Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.

How to Specify:

Unit

14.0 kVA

Battery

2,995 lbs.

Cabinet

(1,358 kg)

Electronics

465 lbs.

Cabinet

(211 kg)

Total System

3,460 lbs.
(1,569 kg)

L1PH Series Uninterruptible Power Supplies

L1PH

Page 1 of 2

14.0 kVA Single Phase UPS System

Job Information

Type:

Job Name:
Cat. No.:

Lamp(s):
Notes:

Lightolier

a Genlyte Thomas Company

www.lightolier.com

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504

Overall Characteristics

• 86% throughput efficiency
• Operating temperature range 32°F (0°C) to 104°F (40°C)
• Internal maintenance by-pass is standard
• Main load disconnect switch standard
• Double conversion, no interruption
• Standard backup time of 90 minutes, other run times optional
• Output circuit breakers and normally-off loads optional

Housing

• Free standing, NEMA 1 enclosure
• Acid resistant powder coat finish
• Multiple conduit entries

Metering/Controls

Standard
• Alpha-numeric front panel display with 14 metered measurements and

53 messages/alarms

• Normal, caution and alarm indicating LEDs
• Audible failure alarms with silence switch
• Dry contact for remote failure alarm
• “D” type 9-pin computer interface connector (see pin config. on back)
• Programmable battery monitor with alarm

Optional
• Diagnostics software for remote computer (PC) monitoring and control
• Stand-alone remote display mimics all measurements, indications and

alarms shown on the front panel display

• Additional RS-232 input/output port for remote monitoring and system

control

Electrical

• Sine Wave Output
• Completely solid-state Pulse Width Modulation (PWM) inverter
• 16-bit microprocessor control
• Input power factor correction maintains power factor at 0.99
• Transient response

5%; Recovery time, 10 mS (100% load step)

• 3:1 crest factor capability
• Inverter output distortion

2.5% THD (at unity power factor)

• Output voltage regulation ±6% of nominal at full load
• Frequency within ±0.05% of nominal
• Inverter efficiency

84%

• Load power factor capability is 0.5 leading to 0.5 lagging

(Continued on page 2)

NOTE:

Input circuit

breaker not available.
Input switch is
standard.

L1PH

I

14.0

S

SERIES

INPUT

SYSTEM

BASE

BATTERY

OUTPUT

OUTPUT

# ON 2ND

NORMALLY

# OF

NOL

VOLTAGE

TYPE

SIZE

TYPE

VOLTAGE

CKT BRKRS

1

VOLTAGE

OFF LOAD

NOL

VOLTAGE

L1PH = Single
Phase
Uninterruptible
Power
Supplies

14.0 = 14.0 kVa

2 = 208 V
3 = 240 V
4 = 277 V
Z = Special
Voltage

(Consult
Factory)

1 = 120 V
2 = 208 V
3 = 240 V
4 = 277 V
5 = 120/208 V
6 = 120/240 V
7 = 120/277 V
Z = Special
Voltage

(Consult
Factory)

Y = Hardwire
A = 1 0CB
B = 2 0CB
C = 3 0CB
D = 4 0CB
E = 5 0CB
F = 6 0CB
G = 7 0CB
H = 8 0CB
J = 9 0CB
K = 10 0CB
L = 11 0CB
M = 12 0CB
N = OCBA1
P = OCBA2
R = OCBA3
S = OCBA4
T = OCBA5
U = OCBA6
V = OCBA7
W = OCBA8
X = OCBA9

0
1
2
3
4
5
6
7
8
9

10
11

A = No
B = Yes
C = Yes w/ Time
Delay Timer

0 = No NOL
Y = Hardwire
Terminal
1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
6 = 6
7 = 7
8 = 8
9 = 9
10 = 10
11 = 11
12 = 12

X = None
A = 1st
B = 2nd

I = ETL Listed
to UL 924 for
Emergency
Lighting
Applications

S = Sealed
Lead Calcium

34.0”

86.4 cm

33.0”

83.8 cm

70.0”

177.8 cm

Battery

Cabinet

33.0”

83.8 cm

30.0”

76.2 cm

43.5”

110.5 cm

Electronics

Cabinet

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.