Page 3 - TABLE OF CONTENTS
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.0 I NTRODUCTION ....
Page 4 - ii; FIGURES
ii 9.0 V OLTAGE P ROGRAMMING P ROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 10.0 M AINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 10.1 Cleaning the UPS . . . . . . . . . . . ...
Page 5 - SAVE THESE INSTRUCTIONS; install or operate this UPS.; Battery Replacement; WARNING; supply socket outlet with an earth/ground connection.; CAUTION; cloth is recommended to remove dust from the surface of your UPS.; WARNING
1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions that should be followed during the installation and maintenance of the UPS and batteries. Please read this manual thoroughly before attempting to install or operate this UPS. ! WARNING SAFET...
Page 6 - 000VA models to the mains supply.; Electromagnetic Compatibility; —The PowerSureTM PSI series complies with the requirements of; mended type of battery listed in; Table 3
2 CONDITIONS OF USE: The mains supply socket must be within 2m (6.5 ft.) of the UPS and be eas- ily accessible.Your UPS provides conditioned power to connected equipment. This product is designed for Commer- cial use only. It is not intended for use with life support and other designated “critical” ...
Page 8 - Introduction; NTRODUCTION; Specifications; when used in conjunction with Liebert’s MultiLink; Figure 1
Introduction 4 2.0 I NTRODUCTION Congratulations on your choice of the Liebert PowerSure™ PSI Uninterruptible Power Supply (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.Upon generation, AC power is clean and stable. However, during transmission it ma...
Page 9 - Figure 2
Introduction 5 Figure 2 1000 and 1440VA PSI—rear view Figure 3 2200 and 3000VA PSI—rear view PHONE / FAX / MODEM / NETWORK PROTECTION BATTERYCONNECTOR1440VA/DC 48V/30A1000VA/DC 48V/20A 1234 INTELLISLOT INPUT BREAKER PUSH TO RESET + - LOAD 2 INPUT LOAD 1 IN OUT REPO RS-232 Data Line Connectors Circui...
Page 10 - Major Components; AJOR; Figure 4; Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters; line and keep the sensitive equipment protected.; Relay; Input
Major Components 6 3.0 M AJOR C OMPONENTS Figure 4 Line diagram of PowerSure PSI 1000VA & 1440VA Figure 5 Line diagram of PowerSure PSI 2200VA & 3000VA 3.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters These UPS components provide surge protection and filter both electromagn...
Page 11 - Automatic Voltage Regulator; mains voltage fluctuations without utilizing the batteries.; Battery Charger
Major Components 7 3.3 Automatic Voltage Regulator The Automatic Voltage Regulator (AVR) protects connected equipment from power spikes, sags and other abnormalities by raising (boosting) or lowering (bucking) the output voltage as needed. This keeps the UPS output voltage within the connected equip...
Page 12 - What’s Included; HAT; The PowerSure PSI is shipped with the following items:
What’s Included 8 4.0 W HAT ’ S I NCLUDED The PowerSure PSI is shipped with the following items: • PowerSure PSI user manual• MultiLink software CD• MultiLink serial cable, 3m (10 ft)• USB cable, 1.8m (6 ft)• RJ-11 cord, 2.1m (7 ft)• Rack mount handles• Support base• Fixed rails• Mounting hardware (...
Page 13 - Installation; NSTALLATION; Preparation; or Liebert representative.; or; Rack-Mount UPS Conversion; Tower UPS Installation; Figure 6; The UPS is heavy (see; Table 4 - Battery cabinet specifications; when lifting or moving it.; NOTE; UPS operation in temperatures above 25°C (77°F) reduces battery life.
Installation 9 5.0 I NSTALLATION 5.1 Preparation 1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative. 2. Decide where to place the PowerSure PSI. Install the UPS indoors in a controlled environment where it cannot be accidental...
Page 14 - Rack-Mount UPS Conversion and Installation; Figure 7; the inner members to their outermost position (see; Figure 8; used to move the UPS into and out of the rack.; lowest possible rack position.
Installation 10 5.3 Rack-Mount UPS Conversion and Installation 1. For fixed rail installations, install the rack mount handles using four (4) M4x6 screws (see Figure 7 ). Figure 7 Rack mount handles 2. Unpack the two fixed rail assemblies and mounting hardware. Loosen the wing nuts and extend the in...
