 ? (AC 220/230/240 V) Indoor electrical components are normal. Is the voltage between terminal blocks 2 and 3 oscillating between DC 0 and 12V? Inspect p...
Page 103 - How to make sure of remote control; Press the reset switch of the remote control.
- 101 - (6) How to make sure of remote control Is remote control normal? YES Again pushingoperating switch Operating the unit? NO Does unit ON/OFFbutton operates? Operating the unit. NO NO YES YES Remote controldefects Abnormality is notfound. LO MED HI AUTO HI POWER ECONO ON OFF AM PM (a) Press the...
Page 105 - CAUTION – HIGH VOLTAGE; Check these points with the power supply on.
- 103 - BK 250V 15A FUSE 1 Phase 220-240V 50Hz Power Source BK L T2 T1 A UNIT EARTH Y/G Y/G 3 2 1 WH N BK WH RD OR OR N_1 P_1 BK RD N_1 P_1 DC-N DC-P PWB3 (CAPACITOR) BK RD CNG PWB1 (MAIN) PWB2 (POWER) A EEV B EEV HEATER CNC CNT CNK CNJ CND CNB FMo 20S L-1 AC.N AC.N AC.L AC.L BL GR BL GR L AF_L2 AF_...
Page 109 - Power transistor inspection procedure
- 107 - Output voltage (ACV) (Example)Self-diagnosis display : Flashes 2 times Measure in this section Operation SW ON 8 ~ 10 sec. 0 1 ◆ Power transistor inspection procedure [Use a tester with a needle indicator for the inspection. (Do not use a digital tester. Check in the AC 300 volt range.)] 1) ...
Page 110 - Evacuation
- 108 - Liquid side Gas side Check joint Service hose Charge hose Vacuumpump Refrigerantcylinder Gaugemanifold 6.2 Servicing (1) Evacuation The evacuation is an procedure to purge impurities ...... noncondensable gas, air, moisture from the refrigerant equipment by using a vacuum pump. Since the ref...
Page 111 - Air Conditioning Industry Association)
- 109 - 7 REFRIGERANT PIPING INSTALLATION/SERVICINGMANUAL FOR AIR CONDITIONERS USING R410A (These materials are extracted from document issued by The Japan Refrigeration and Air Conditioning Industry Association) 7.1 Outline 7.1.1 Refrigerant R410A (1) Adoption of R410A in air conditioners In 1974, ...
Page 112 - Refrigerant piping installation
- 110 - (3) Lubricating oils for R410A As the lubricating oils for R22, mineral oils, alkylbenze synthetic oils, etc. have so far been used. As R410A features less solubility with these conventional lubricating oils such as mineral oils, the lubricating oils tend to stay within the refrigeration cyc...
Page 118 - Fig.5 Prevention of oxidation during brazing
- 116 - Fig.5 Prevention of oxidation during brazing Flow meter Stop valve Reducing valve Piping Rubber plug for sealing From the nitrogen cylinder Nitrogen gas Nitrogen gas M * Cautions during brazing 1 General cautions 1) The brazing strength should be high as required. 2) After operation, airtigh...
Page 121 - Fig.6 Configuration of air purge by vacuum pump; • Be sure to use the vacuum pump, vacuum pump adapter and
- 119 - 7.3.2 New installation work (when using new refrigerant piping) (1) Air purge by vacuum pump and gas leakage inspection (see Fig. 6) a) Connect the charge hose to the outdoor unit. 1 b) Connect the charge hose to the vacuum pump adapter. 2 At this time, keep the control valves in the fully c...
Page 122 - Fig.7 Configuration of additional refrigerant charging
- 120 - f) After charging liquid refrigerant into the air conditioner by closing the charging valve, stop operation by fully closing the gauge manifold’s valve Lo . 2 5 g) Quickly remove the charge hose from the service port. 6 When stopped halfway, refrigerant being cycled will be released. h) Afte...
Page 123 - Refrigerant recharging at servicing; Refrigerant recovery
- 121 - 7.3.6 Refrigerant recharging at servicing When it becomes necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. (For details, see the instruction manual prepared by the equipment manufacturer) 1) Connect the charge hose to the out...
Page 126 - MEMO