ERROR CODES – R410A

Black = All R410A

Red = FD Split 1, 2 Series R410A

Blue = KX4 & KXR4 Series R410A

(does not cover SRK & SCM MODELS)

Indoor Circuit Board

Outdoor Circuit Board

Error

Code

Red LED

Green

LED

Red LED

Green LED

Details of Fault

Stays Off

Keeps

Flashing

Stays Off

Keeps

Flashing

Normal operation.

Stays Off

Stays Off

Stays Off

Stays Off

No mains power detected [power off or power
failure].

L phase wire is open circuit.

No

indication

Flashes 3

times

Keeps

Flashing

Stays Off

Keeps

Flashing

Remote controller wires - X & Y connections are
reversed.

Remote controller wires - Y & Z connections are
reversed.

Remote controller wiring is open circuit. (X wire
broken - a beep is produced and no indication is
made. Z wire broken -no beep and no indication).

LCD

Flashes

continuou

sly or Off

Stays Off

Keeps

Flashing

Flashes

Twice

Keeps

Flashing

Open Circuit or poor indoor/outdoor interconnecting

wiring

Stays Off

Off or On

continuousl

y

Stays Off

Keeps

Flashing

Indoor circuit board or CPU failure.

Off or On
continuou

sly

Off or On

continuousl

y

Stays Off

Keeps

Flashing

Indoor circuit board or CPU failure.

Stays Off

Keeps

Flashing

Stays Off

Keeps

Flashing

In group control, power supply to at least one indoor

unit off

Remote controller wire Y is open circuit

Remote controller wires X and Y are reversed

Faulty Indoor or Remote controller PCB

Electrical noise interference

Stays Off

Keeps

Flashing

Stays Off

Keeps

Flashing

Remote controller wiring connected to A and B

A and B wiring connected in closed loop

Indoor unit PCB processor runs away

E1

Flashes 3

times

Keeps

Flashing

Stays Off

Keeps

Flashing

Remote controller wiring open circuit