Mitsubishi 930- User Manual
Mitsubishi 930– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
F930GOT Series (F93*GOT-BWD-E)
Installation Manual
JY992D95701E
T h i s m a nu a l c o n ta i n s tex t , d ia g ra m s a n d ex p la n a t i o n s w h ic h w i l l g u i d e th e r e a d e r in th e c o r r e c t
installation, safe use and operation of the F93*GOT-BWD-E and should be read and understood before
attempting to install or use the unit. Further information can be found in the associated manuals list below.
Specifications are subject to change without notice
Guidelines for the Safety of the User and Protection of the
F930GOT-BWD-E
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c)
All operators of the completed equipment should be trained to use that product in a safe and
co-ordinated manner in compliance to established safety practices.
Note:
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Note’s on the Symbols Used in this Manual
At various times through out this manual cer tain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger
WILL
cause physical and property damage.
2) Indicates that the identified danger could
POSSIBLY
cause physical and property
damage.
•
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
•
All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the
product based on these illustrative examples.
•
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific application.
Associated Manuals
~
Indispensable manual
|
Either manual is necessary.
Refer to the Programming manual (
ΙΙ
) or relevant hardware manuals for details concerning the applicable
PLC.
Manual Name
Manual Number
Description
|
F930GOT Series
(F93*GOT-BWD-E)
Installation Manual
JY997D95701
Describes the specifications, wiring, and
installation of F930GOT Series graphic operation
terminal. (hardware)
~
GOT-F900
OPERATION MANUAL
(describes GT Designer2)
JY997D09101
(separate volume)
Describes the operation and use of the GOT-
F900 Series graphic operation terminals and GT
Designer2.
~
GOT-F900 Series
Operation Manual
JY992D94701
(separate volume)
Describes the operation and use of the GOT-
F900 Series graphic operation terminals, GT
Designer and FX-PCS-DU/WIN-E.
~
GOT-F900 Series
Hardware Manual
(connection diagram)
JY992D94801
(separate volume)
Describes wiring and installation of the GOT-
F900 Series graphic operation terminals.
|
GT Designer2 Version1
Operating Manual
(PDF files on CD-ROM
included with product)
Describes the operation of GT Designer2
(SW*D5C-GTD2-E) and data transfer to the
GOT-900 Series.
|
GT Designer2 Version1
Reference Manual
(PDF files on CD-ROM
included with product)
Describes the specifications and setting of object
functions in GT Designer2 (SW*D5C-GTD2-E).
|
GT Designer
Operating Manual
Included with the
screen creation
software
Describes the operation of GT Designer
(SW*D5C-GOTR-PACKE) and data transfer to
the GOT-900 Series. (Refer to the help file)
|
FX-PCS-DU/WIN-E
SOFTWARE MANUAL
JY992D68301
(included with the
screen creation
software)
Describes the operation of FX-PCS-DU/WIN-E
screen creation software.
1. Introduction
The F930GOT-BWD-E (hereafter called “GOT or F930GOT”) is to
be mounted on the face of a control panel or operations panel,
a n d c o n n e c t e d t o t h e p r o gra m m i n g p o r t ( C P U p o r t ) o r t h e
communication por t (communication port) of a PLC.
Various devices can be monitored and PLC data changed via the
GOT screens. Several display screens are built-in to the GOT,
and additional personalized screens can be created by the user.
1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs
as well as a host of third par ty manufactured units. Fur ther
in fo r ma tio n c an b e fo un d in GOT-F 90 0 S er i es H a r dwar e
Manual.
2) PLC user programs can be downloaded, uploaded and
monitored using programming software GX-Developer or FX-
PCS/WIN-E on a personal computer via the GOT. Fur ther
information can be found in the GOT-F900 Series Operation
Manual.
3) Display screens are created using the following software.
1.1 Product Lists
Caution
During abnormal communication (including cable breakages) when monitor is executed within
the GOT, communication between the GOT and programmable controller CPU is interrupted.
It is then impossible to operate switches or devices in the PLC through the GOT.
Communication and normal operation resumes when the GOT system is correctly configured.
DO NOT configure emergency stop or safety features to operate through the GOT, and be
sure that there is no adverse consequences in the event of a GOT - PLC communications
malfunction.
Note;
•
Do not lay signal cables near high voltage power cables or allow them to share the same
trunking duct, otherwise, effects of noise or surge induction are likely to take please. Keep
a safe distance of more than 100 mm from these wires.
•
Operate touch switches on the display screen by hand.
DO NOT use excessive force, or attempt operate them with hard or pointed objects.
The tip of a screw driver, pen or similar object for example may break the screen.
