K00364 Electronic Bin Thermostat

Installation Instructions


This kit reduces overfill and condensation issues and can be used on any Manitowoc ice machine installed on an ice
dispenser. Order kit number K00336 for the following models IB0620, IB0820, IB1020, QF0400 and QF2300.

Control Settings

Flake/Nugget/Chiplet:
The control must be reset from the factory setting.
Refer to the jumper and control settings.


Ice Cube Machines:
The machines use the factory control settings.

The controller has a one-minute time delay anytime
power is interrupted and restored.

Positioning the Touchpad Jumpers


P5 Jumper

The P5 jumper position determines if the touchpad is
locked or unlocked. The control is factory locked; to
unlock, move the jumper from one pin to two pins.


P4 Jumper

The P4 jumper labeled Jump 1 is used to set the control
for heating or cooling mode. Jump 2 is used to
establish set point at either cut-in or cut-out.









Cubers

Flake/Nugget/Chiplet

Setting Control Set point Value


To view and adjust set point, follow these steps:

A.

Press MENU until the display flashes SP.

B.

Press MENU again to display the existing set
point value.

C.

Press up or down (arrows) to change the set
point value.

D.

Press MENU again to save the new value. The
display returns to the sensed temperature.

E.

If no setup entry is made for 30 seconds, the
control reverts to the normal temperature
display.


IMPORTANT:

If MENU is not pressed after changing the set point
value, the control reverts to the previously
programmed set point value.








RED
SENSOR
LEAD

BLACK
SENSOR
LEAD

JUMPER
LOCATIONS

MATCH
WIRING
TO ICE
MACHINE
VOLTAGE

BIN SWITCH OR

TOGGLE SWITCH

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 3 - WARNING; Fault Codes; Check for proper operation.

WARNING Line voltage is present inside control. Contact with line voltage can cause serious injury or death. Differential, Anti-Short Cycle Delay, Temperature Offset, or Sensor Failure Operation To set or verify the Differential, Anti-Short Cycle Delay, Temperature Offset or Sensor Failure Operation...

Page 5 - Universal Thermostat Kit; Installation Instructions; FOR USE WITH DISPENSERS ONLY; Remove all ice from dispenser.; Do; The control box line voltage wiring offers two options:; View A

Universal Thermostat Kit Installation Instructions FOR USE WITH DISPENSERS ONLY THIS CONTROL KIT IS INTENDED TO REDUCE OVERFILL AND CONDENSATION ISSUES 1. Remove all ice from dispenser. 2. Disconnect all power to the ice machine and dispenser at the service disconnect or fuse/breaker panel. 3. Move ...

Page 7 - View C; FACTORY PRESET

View C FACTORY PRESET TEMPERATURE CONTROL CODE SETTINGS AS FOLLOWS: Set Point - SP: 40 Differential - DIF: 1 Anti Short Cycle Delay - ASD: 1 Temperature Offset - OFS: 0 Sensor Failure Operation - SF: 1 - Cube 0 - Flake/Nugget/Chiplet Keypad Locked Out Jumper Position Red Lead Sensor Probe Black Lead...