Mitsubishi MUY-GE12NA- User Manual

Mitsubishi MUY-GE12NA

Mitsubishi MUY-GE12NA– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

Job Name:

Location:

Date:

Purchaser:

Engineer:

Submitted to:

For

Approval

Unit Designation:

Schedule No.:

Zoning

Cooling*

Rated Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12,000 Btu/h

Minimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,800 Btu/h

SEER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20.5 Btu/h/W

Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .960 W

*

Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB, 67ºF (19ºC) WB; Outdoor: 95ºF

(35ºC) DB, 75ºF (24ºC) WB.

Electrical Requirements

Power Supply . . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz

Breaker Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 A

Voltage

Indoor - Outdoor S1-S2 . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V

Indoor - Outdoor S2-S3 . . . . . . . . . . . . . . . . . . . . . . . . . DC 12-24V

Indoor - Remote Controller . . . . . . . . . . . . . . . . . . . . . . . . . Wireless

OPERATING RANGE

Indoor Intake Air Temp. Outdoor Intake Air Temp.

Cooling

Maximum

90

°

F (32

°

C) DB,

73

°

F (23

°

C) WB

115

°

F (46

°

C) DB

Minimum

67

°

F (19

°

C) DB,

57

°

F (14

°

C) WB

14

°

F (-10

°

C) DB

Indoor Unit

MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A

Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.76 F.L.A.

Airfl ow (Quiet - Lo - Med - Hi - Super Hi)

Cooling . . . . . . . . . . . . . . . . 145 - 170 - 237 - 321 - 399 Dry CFM

109 - 134 - 201 - 286 - 364 Wet CFM

Sound Pressure Level (Quiet - Lo - Med - Hi - Super Hi)

Cooling . . . . . . . . . . . . . . . . . . . . . . . . 19 - 22 - 30 - 37 - 45 dB(A)

DIMENSIONS

UNIT INCHES / MM

W

31-7/16 / 799

D

9-1/8 / 232

H

11-5/8 / 295

Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 lbs. / 10 kg

External Finish . . . . . . . . . . . . . . . . . . . . .Munsell No. 1.0Y 9.2 / 0.2

Field Drainpipe Size O.D. . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm

Remote Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wireless

(Optional Wired Remote Controller PAR-21MAA;

see Data Submittal Sheet)

Outdoor Unit

Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DC Inverter-driven

MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 A

Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.50 F.L.A.

Sound Pressure Level

Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 dB(A)

DIMENSIONS

INCHES / MM

W

31-1/2 / 800

D

11-1/4 / 286

H

21-5/8 / 549

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 lbs. / 35 kg

External Finish . . . . . . . . . . . . . . . . . . . . . . Munsell No. 3Y 7.8 / 1.1

Refrigerant Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R410A

Refrigerant Pipe Size O.D.

Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3/8" / 9.52 mm

Liquid Side. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/4" / 6.35 mm

Max. Refrigerant Pipe Length. . . . . . . . . . . . . . . . . . . . . 65 ft. / 20 m

Max. Refrigerant Pipe Height Difference . . . . . . . . . . . . 40 ft. / 12 m

Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flared

SUBMITTAL DATA: MSY-GE12NA & MUY-GE12NA

12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEMS

OPTIONAL ACCESSORIES

Outdoor Unit

• Drain Socket Assembly (MAC-860DS)

Indoor Unit

• M-NET Control Adapter (MAC-399IF)

• MA Contact Terminal Interface (MAC-397IF)

• Wired Remote Controller (PAR-21MAA; requires MAC-397IF)

• Condensate Pump (230V; SI3100-230)

• Anti-allergy Enzyme Filter (Two pieces per set; MAC-408FT-E)

GENERAL FEATURES

• Wall-mounted indoor unit

• Standard Hybrid Catechin Prefi lter is included with indoor unit

• Quiet operation

• Choice of fan speeds: Quiet, Low, Medium, High, and Super High;

Auto fan speed control also included

• Wireless remote controller is included; PAR-21MAA wired

remote controller can be installed as an option

• Indoor unit powered from outdoor unit using A-Control

• Auto restart following a power outage

• Limited warranty: fi ve years on parts and defects and seven years

on the compressor

Indoor Unit: MSY-GE12NA

Wireless Remote

Controller

Outdoor Unit: MUY-GE12NA

Reference

Construction

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Mitsubishi Models