Software Name
Version
GT Designer2
SW
D5C-GTD2-E
(
indicates version)
GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
GT Designer
SW
D5C-GOTR-PACKE
(
indicates version)
GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
SW1-H edition of SW1D5C-GOTR-PACKE or later
FX-PCS-DU/WIN-E
GOT-F900 Series (for Windows) screen creation software.
SW0PC-FXDU/WIN-E version 2.20 or later
Production Name
Description
F930GOT-BWD-E
Graphic operation terminal main unit
FX-50DU-CAB0
Communication cable (GOT
↔
CPU port in FX
0
, FX
0S
, FX
1S
, FX
0N
, FX
1N
, FX
2N
or FX
2NC
series PLC)
The connector on the GOT side is wired straight.
Cable length is 3m (9' 10").
FX-50DU-CAB0/EN
Communication cable (GOT
↔
CPU port in FX
0
, FX
0S
, FX
1S
, FX
0N
, FX
1N
, FX
2N
or FX
2NC
series PLC)
The connector on the GOT side is wired straight. Cable length is 3m (9' 10").
FX-50DU-CAB0-**M
Communication cable (GOT
↔
CPU port in FX
0
, FX
0S
, FX
1S
, FX
0N
, FX
1N
, FX
2N
or FX
2NC
series PLC)
The connector on the GOT side is wired straight.
** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"),
30M: 30m (98' 5")
FX-40DU-CAB
Communication cable (GOT
↔
CPU port in FX, FX
2C
, A or QnA series PLC)
The connector on the GOT side is wired straight. Cable length is 3m (9' 10").
FX-40DU-CAB-**M
Communication cable (GOT
↔
CPU port in FX, FX
2C
, A or QnA series PLC)
The connector on the GOT side is wired straight.
** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5")
QC30R2
Communication cable (GOT
↔
CPU port in Q series PLC)
The connector on the GOT side is wired straight. Cable length is 3m (9' 10").
FX-232CAB-1
Data exchange cable (GOT
↔
Personal computer <9-pin D-sub>)
FX
2NC
-32BL
Battery for Alarm history and current time data retention.
F9GT-30PSC
Transparent protection sheet for F930GOT (5 pieces)
F9GT-30LTB
Backlight for F930GOT
P L C
P r o g r a m m i n g
p o r t
G O T
1.2 Dimensions and Each Part Name
Dimensions: mm (inches)
MASS (Weight): 0.3 kg (0.66 lbs)
Accessory:
Mounting brackets, Tightening bolt (M3, 4 bolts),
Packing seal for dust and water resistance
a) Display
b) Mounting bracket and tightening bolt
c)
Communication ports
d) Communication cable
e) DC power supply terminal (M3)
f)
FX
2NC
-32BL battery
g) Packing seal
2. Specifications
2.1 General Specifications
Port
Description
RS-422
RS-422 por t for connecting PLC (including1:N connection) or communication
(computer link) unit <9-pin D-sub>
RS-232C
RS-232C port for connecting either a personal computer, printer, bar-code reader
or 1:N connection <9-pin D-sub>
Item
Specifications
Operating Temperature
0 ~ 50 °C (32 ~ 122 °F)
Storage Temperature
-20 ~ 60 °C (-4 ~ 140 °F)
Humidity
35 ~ 85% Relative Humidity, No condensation
Operating atmosphere
Must be free of lamp black, corrosive gas, flammable gas, or excessive
amount of electroconductive dust par ticles and must be no direct sunlight.
(Same as for saving)
Vibration Resistance
- intermittent vibration
10 ~ 57 Hz: 0.075 mm Half Amplitude
57 ~ 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Vibration Resistance
- Continuous vibration
10 ~ 57 Hz: 0.035 mm Half Amplitude
57 ~ 150 Hz: 4.9 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Shock Resistance
147m/s
2
Acceleration,
3 times in each direction X, Y, and Z
Noise Immunity
1000 Vp-p, 1micro second, 30 ~ 100 Hz, tested by noise simulator
Dielectric Withstand
Voltage
500 V AC > 1 min, tested between power terminals and ground
Insulation Resistance
5 M
Ω
> at 500 V DC, tested between power terminals and ground
Ground
Grounding resistance of 100
Ω
or less. (Class D)
Protection
IP 65F
1 4 6 ( 5 . 7 5 " )
4 9 ( 1 . 9 3 " )
5 ( 0 . 2 0 " )
65
(2
.5
6"
)
75
(2
.9
5"
)
a )
2 4 V D C
9 ( 0 . 3 5 " )
2 3 ( 0 . 9 1 " )
2 3 ( 0 . 9 1 " )
1 3 6 ( 5 . 3 5 " )
85
(3
.3
5"
)
75
(2
.9
5"
)
5 ( 0 . 2 0 " ) o r l e s s
d )
b )
c )
f )
e )
g )
9 ( 0 . 3 5 " )
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.