Lochinvar SBN1000 - Manual
Lochinvar SBN1000 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
SYNC PUMP RECOMMENDATION TABLE
Temperature Rise
Temperature Rise
Temperature Rise
Temperature Rise
20°F
Δ
T
25°F
Δ
T
30°F
Δ
T
35°F
Δ
T
Boiler
Flow
Head
Pump
Flow
Head
Pump
Flow
Head
Pump
Flow
Head
Pump
Rate
Loss
Rate
Loss
Rate
Loss
Rate
Loss
SBN1000
GPM
Ft/Hd
N/A
GPM
Ft/Hd
PUM30001
GPM
Ft/Hd
PUM30001
GPM
Ft/Hd
PUM30001
55.0
31.0
44.0
22.0
38.0
18.0
32.0
13.0
Boiler
Flow
Head
Pump
Flow
Head
Pump
Flow
Head
Pump
Flow
Head
Pump
Rate
Loss
Rate
Loss
Rate
Loss
Rate
Loss
SBN1300
GPM
Ft/Hd
N/A
GPM
Ft/Hd
PUM30001
GPM
Ft/Hd
PUM30001
GPM
Ft/Hd
PUM30001
65.0
30.0
52.0
20.0
45.0
16.0
37.0
11.0
Boiler
Flow
Head
Pump
Flow
Head
Pump
Flow
Head
Pump
Flow
Head
Pump
Rate
Loss
Rate
Loss
Rate
Loss
Rate
Loss
SBN1500
GPM
Ft/Hd
N/A
GPM
Ft/Hd
PUM30001
GPM
Ft/Hd
PUM30001
GPM
Ft/Hd
PUM30001
74.0
33.0
60.0
23.0
51.0
18.0
42.0
12.0
This chart provides Pump recommendations for SYNC boilers for the Boiler Loop / Space Heating piping.
Based on specific Temperature Rises, this chart includes calculated Gallon Per Minute flow rate, calculated Foot Head Loss and recommended Pump.
The GPM, Ft/Hd and Pump selection is based on Primary / Secondary Boiler Loop piping of maximum 20 feet of straight pipe, 4 - 90° elbows and 2 - full port ball valves.
See the Installation and Operation manual for more details including pipe diameters and piping diagrams.
Reminder: The SYNC boiler requires TWO pump, one for each heating module.
The Pump recommendations listed above are for the individual heating module.