Page 5 - Mechanical Data; Liebert UPStation STM SITE PLANNING DATA
5 Heat Rejection at Full Load BTU / HR 2170 2411 3616 4520 5062 7593 Weight Including Battery (lbs.) 270 270 560 560 560 780 Mechanical Data Dimensions in Inches WxDxH 9x31x29 9x31x29 18x27x29 9x31x29 9x31x29 27x27x29 UPS Output Circuit Breaker (Amps) 30 A 30 A 100 A 100 A 100 A 125 A Full Load Curr...
Page 6 - INTRODUCTION; Optional System Components; UNLOADING THE UPS
6 INTRODUCTION The Liebert UPStation S™ Uninterruptible power supply(UPS) system protects valuable equipment, data, andprocesses from utility power disturbances. The high-performance, on-line, microprocessor-controlled designensures clean, regulated, sinewave power to loadsregardless of utility powe...
Page 7 - INSTALLATION; See the figure to the right for connection locations.; REAR VIEW
7 INSTALLATION Read Operation section to understand user controls anddisplayed messages before beginning. Operate UPS in a clean, controlled environment withadequate airflow.Exposure to excessive dirt or dust adversely affects UPSoperation. Internal fans cool the UPS. The unit intakes air at the fro...
Page 8 - Unit Installation; Terminal
8 3.5-6 kVA Start-up Checklist 1. Remove POD from box. Set aside the two UPS battery fuses inside the user manual packet for laterinstallation. Steps 2 – 4 apply to UPS Hardwire Input / Outputconnections ONLY.For standard plug connections, skip to step 5. 2. Note conduit knockouts on unit side. Remo...
Page 10 - -18kVA Single Line Diagram
10 8 - 18 kVA Start-Up Checklist 1. Open (turn OFF) UPS Output Circuit Breaker.2. Open (turn OFF) customer supplied distribution circuit breakers. 3. Turn OFF critical loads and plug them into output distribution units or customer-supplied distribution. 4. Turn ON battery circuit breaker on rear of ...
Page 11 - OPERATION; ESC; NORMAL OPERATION; Press for Menu; OFF
11 OPERATION Control / Display PanelThe control panel includes tactile pads (dome buttons) anda menu-driven LCD (liquid crystal display). The displayprovides full metering, present status, and alarms, if any.See figure on right. Control ButtonsON Button - This button turns on the UPS inverter. Itsup...
Page 13 - LCD MENU TREE
13 LCD MENU TREE MAIN MENU Configuration Review Change Settings UPS Meters Event Log Test Options Power Management UPS RATINGINPUT VOLTAGEINPUT FREQUENCYOUTPUT VOLTAGEOUTPUT FREQUENCYLOW BATTERY WARNING TIMEAUTO BATTERY TEST SETTINGSTOTAL UPS RUNTIMEADVANCE CONFIGURATION Input WiringOutput WiringTim...
Page 15 - Maintenance Bypass Operation; With UPS in bypass, rotate the unit Maintenance; Press the UPS OFF Button twice. Utility power now; kVA Startup Checklist.; UPS begins start-up and the manual bypass alarm; UPS display indicates ”Start up test warning: check; Wait for the UPS display to indicate ”Normal; System Shutdown
15 Maintenance Bypass Operation on 3.5 - 6 kVA Units The POD includes a Maintenance Bypass Switch thatallows UPS removal for service or maintenance withoutinterrupting power to the loads. Transferring from UPS Operation to MaintenanceBypass Operation1. Transfer UPS to manual bypass operation via swi...
Page 16 - OPTIONS; NOTES
16 OPTIONS Contact your Liebert UPS distributor for option availability and ordering information. DistributionConfigurable Distribution (CD)An optional enclosure hardwires to 3.5 - 12 kVA units and accommodates up to eight Standard or Power Management LoadModules. It may be wall or floor-mounted and...
Page 17 - Standard Load Module; Hardwire Load Module
17 Load ModulesLoad Modules for 3.5 to 12 kVA units offer a variety ofpower receptacles when used in conjunction with theConfigurable Distribution. Each Load Module includes: 1. Circuit Breaker2. Green output receptacle(s) power indicator3. 1 or 2 Output Receptacles. Hard Wire (terminal block) Load ...
Page 18 - Maintenance Bypass 8 - 18kVA; Approximate Weights in Pounds; A locking handle prevents unauthorized; Modes of Operation
18 Maintenance Bypass 8 - 18kVA The Liebert UPStation S™ Maintenance BypassCabinet allows the customer to completely isolatethe UPS for repair and/or preventivemaintenance. A rotary switch provides a make-before-break system that enables a transfer toand from maintenance bypass withoutinterruption t...
