Lincoln 1600 Series - Manual

Lincoln 1600 Series

Lincoln 1600 Series – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
Page: / 4

Table of Contents:

  • Page 2 – Global; Lincoln Impinger; Easy to Operate
  • Page 3 – Gas Supply Pressure Recommendations:; Natural; Recommended Minimum Clearances:; All new impinger
  • Page 4 – GAS; GAS; GAS; GAS; GAS
Loading the manual

Global

1111 North Hadley Road
P.O. Box 1229
Fort Wayne, Indiana 46801-1229

Tel 1.260.459.8200
Fax 1.260.436.0735
E mail [email protected]
web www.lincolnfp.com

©2007 Lincoln Foodservice Products, Inc.
Printed in the U.S.A.
1256-2.5K-04/07-SP

Capacity Estimates | Pies Per Hour:

BAKE TIME

Pie Size

3 min.

3½ min.

4 min.

4½ min.

5 min.

5½ min.

6 min.

6½ min.

7 min.

12” (30 cm)

182

155

135

120

108

99

90

84

78

14” (36 cm)

115

99

87

88

69

63

58

53

50

16” (41 cm)

101

87

76

67

61

55

51

47

44

Ventilation Requirements:

Ventilation is required. Local codes prevail. These are the “authority having jurisdiction” as stated by the
National Fire Protection Association, Inc., in NFPA 96-1994. Estimates of CFM requirements can vary from
2400 to as high as 6000 CFM exhaust. In all cases the ambient temperature around the oven must not
exceed 95°F (35°C) when the oven is operating.

This information is shown as a guideline for ventilating

the Impinger

®

1600 Ovens.

18-24”

(457 mm -

610mm)

8”

(203 mm)

CAPTURE AREA

CAPTURE AREA

CAPTURE VELOCITY 50 FPM

CAPTURE

VELOCITY

50 FPM

78”

(1981 mm)

94” (2388 mm)

8”

(203 mm)

6”

(153 mm)

6”

(153 mm)

70” (1778 mm)

1. Dimensions shown are for ovens without long extension shelves.

The outside end of the conveyor

frame must be a minimum of eight (8) inches (203 mm) inside the canopy as shown.

2.

The capture velocity across the lower edge of the canopy is to be 50 FPM at sides and front.

3. Use filters at rear exhaust area of the hood, as shown. Do

not

just put an opening into a 4 sided canopy.

4. The ovens are to be centered in the canopy space left-to-right and front-to-back if possible.
5. A six (6) inch space at rear of oven is recommended for utilities.
6. Use of a Type I or Type II application and overall final installation is determined per local codes.
7.

Recommended 2400-3000 CFM exhaust

, typical, or higher per local codes; as a guideline to obtain

adequate capture velocity.

8.

Recommended 80% of make-up air provided outside of the canopy

through perforated metal dif-

fusers directed straight down...

not at the oven

; located at front , side or both.

9.

Room air diffusers must not be directed onto the oven and should be positioned a minimum of

three (3) feet from the perimeter of the hood to keep airflow from affecting the oven.

NOTE: Specifications subject to change without notification.

1600 S

er

ies | I

mpinger® L

ow P
rofile Single B

elt C

on

ve

yor

iz

ed O

ven

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Global; Lincoln Impinger; Easy to Operate

Global 1600 Series Impinger® Low Profile Single Belt Conveyorized Oven Lincoln Impinger ® Conveyor O vens are the premier continuous cook platform for the food ser vice industr y. Using the latest advancements in air impingement technology, Impinger ® O vens allow for rapid heating, cook ing, bak in...

Page 3 - Gas Supply Pressure Recommendations:; Natural; Recommended Minimum Clearances:; All new impinger

Global Gas Supply Pressure Recommendations: Gas Type Supply (Inlet) Pressure (mbar) Recommended Minimum Gas Pipe Size Natural 9-14” WC (2.2 kPA / 22.4 mbar - 3.5kPa / 34.9 mbar) 2” (51 mm) LP 11-14” WC (2.7 kPa / 27.36 mbar - 3.5 kPa / 34.9 mbar) 2” (51 mm) *Gas supply pressures are dependent on loc...

Page 4 - GAS; GAS; GAS; GAS; GAS

Global 91” (2311mm) 3/4” N.P.T. INLET w/Tee (19 mm) 120 VOLT 10 FT. LONG POWER CORD 3/4” N.P.T. (19 mm) UNION GAS DOOR SWING 80” (2032 mm) 18” (457 mm) 40” (1016 mm) 22” (585 mm) 7 1/2” (191 mm) 44 1/8” (1121 mm) 32 1/8” (816 mm) 7 1/2” (191 mm) 32 1/8” (816 mm) 51 3/8” (1305 mm) 63 3/8” (1610 mm) 5...

Other Lincoln Models

All Lincoln Other