Page 15 - Figure 9
Installation 11 4. Attach the two (2) fixed rails to the racks mounting rails. The fixed rail assemblies fit on the inside of the rack mounting rails. 5. Insert two (2) M5 flat head screws loosely (finger-tight) into the top and bottom holes on the front of the fixed rail assembly (see Figure 9 ). 6...
Page 16 - Option 1 - Serial Communications; Option 2 - Contact Closure Communications; manual, are on the CD included in the PowerSure PSI package.; Option 3 - USB Communications; Windows XP and 2000 and Mac OS 10.2 or later (see; Option 4 – Intellislot; munications operate in parallel.; connection
Installation 12 15. Connect Phone/Fax/DSL/Network/Modem devices to data line connectors. 16. Communication options (see 8.0 - Communications for details): Option 1 - Serial Communications Serial communications provides parametric data, for example, input voltage and battery voltage.a. Connect MultiL...
Page 17 - Figure 10 REPO switch connections; External Battery Cabinet Installation; and your local dealer or Liebert representative.; Steps 1; through; Table 5 - Battery run times
Installation 13 Figure 10 REPO switch connections 5.4 External Battery Cabinet Installation Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath...
Page 18 - Controls and Indicators; ONTROLS; until a new alarm condition is detected.; OFF Button; will shut down the UPS. An audible alarm sounds briefly.
Controls and Indicators 14 6.0 C ONTROLS AND I NDICATORS 6.1 ON/Alarm Silence/Battery Test Button This button controls output power to connected load(s) and has three functions: • On• Alarm Silence• Battery Test ON —When the UPS is Off, pressing the ON/Alarm Silence/Battery Test button for more than...
Page 19 - Figure 11 Load level indicators—4 green, 1 amber; pensate for a high mains voltage condition (see
Controls and Indicators 15 6.3 Voltage Programming Button The PowerSure PSI contains a Voltage Programming button that allows the operator to select the nominal mains voltage. This setting changes the mains transfer points (low and high) of the UPS and the nominal output voltage when operating in Ba...
Page 20 - Over Temp Indicator—Amber; shooting; Fault Indicator—Red; bleshooting
Controls and Indicators 16 6.9 Over Temp Indicator—Amber The Over Temp Indicator flashes when the UPS detects an over temperature condition. This indicator illuminates when the UPS shuts down due to an over temperature condition (see 11.0 - Trouble- shooting for details). 6.10 Fault Indicator—Red Th...
Page 21 - Modes of Operation; ODES; Normal Mode; Figure 13 Normal mode operation with 26-50% load; green when the UPS is operating in Boost mode (see
Modes of Operation 17 7.0 M ODES OF O PERATION 7.1 Normal Mode During Normal mode operation, the PowerSure PSI supplies conditioned, computer-grade power to the connected equipment: mains power passes through the TVSS circuitry and the EMI/RFI filters and then through the Inverter (1000VA & 1440...
Page 22 - Battery Mode; shows the; Figure 15 Battery mode at 61 – 80% battery capacity; For more information, refer to; Figure 16 Low Battery mode; For approximate battery run times, refer to; . These run times are; Battery Recharge Operation; Battery Indicator
Modes of Operation 18 7.3 Battery Mode The UPS switches to Battery mode in the event of an extreme input voltage/frequency condition or complete mains failure. The battery system supplies power through the Inverter (1000VA & 1440VA) or through the DC-to-DC converter to the Bi-Directional Convert...
Page 23 - Communications; OMMUNICATIONS; tions using Liebert ESP II protocol.; Remote Shutdown Via the DB-9 Connector; ware, the UPS remains Off until a manual restart.; Table 1; Assignment Description; UPS TxD; Pin Assignment
Communications 19 8.0 C OMMUNICATIONS 8.1 DB-9 Connector The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer system running MultiLink software. The DB-9 is capable of supplying serial communica- tion, on battery and low battery signals. MultiLin...
Page 24 - USB Interface Port; The PowerSure PSI is equipped with an Intellislot; OCWEBCARD disables the Serial Communications of the DB-9.