Page 20 - Remove the banding from the container; Mounting; Note: All dimensions are in inches
20 INSTALLATION This section includes unloading, inspection, mounting and connections for the maintenance bypasscabinets. Reading this section in its entirety before you begin is a good preparation for your start-up. UNLOADING The unit is shipped on a box that is banded downto a pallet. To unload th...
Page 21 - -18 kVA UPS Connections; Input and Output Power wiring must be run in separate conduit.
21 8-18 kVA UPS Connections The 8-18 kVA Liebert UPStation S™ allows the customerto connect a three-phase input if desired. The only benefitto connecting a third phase is to balance a three-phasefeed transformer. The 8-18 kVA Liebert UPStation S™ has two basicconnections; UPS Input and UPS Output. B...
Page 22 - -18 kVA Maintenance Bypass Connections; The input to the maintenance bypass comes from the
22 Input and output terminal blocks are provided on the back of the 8-12 kVA Liebert UPStation S™ as illustrated below. Conduitcan be landed on the rear or bottom of the UPS. Note that side, rear, front and top access is required for service on all LiebertUPStation S™ product lines. Input and output...
Page 27 - Define Parameters
27 POWER MANAGEMENT SAMPLE #1 Objective: Save energy by turning OFF computers afterhours. Specifically, turn ON all loads except load 03 at7:00 a.m. and then turn them OFF at 6:00 p.m. everyworkday (M-F). Remain off during the weekend. Define ParametersStartLoads: #1,2,4Action: Turn ON loadsEvent: T...
Page 28 - Communications Options
28 Remote Emergency Power Off (REPO) Cable This optional 50-foot cable includes the attached mattingconnector for connection to the UPS. The REPOconnector is at the rear of the unit. The factory suppliedswitch provides a normally open (N.O.) contact rated for 1Amp at 24 Volts. Pressing the REPO butt...
Page 29 - Cables; An optional factory-assembled 6-foot cable enables
29 Use the following Modem Mode configuration screen tocontrol modem operations: Modem Mode: IN1-(000) 000-0000Site ID:Your Location The options of the first line of this screen are IN, OUT,BOTH, or OFF. IN calls are from a remote terminaloperator to the UPS. OUT calls are alarms reported fromthe UP...
Page 32 - APPENDIX; NEC Wire Gauge Chart
32 APPENDIX NEC Wire Gauge Chart Allowable Ampacities of Insulated Conductors Rated 0 – 2000 Volts, 60° to 90°C (140° to 194°F), not more than three conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F) *Unless otherwise specifically permitted elsewhe...
Page 34 - – 8 kVA Battery Run Times
34 6 – 8 kVA Battery Run Times UPStation S 6 kVABattery Run Times #1 Runtime (mins. ) 400 350 300 250 200 150 100 50 0 Internal Batteries+(1) VBD061 Cabinet Internal Batteries+(1) VBS062 Cabinet Internal Batteries+(1) VBS 061 Cabinet Internal BatteriesOnly PERCENT LOAD 25 50 75 100 UPStation S 6 kVA...
Page 35 - 0 – 12 kVA Battery Run Times
35 10 – 12 kVA Battery Run Times UPStation S 10 kVABattery Run Times #1 Runtime (mins. ) 400 350 300 250 200 150 100 50 0 Internal Batteries+(1) VBS122 and (1)VBD121 Cabinet Internal Batteries+(1) VBD121 Cabinet Internal Batteries+(1) VBS122 Cabinet Internal Batteries Only PERCENT LOAD 25 50 75 100 ...
Page 36 - 8 kVA Battery Run Times
36 18 kVA Battery Run Times UPStation S 15 kVABattery Run Times #1 Runtime (mins. ) 160 140 120 100 80 60 40 20 0 Internal Batteries+(1) VBD181 Cabinet Internal BatteriesOnly PERCENT LOAD 25 50 75 100 UPStation S 15 kVABattery Run Times #2 Runtime (mins. ) 480 420 360 300 240 180 120 60 0 Internal B...
Page 37 - Alarm Messages, Meanings, and Corrective Actions
37 Alarm Messages, Meanings, and Corrective Actions MESSAGE MEANING CORRECTIVE ACTION Start-Up Sequence Aborted The UPS detects a condition that prevents acomplete start-up. Review and record all alarm messages. Performprescribed action for specified alarm. If Start upstill aborts, contact Liebert a...
Page 38 - The Company Behind The Products; Power Protection; UPStation
U.S.A. 1-800-222-5877 Worldwide Support 614-841-6755 U.K. +44 (0) 1793 553355 France +33 (0) 1 43 60 01 77 Germany +49 89 99 19 220 Italy +39 2 98250 1 Netherlands +31 (0) 475 503333 E-mail [email protected] Web site http://www.liebert.com Worldwide FAX tech support +614-841-5471 The Company Behin...