Lifebreath 850FD/DD - Manual
Lifebreath 850FD/DD – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 3 – ERV Questions & Answers; Is an ERV better than an HRV?; Here's a list of characteristics of the fixed plate core.; Can the core become clogged with dust?
- Page 5 – Selecting the Correct Size HRV/ERV; Commercial and Institutional Requirements
- Page 6 – OPTIONS; SPECIFICATIONS; TEMPERATURE EFFECTIVENESS; PERFORMANCE
- Page 9 – Sixty Minute Remote Timer
- Page 13 – NOTE: Fully insulated ducting with an integral; HRV CABINET; Forming the “P” Trap
- Page 14 – Outside Weatherhoods; ground level; Ducting from the Weatherhoods
- Page 15 – Figure A and B; TECHGRILLE
- Page 16 – Figure A; The Integrated HVAC System
- Page 17 – Various Installation Types; Figure 7A; Figure 7B; Figure 7C
- Page 18 – Electrical Connections; FAN DEFROST; Electrical Connection
- Page 19 – DEHUMIDISTAT VENTILATION; Speed Selection and Controls; DEHUMIDISTAT; Optional Remote Controls; 0 MINUTE CRANK TIMER
- Page 20 – OPTIONAL REMOTE CONTROLS; AIR SENTRYTM AIR QUALITY SENSOR; If a PVC or Air Sentry is used, connect; PROGRAMMABLE VENTILATION CONTROLLER (PVC); Connects to; RED; and; YELLOW; VENTILATION DEHUMIDISTAT; *See individual control instructions for more details.
- Page 21 – Glossary
- Page 22 – To select mode of operation for ControlAir 15; Modes of Operation; OFF; No LED’s illuminated; To select speed
- Page 23 – Excessive positive pressure; Excessive negative pressure; BALANCING PROCEDURE; CROSS SECTION AREA; Pitot tube and gauge; PITOT TUBE AIR FLOW BALANCING
- Page 24 – MOTOR; CORE; HRV CORE; When reinstalling; ERV CORE
- Page 25 – FILTERS; CONDENSATE DRAINS; General Maintenance
- Page 26 – TROUBLESHOOTING YOUR HRV/ERV SYSTEM; SYMPTOM
- Page 27 – DEFROST DETAILS; AUTO-TRANSFORMER DETAIL
- Page 28 – Remote Switching; UNITS ONLY
- Page 30 – • 2 Year Limited Warranty • 15 Year Aluminum Core Warranty; NUTECH
* LEAVE FOR HOMEOWNER
NOTE: Due to ongoing research and product development, specifications,
ratings and dimensions are subject to change without notice.
OPERATION AND
INSTALLATION MANUAL
®
C L E A N • F R E S H • A I R
NOTE: ALTHOUGH SOME MODELS
DIFFER IN OPERATION, THE BASIC
STEPS ARE SIMILAR.
CAUTION
Before installation, careful consideration must be given to
how the system will operate if connected to any other piece
of mechanical equipment, i.e. a forced air furnace or air
handler, operating at a higher static. After installation, the
compatibility of the two pieces of equipment must be
confirmed, by measuring the airflow’s of the Heat/Energy
Recovery Ventilator (HRV/ERV), by using the balancing
procedure in this manual.
It is always important to assess how the operation of any
HRV/ERV may interact with vented combustion equipment
(ie. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
NEVER
install an HRV/ERV in a situation where its normal
operation, lack of operation or partial failure may result
i n t h e b a c k d r a f t i n g o r i m p r o p e r f u n c t i o n i n g o f v e n t e d
combustion equipment!!!
TI-72C-NE
0105
Installing Contractor
Telephone / Contact
Serial Number
Installation Date
Model
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION
For Models:
500DCS
ControlAir 15
850FD/DD
Analog Controls
700FD/DD
Analog Controls
1200FD/DD
Analog Controls
500ERV
ControlAir 15
700ERV
Analog Controls
1200ERV
Analog Controls
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
3 ERV Questions & Answers What is the difference between an HRV and an ERV? T h e c o r e i n a n H R V ( H e a t R e c o v e r y V e n t i l a t o r ) transfers heat from one air stream to the other. This iscalled sensible heat. The term ERV (Energy RecoveryVentilator) is usually used to descri...
5 MAKE UP HEAT REQUIREMENT at 1200 CFM (566L/s) Nominal Nominal Nominal Outdoor Temp. kW Req. for kW Req. for kW Req. for C° F° 20°C (68°F) 25°C (77°F) 30°C (86°F) Air Delivery Air Delivery Air Delivery 0 32 7 10 14 -10 14 10 14 17 -20 -4 12 15 19 -30 -22 15 19 22 -40 -40 17 21 24 Selecting the Corr...
6 OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min. (3 wire) 99-105 Programmable Ventilation Control includes Programmable Time Clock, Dehumidistat and Air Sentry™ 99-109 Air Sentry ™ Air Quality Monitor designed to accept remotely mounted Control Pad 99-250 Ventilation Dehumidistat - Dehumidi...