Communications 20 8.3 USB Interface Port The PowerSure PSI has a USB interface port for communication that will work with the built-in Microsoft Power Manger software on the user’s PC, if so equipped. It will provide UPS status and manages the automatic orderly shutdown of the computer. The UPS’s US...
Page 25 - Voltage Programming Procedure; OLTAGE; Figure 17 Load Level Indicators; Indicator is flashing.; Mains power will be applied to the
Voltage Programming Procedure 21 9.0 V OLTAGE P ROGRAMMING P ROCEDURE Figure 17 Load Level Indicators 1. Remove the front bezel from the UPS.2. UPS must be operating in Normal (AC) mode. 3. The AC Input, Load, and Battery Level Indicators should be lit. 4. Press the Voltage Programming button for at...
Page 26 - Maintenance; AINTENANCE; Cleaning the UPS; The following will help ensure trouble-free operation for years:; Maintaining Batteries; appropriate replacement battery kit part number and pricing.; Battery Replacement; your local dealer or Liebert representative immediately.
Maintenance 22 10.0 M AINTENANCE The PowerSure PSI UPS requires very little maintenance. Follow these practices to prevent prob- lems. 10.1 Cleaning the UPS The following will help ensure trouble-free operation for years: • Vacuum dust from the ventilation intake occasionally.• Wipe the cover period...
Page 27 - Internal Battery Replacement Procedure; Figure 18 Battery replacement procedure
Maintenance 23 10.3.1 Internal Battery Replacement Procedure 1. Gently remove the front plastic bezel cover from the UPS.2. Loosen and remove the five (5) screws on the front cover plate. Lay the cover plate aside for reassembly. 3. Loosen and remove four (4) screws on battery bracket.4. Disconnect ...
Page 28 - Troubleshooting; ROUBLESHOOTING; Table 2 - Troubleshooting chart; for suggested remedy.; Figure 19 Status indicators; problem persists, refer to; Table 2; All indicators illuminated
Troubleshooting 24 11.0 T ROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the PowerSure PSI experiences a problem. Use this information to determine whether external factors caused the problem. See Table 2 - Troubleshooting chart for suggested remedy...
Page 29 - Problem
Troubleshooting 25 Table 2 Troubleshooting chart Problem Cause Solution UPS will not start Short circuit Check the circuit protector on the rear of the UPS. If it is tripped, reset it and restart the UPS. For further help, contact your local dealer, Liebert representative or the Liebert Worldwide Su...
Page 30 - PECIFICATIONS
Specifications 26 12.0 S PECIFICATIONS Table 3 UPS specifications Model Number PS1000RT2-230 PS1440RT2-230 PS2200RT2-230 PS2200RT2-230E PS3000RT2-230 PS3000RT2-230E Power Rating, VA/W 1000VA/750W 1440VA/1080W 2200VA/1650W 3000VA/2250W Dimensions, W x D x H, mm (in) Unit 87 x 557 x 430 (3.43 x 22 x 1...
Page 31 - Table 4
Specifications 27 Agency Safety EN 62040-1-1; TUV/GS listed; CE compliance mark Surge EN61000-4-5, Level 3, Criteria B ESD EN61000-4-2, Level 3, Criteria B Susceptibility EN61000-4-3, Level 3, Criteria A Electrical Fast Transient EN61000-4-4, Level 4, Criteria A Emissions EN 50091-2, Class B Conduct...
Page 32 - Table 5
Specifications 28 Table 5 Battery run times Load% 1000VA 1440VA 2200VA 3000VA Internal Battery (minutes) 5% 174 138 171 177 10% 118 79 73 91 20% 65 45 47 47 30% 41 28 26 28 40% 37 24 23 22 50% 26 16 16 16 60% 24 14 13 14 70% 18 10 10 10 80% 16 9 8 9 90% 12 6 6 7 100% 11 5 5 6 Internal Battery + 1 Ex...
Page 34 - Via Leonardo Da Vinci 8; OWER; PowerSure PSITM; SER
The Company Behind the Products With over a million installations around the globe,Liebert is the world leader in computer protectionsystems. Since its founding in 1965, Liebert hasdeveloped a complete range of support andprotection systems for sensitive electronics: • Environmental systems—close-co...